AS/NZS 3008.1.2:2017
The cable selection standard for New Zealand. AmpSize uses it for conductor data: current ratings, resistance and reactance, the derating factors for the route, and the short-circuit k factor.
Notes
- Edition cited
- AS/NZS 3008.1.2:2017
- Amendments applied
- No amendment named in the source (16 tables)
- Tables last checked
- 26 Sept 2026 (first 19 Sept 2026)
- Tables
- 16: 16 verified
- Clauses
- 6
No text of the standard is reproduced here. AmpSize is a design aid. Verify results against the current standard.
Contents (22)
Clauses (6)
Groups of circuits in underground wiring enclosures
The cable size tool names this clause on a group of circuits in underground enclosures. The clause names Tables 26(1) and 26(2), which the tool reads for one cable per duct. For a duct that holds the whole circuit, Table 3(4) sends circuits that share one enclosure to Table 22. There the tool takes the lower of the Table 26(2) and Table 22 factors and names the table it read.
Tools that read it:
Third harmonic current in the neutral
The cable size tool reads this clause once you enter a third harmonic percentage on a three-phase circuit. It prints the neutral current the harmonic produces, applies the Table 2 reduction factor, and names the clause beside the step so you can check the sizing basis the clause sets. The correction factors tool does the same.
Tools that read it:
Cable size calculator, Correction factor calculator and Harmonics, neutral current and K-factor.
Cited by 1
Voltage drop method
The voltage drop and voltage rise tools use this method. Resistance and reactance are combined at the power factor to give millivolts per amp metre. That figure is then multiplied by the current and the route length.
Tools that read it:
Cited by 11
- Voltage rise on a long rural PV run of 80 m
- Voltage rise for a 10 kW three-phase inverter
- Voltage drop single phase vs three phase
- Voltage drop on 2.5 mm² over 30 m
- Submain voltage drop estimate for a 160 A tender
- 24 V DC voltage drop on an instrument loop
- Total voltage drop: mains, submain and final
- Voltage rise for a 5 kW solar inverter cable
- AS/NZS 3000 Clause 3.6.2: voltage drop limit
- Voltage drop with the mV/A·m method
- Voltage drop basics
Voltage drop with an unbalanced load
The voltage drop tool switches to Equation 4.6 of this clause once you enter a neutral current on a three-phase circuit. It then works on a single-conductor basis and prints the neutral drop as its own step, each conductor over its own length.
Tools that read it:
Short-circuit performance
The fault rating tool works to this clause. It compares the energy let through by the protective device with the energy the conductor can take. The check uses the fault current, the clearing time and the k factor.
Tools that read it:
Cited by 7
- Switchboard fault rating at 25 kA for 1 s
- Consumer mains fault withstand for 16 mm² copper
- AS/NZS 3008.1.2 Table 52: the k factor
- AS/NZS 3008 vs BS 7671: cable sizing compared
- Prospective fault current at a main switchboard
- IB ≤ IN ≤ IZ: the overload rule on a 32 A circuit
- Short-circuit withstand and the k factor
Short-circuit duration
The fault rating tool names this clause when the clearing time you enter is longer than the 5 s the clause covers. The result still prints, with a warning that the cited basis stops at 5 s.
Tools that read it:
Cited by 1
Tables (16)
Reduction factors for harmonic currents in 4- and 5-core cables
The correction factors tool reads the reduction factor for third harmonic current in a four-core or five-core cable. Above 33 %, it sizes on the neutral current. The harmonics tool reads the same band from a spectrum.
Verified: read against the printed standard, pages 27–28. Checked 24 Sept 2026.
Tools that read it:
Correction factor calculator and Harmonics, neutral current and K-factor.
Current ratings, single-core cable, two cables per circuit, thermoplastic 75 °C
The cable size tool reads the printed rating here for single-core thermoplastic cable on a single-phase circuit, in copper or aluminium, for each installation method.
Verified: read against the printed standard, pages 35–37. Checked 24 Sept 2026.
Tools that read it:
Cited by 10
- Worked examples index by tool and trade
- Hot water cylinder cable size for a 3 kW element
- Cable size for a 20 A heat pump circuit in summer
- AmpSize vs jCalc vs free cable sizing tools
- EV charger cable size for a 7 kW 32 A circuit
- AS/NZS 3008.1.2 Tables 4 to 21: current ratings
- AS/NZS 3008 vs BS 7671: cable sizing compared
- Motor full load current: 11 kW 400 V DOL
- Cable size for a 32 A single-phase 25 m run
- Current-carrying capacity and derating
Current ratings, single-core cable, two cables per circuit, cross-linked 90 °C
The cable size tool reads the printed rating here for single-core cross-linked cable on a single-phase circuit, in copper or aluminium, for each installation method.
Verified: read against the printed standard, pages 38–40. Checked 24 Sept 2026.
Tools that read it:
Cited by 10
- Worked examples index by tool and trade
- Hot water cylinder cable size for a 3 kW element
- Cable size for a 20 A heat pump circuit in summer
- AmpSize vs jCalc vs free cable sizing tools
- EV charger cable size for a 7 kW 32 A circuit
- AS/NZS 3008.1.2 Tables 4 to 21: current ratings
- AS/NZS 3008 vs BS 7671: cable sizing compared
- Motor full load current: 11 kW 400 V DOL
- Cable size for a 32 A single-phase 25 m run
- Current-carrying capacity and derating
Current ratings, single-core cable, three cables per circuit, thermoplastic 75 °C
The cable size tool reads the printed rating here for single-core thermoplastic cable on a three-phase circuit, in copper or aluminium, for each installation method.
Verified: read against the printed standard, pages 44–46. Checked 24 Sept 2026.
Tools that read it:
Cited by 10
- Worked examples index by tool and trade
- Hot water cylinder cable size for a 3 kW element
- Cable size for a 20 A heat pump circuit in summer
- AmpSize vs jCalc vs free cable sizing tools
- EV charger cable size for a 7 kW 32 A circuit
- AS/NZS 3008.1.2 Tables 4 to 21: current ratings
- AS/NZS 3008 vs BS 7671: cable sizing compared
- Motor full load current: 11 kW 400 V DOL
- Cable size for a 32 A single-phase 25 m run
- Current-carrying capacity and derating
Current ratings, single-core cable, three cables per circuit, cross-linked 90 °C
The cable size tool reads the printed rating here for single-core cross-linked cable on a three-phase circuit, in copper or aluminium, for each installation method.
Verified: read against the printed standard, pages 47–49. Checked 24 Sept 2026.
Tools that read it:
Cited by 10
- Worked examples index by tool and trade
- Hot water cylinder cable size for a 3 kW element
- Cable size for a 20 A heat pump circuit in summer
- AmpSize vs jCalc vs free cable sizing tools
- EV charger cable size for a 7 kW 32 A circuit
- AS/NZS 3008.1.2 Tables 4 to 21: current ratings
- AS/NZS 3008 vs BS 7671: cable sizing compared
- Motor full load current: 11 kW 400 V DOL
- Cable size for a 32 A single-phase 25 m run
- Current-carrying capacity and derating
Current ratings, multicore cable with three or four cores, thermoplastic 75 °C
The cable size tool reads the printed rating here for a thermoplastic multicore cable, in copper or aluminium, for each installation method. That figure is the starting point, before any derating.
Verified: read against the printed standard, pages 62–64. Checked 24 Sept 2026.
Tools that read it:
Cable size calculator, Correction factor calculator, Existing circuit check and Motor circuit calculator.
Cited by 28
- Worked examples index by tool and trade
- AS/NZS 3000 Cl 7.9: EV charging in NZ
- Hot water cylinder cable size for a 3 kW element
- How many amps can 1.5 mm² cable carry?
- How many amps can 10 mm² cable carry?
- How many amps can 16 mm² cable carry?
- How many amps can 2.5 mm² cable carry?
- How many amps can 6 mm² cable carry?
- What size cable for a 22 kW EV charger?
- What size cable for a 25 A circuit?
- What size cable for a lighting circuit in NZ?
- What size cable for power points in NZ?
- Three circuits in a hot ceiling: correction factor
- What size breaker for 4 mm² cable
- Cable size for a 20 A heat pump circuit in summer
- AmpSize vs jCalc vs free cable sizing tools
- EV charger cable size for a 7 kW 32 A circuit
- AS/NZS 3008.1.2 Tables 22 to 29: derating
- AS/NZS 3008.1.1 vs 3008.1.2: AU and NZ conditions
- AS/NZS 3008.1.2 Tables 4 to 21: current ratings
- AS/NZS 3008 Table 13 (now 3.18): multicore ratings
- AS/NZS 3008 vs BS 7671: cable sizing compared
- AWG and the NEC for NZ and AU electricians
- Motor full load current: 11 kW 400 V DOL
- Cable size for a 32 A single-phase 25 m run
- Cable size for an estimate: length matters
- Current-carrying capacity and derating
- Checking an existing circuit
Current ratings, multicore cable with three or four cores, cross-linked 90 °C
The cable size tool reads the printed rating here for a cross-linked multicore cable, in copper or aluminium, for each installation method.
Verified: read against the printed standard, pages 65–67. Checked 24 Sept 2026.
Tools that read it:
Cited by 11
- Worked examples index by tool and trade
- Hot water cylinder cable size for a 3 kW element
- Submain cable size for 3-phase 100 A over 60 m
- Cable size for a 20 A heat pump circuit in summer
- AmpSize vs jCalc vs free cable sizing tools
- EV charger cable size for a 7 kW 32 A circuit
- AS/NZS 3008.1.2 Tables 4 to 21: current ratings
- AS/NZS 3008 vs BS 7671: cable sizing compared
- Motor full load current: 11 kW 400 V DOL
- Cable size for a 32 A single-phase 25 m run
- Current-carrying capacity and derating
Grouping factors for bunched circuits, buried circuits and underground wiring enclosures
The cable size and correction factors tools read the factor for circuits that share a route. More circuits together means a lower factor and a larger cable.
Verified: read against the printed standard, pages 79, 84–87. Checked 24 Sept 2026.
Tools that read it:
Cable size calculator, Correction factor calculator and Existing circuit check.
Cited by 9
- Hot water cylinder cable size for a 3 kW element
- Submain cable size for 3-phase 100 A over 60 m
- Three circuits in a hot ceiling: correction factor
- What size breaker for 4 mm² cable
- Cable size for a 20 A heat pump circuit in summer
- AS/NZS 3008.1.2 Tables 22 to 29: derating
- AS/NZS 3008 Table 22 (now 3.33): bunched grouping
- Current-carrying capacity and derating
- Correction factors in the 2017 and 2025 editions
Grouping factors for single-core circuits on trays, ladder supports, racks and cleats in air
The cable size and correction factors tools read the factor for single-core circuits on a tray, a ladder, a rack or cleats. The factor depends on the support, the tiers, and whether the circuits touch.
Verified: read against the printed standard, pages 80. Checked 26 Sept 2026.
Tools that read it:
Cable size calculator, Correction factor calculator, Existing circuit check and Cable tray and ladder fill.
Grouping factors for multicore cables on trays, ladder supports, racks and cleats in air
The cable size and correction factors tools read the factor for multicore cables on a tray, a ladder, a rack or cleats. The factor depends on the support, the tiers, and whether the cables touch.
Verified: read against the printed standard, pages 82. Checked 26 Sept 2026.
Tools that read it:
Cable size calculator, Correction factor calculator, Existing circuit check and Cable tray and ladder fill.
Rating factors for air and soil ambient temperature
The cable size and correction factors tools read the factor for the air or ground temperature on the route. A hot route lowers the current the cable can carry.
Verified: read against the printed standard, pages 88. Checked 24 Sept 2026.
Tools that read it:
Cable size calculator, Correction factor calculator and Existing circuit check.
Cited by 11
- Submain cable size for 3-phase 100 A over 60 m
- Three circuits in a hot ceiling: correction factor
- What size breaker for 4 mm² cable
- Cable size for a 20 A heat pump circuit in summer
- AmpSize vs jCalc vs free cable sizing tools
- AS/NZS 3008.1.2 Tables 22 to 29: derating
- AS/NZS 3008.1.1 vs 3008.1.2: AU and NZ conditions
- AS/NZS 3008 Table 27 (now 3.44, 3.45): temperature
- Current-carrying capacity and derating
- Correction factors in the 2017 and 2025 editions
- Underground cables and civil interfaces
Rating factors for depth of laying
The cable size and correction factors tools read the factor for how deep the cable is buried. It applies only to buried cables.
Verified: read against the printed standard, pages 89. Checked 24 Sept 2026.
Tools that read it:
Cable size calculator, Correction factor calculator and Existing circuit check.
Rating factors for thermal resistivity of the soil
The cable size and correction factors tools read the factor for the thermal resistivity of the soil. It applies only to buried cables.
Verified: read against the printed standard, pages 90. Checked 24 Sept 2026.
Tools that read it:
Cable size calculator, Correction factor calculator and Existing circuit check.
Reactance at 50 Hz and a.c. resistance at 50 Hz
The voltage drop, voltage rise, loop impedance and cable size tools read conductor resistance and reactance at the operating temperature from this data. The loop power budget reads the conductor resistance.
Verified: read against the printed standard, pages 98, 102–103. Checked 24 Sept 2026.
Tools that read it:
Cable size calculator, Voltage drop calculator, Earth fault loop impedance calculator, Voltage rise calculator, Maximum circuit length calculator, Loop power budget for 4-20 mA loops, Existing circuit check, Fault level calculator, Total voltage drop calculator and Cable loss running cost.
Cited by 16
- Voltage rise on a long rural PV run of 80 m
- Voltage rise for a 10 kW three-phase inverter
- Homeowner shed supply voltage drop over 60 m
- Lighting circuit loop impedance, B curve 10 A
- Voltage drop single phase vs three phase
- Submain voltage drop estimate for a 160 A tender
- Max cable length for a 20 A C curve subcircuit
- 24 V DC voltage drop on an instrument loop
- Fault level at a sub-board, 300 kVA transformer
- Off-grid battery bank autonomy at 48 V
- AS/NZS 3000 Table 8.1: max Zs by curve and rating
- Voltage rise for a 5 kW solar inverter cable
- Voltage drop with the mV/A·m method
- Voltage drop basics
- Loop power and the 4-20 mA voltage budget
- Prospective fault current at a board
Values of constant K for determination of permissible short-circuit currents
This table gives one flat k factor per material and insulation. The cable size and fault rating tools read Table 52 from the short-circuit limits table instead. There, the k factor depends on the temperature limits Tables 53 and 55 set.
Verified: read against the printed standard, pages 121–122. Checked 19 Sept 2026.
Tools that read it:
Cable size calculator, Cable fault rating calculator, Existing circuit check and MCB trip curve and cable limit.
Short-circuit K values and temperature limits
The fault rating tool reads the k factor for the conductor start temperature and the short-circuit temperature limit. The limit comes from the insulation class and the conductor size band, or from the joint in the run when the joint is the lower of the two.
Verified: read against the printed standard, pages 121–123 (PDF 125–127), with Table 1 on page 13. Checked 26 Sept 2026.
Tools that read it:
Cable size calculator, Cable fault rating calculator, Existing circuit check and MCB trip curve and cable limit.
Guides and learn pages that cite it (62)
- GuideWorked examples index by tool and trade
- GuideAS/NZS 3000 Cl 7.9: EV charging in NZ
- GuideVoltage rise on a long rural PV run of 80 m
- GuideVoltage rise for a 10 kW three-phase inverter
- GuideHomeowner shed supply voltage drop over 60 m
- GuideLighting circuit loop impedance, B curve 10 A
- GuideVoltage drop single phase vs three phase
- GuideCable tray fill for a plant room: a second tier
- GuideSwitchboard fault rating at 25 kA for 1 s
- GuideHot water cylinder cable size for a 3 kW element
- GuideConsumer mains fault withstand for 16 mm² copper
- GuideHow many amps can 1.5 mm² cable carry?
- GuideHow many amps can 10 mm² cable carry?
- GuideHow many amps can 16 mm² cable carry?
- GuideHow many amps can 2.5 mm² cable carry?
- GuideHow many amps can 6 mm² cable carry?
- GuideVoltage drop on 2.5 mm² over 30 m
- GuideWhat size cable for a 22 kW EV charger?
- GuideWhat size cable for a 25 A circuit?
- GuideWhat size cable for a lighting circuit in NZ?
- GuideWhat size cable for power points in NZ?
- GuideSubmain voltage drop estimate for a 160 A tender
- GuideMax cable length for a 20 A C curve subcircuit
- GuideSubmain cable size for 3-phase 100 A over 60 m
- Guide24 V DC voltage drop on an instrument loop
- GuideFault level at a sub-board, 300 kVA transformer
- GuideThree circuits in a hot ceiling: correction factor
- GuideWhat size breaker for 4 mm² cable
- GuideTotal voltage drop: mains, submain and final
- GuideOff-grid battery bank autonomy at 48 V
- GuideCable size for a 20 A heat pump circuit in summer
- GuideAmpSize vs jCalc vs free cable sizing tools
- GuideEV charger cable size for a 7 kW 32 A circuit
- GuideAS/NZS 3008.1.2 Table 52: the k factor
- GuideAS/NZS 3008.1.2 Tables 22 to 29: derating
- GuideAS/NZS 3008.1.1 vs 3008.1.2: AU and NZ conditions
- GuideAS/NZS 3008.1.2 Tables 4 to 21: current ratings
- GuideAS/NZS 3008 Table 13 (now 3.18): multicore ratings
- GuideAS/NZS 3008 Table 22 (now 3.33): bunched grouping
- GuideAS/NZS 3008 Table 27 (now 3.44, 3.45): temperature
- GuideAS/NZS 3008 vs BS 7671: cable sizing compared
- GuideAWG and the NEC for NZ and AU electricians
- GuideMotor full load current: 11 kW 400 V DOL
- GuideProspective fault current at a main switchboard
- GuideAS/NZS 3000 Table 8.1: max Zs by curve and rating
- GuideVoltage rise for a 5 kW solar inverter cable
- GuideAS/NZS 3000 Clause 3.6.2: voltage drop limit
- GuideCable size for a 32 A single-phase 25 m run
- GuideVoltage drop with the mV/A·m method
- LearnCable size for an estimate: length matters
- LearnConduit fill and installation methods
- LearnCurrent-carrying capacity and derating
- LearnVoltage drop basics
- LearnCable tray fill: one layer, tiers and grouping
- LearnChecking an existing circuit
- LearnCorrection factors in the 2017 and 2025 editions
- LearnIB ≤ IN ≤ IZ: the overload rule on a 32 A circuit
- LearnLoop power and the 4-20 mA voltage budget
- LearnShort-circuit withstand and the k factor
- LearnUnderground cables and civil interfaces
- LearnHarmonics and neutral sizing
- LearnProspective fault current at a board