How many amps can 1.5 mm² cable carry?

Existing circuit check

+2 references

Worked to AS/NZS 3008.1.2:2017 (NZ) and AS/NZS 3000:2018. Tables checked 27 Sept 2026.

Corrected rating Iz

16A

Largest curve C device the cable allows
16A
Voltage drop
4.59%
Maximum Zs for the device
1.92Ω
Open the calculator with these inputs

This result is a design aid. Verify it against the current standard.

A drawn result card from the Circuit Check tool: circuit on 1.5 mm² passes.

1.5 mm² copper multicore PVC cable carries 16 A enclosed in air at 30 °C in New Zealand. That is its corrected rating Iz from AS/NZS 3008.1.2:2017 Table 13, with no derating. The largest curve C breaker it allows is 16 A.

The case

The circuit is single‑phase at 230 V and runs 20 m. The design current is the full 16 A of the breaker. Over that run the voltage drop is 4.59 %, close to its limit, and the earth fault loop impedance is 1.01 Ω. Table 8.1 allows up to 1.92 Ω for the breaker.

The circuit check reads Passes.

What changes the rating

The installation method sets the column the tool reads. Clipped direct to a surface, the cable carries 17 A.

Heat lowers it. At 40 °C ambient the factor is 0.88 and the cable carries 14.08 A.

Grouping lowers it further. Bunched with two other circuits, it carries 11.2 A.

See also: What size cable for a lighting circuit in NZ? and Current-carrying capacity and derating.

Try it with these inputs

Ambient temperature
30 °C
Cores
Multicore
Device curve
Curve C
Grouped circuits
1
Insulation
PVC 75 °C
Run length
20 m
Design current
16 A
Material
Copper
Installation method
Enclosed in air
Power factor
1
Phases
Single phase
Device rating
16 A
Installed cable size
1.5 mm²
Voltage
230 V
External impedance Ze
0.35 Ω
Open the calculator with these inputs