Engineer guides
Checking a design, producing evidence and comparing candidate cable sizes for a job.
- 3 min readWill a heat pump fit a 63 A supply?Check if a 3.5 kW heat pump fits a house with a 63 A main switch. Find the maximum demand by measurement, then cross-check it by limitation, per AS/NZS 3000.

- 3 min readShop and office maximum demand by floor areaEstimate the maximum demand of a small retail and office building from its floor area with AS/NZS 3000 Table C3, with basement EV charging and the range.

- 5 min readWorked examples index by tool and tradeEvery AmpSize worked example in one place, grouped by calculator and tagged with the trade it was written for, from house circuits to industrial boards.

- 3 min readIDMT grading main switch and submainTwo IEC standard inverse relays graded at an 8 kA fault on a commercial building, showing how an instantaneous setting overrides the curve and sets the margin.

- 4 min read63 A three‑phase submain buried in QueenslandA 63 A three-phase submain buried direct in hot Queensland ground, sized on AS/NZS 3008.1.1:2025 with the soil and depth factors, then run again on 2017.

- 3 min readArc flash label calculation at 400 VIncident energy, arc flash boundary and PPE category for a 400 V commercial main switchboard at 12 kA with a 0.3 s clearing time and a 600 mm working distance.

- 4 min read1000 kVA transformer amps at 11 kVFull load current for a 1000 kVA 11 kV to 400 V transformer, with the primary current, the secondary current and the fault current at 5 % impedance.

- 4 min readCar-park floodlight: obtrusive light at a boundaryTwo 10 000 lm floodlights 10 m from a neighbour's window in zone A2, checked against AS/NZS 4282 for lux at the window, candela and the upward light ratio.

- 3 min readGenerator fault current calculation at 400 VA 500 kVA 400 V standby set at 12 % subtransient reactance gives 721.69 A full load and 6014.07 A fault current, with the decay the figure leaves out.

- 3 min readIEEE 1584-2002: arc flash model and limitsWhat the IEEE 1584-2002 empirical model governs, where it stops applying, and a 400 V switchboard study that lands on 7.54 cal/cm² at 455 mm.

- 5 min readArc flash at a 48 V home batteryClass a 48 V lithium home battery with 6 kA at its terminals by AS/NZS 5139, find its arc flash energy and PPE level, then bring it down with fuses.

- 3 min readIEC 60255-151: IDMT curve constantsWhat IEC 60255-151 governs, which curve sets the IDMT tool carries, and a worked grading pair on standard inverse that clears in 0.21 s and 0.74 s.

- 3 min readArc flash boundary at a motor control centreArcing current, incident energy and arc flash boundary for a 400 V MCC at 25 kA with a 0.1 s clearing time, and why the equipment type moves the result.

- 4 min readSwitchboard fault rating at 25 kA for 1 sA 1 second withstand check at 25 kA on 185 mm² copper XLPE, returning a 174.83 mm² minimum size and a 26.46 kA withstand, with a thin margin explained.

- 3 min readDC isolator rating for a 10 kW solar arrayRate the d.c. isolator and size the frame earth for a four-string domestic array. Check one data sheet that passes and one that fails per pole.

- 3 min readSolar string sizing for a 600 V inverterHow many 49.5 V modules fit a string on a 600 V inverter at -5 °C? Work cold Voc, hot Vmp, the string current, fuses and the d.c. isolator by AS/NZS 5033.

- 3 min readStarting a loaded conveyorA 22 kW conveyor that needs 120 % torque to break away. Why star-delta and a soft starter will not start it, and what a drive or autotransformer does.

- 4 min readMotor circuit for a 15 kW pump: DOL or star-deltaSize a 15 kW 400 V pump circuit: cable, breaker, contactor and overload relay. Compare DOL, star-delta, soft starter and drive starts.

- 3 min readTransformer secondary fault current for 500 kVAA 500 kVA 11 kV to 400 V transformer at 6 percent impedance, worked through to 721.69 A of secondary full load current and 12,028.13 A of fault current.

- 3 min readFactory power factor correction: 250 kW at 0.78A 250 kW factory load at 0.78 power factor lifted to 0.95. The kvar, the capacitor steps, the current saved, the kVA released and why the bank is detuned.

- 3 min readFault level at a sub‑board, 300 kVA transformerWork the prospective fault current at a sub-board 45 m from a 300 kVA transformer, three-phase and phase-earth, and check 6 kA and 10 kA breakers against it.

- 4 min readAmpSize vs jCalc vs free cable sizing toolsCompare AmpSize with jCalc and other free cable sizing tools. One 63 A three-phase submain shows which checks decide a size, and what AmpSize leaves out.

- 3 min readArc flash incident energy at a 400 V switchboardA 400 V board with 20 kA bolted fault and 0.2 s clearing gives 6.23 cal/cm² at 455 mm, an arcing current of 9.64 kA and a 1395.97 mm boundary.

- 4 min readAS/NZS 3008.1.2 Table 52: the k factorWhat Table 52 governs, how the adiabatic check uses k, and a 10 kA fault cleared in 0.1 s that needs 22.11 mm² against an installed 25 mm² conductor.

- 3 min readIDMT curve grading for a 100 A feederTwo standard inverse relays at 2000 A give a feeder trip at 0.23 s, an incomer trip at 0.99 s and a grading margin of 0.76 s, read off one chart.

- 6 min readAS/NZS 3008.1.1 table numbers: 2017 to 2025Each AS/NZS 3008.1.1 table AmpSize reads, with its 2017 number, its 2025 number and whether its values moved, and one submain that cites both sets.

- 4 min readAS/NZS 3008.1.1 vs 3008.1.2: AU and NZ conditionsThe AU part of AS/NZS 3008.1 rates cable at 40 °C air and the NZ part at 30 °C. One 32 A circuit needs 6 mm² in Australia and 4 mm² in New Zealand.

- 5 min readAS/NZS 3008 vs BS 7671: cable sizing comparedHow BS 7671 and AS/NZS 3000 with AS/NZS 3008.1 size a cable, where they differ, and why a BS current rating never converts into an AS/NZS one.

- 5 min readDC cable size: 48 V battery and 600 V PV arrayTwo d.c. circuits sized to AS/NZS 3008.1.1:2025, a 48 V battery-to-inverter run that current sizes and a 600 V array feed that voltage drop sizes.

- 3 min readProspective fault current at a main switchboardA 16 kA fault cleared in 0.1 s on 70 mm² copper XLPE, with the minimum conductor size, the withstand current and the k factor the adiabatic check returns.

- 5 min readAS/NZS 3008.1.1:2025: what changed from 2017The 2025 AU part adds d.c. ratings to 1500 V, renumbers every table and moves some ratings. Four circuits, each run on both editions, show what moves.

- 3 min readVoltage rise for a 5 kW solar inverter cableA 5 kW single-phase inverter 40 m from the switchboard on 10 mm² copper, with the rise in volts, the percent and the maximum length the tool returns.

- 4 min readEarth fault loop impedance and maximum ZsWhat earth fault loop impedance measures, how the maximum Zs check works, and a 32 A circuit on 6 mm² over 25 m that lands on 0.67 ohms against a 0.96 limit.

- 3 min readVoltage drop with the mV/A·m methodHow the millivolt per amp metre method works, with a 32 A run over 25 metres on 6 mm² copper and the exact drop, percent and maximum length the tool returns.

Calculators these guides use
- Spare capacity calculatorSee if a new load fits the main switch of a supply.
- Floor area demand calculatorEstimate commercial demand from floor area and use.
- Cable size calculatorFind the smallest cable size that passes each check.
- IDMT grading calculatorPlot the trip curves of inverse-time overcurrent relays.
- Arc flash calculatorEstimate the energy of an arc flash and its PPE category.
- Transformer calculatorCalculate transformer full load current and impedance.
- Obtrusive light checkerCheck outdoor light at a boundary window by AS/NZS 4282.
- Generator current calculatorFull load and fault current of a generator from its kVA.
- Battery arc flash and classBattery DVC, hazard class, arc flash energy and PPE level.
- Cable fault rating calculatorCheck that a conductor can withstand the fault current.
- PV isolator and earthing calculatorRate the PV array cables, d.c. isolator and earthing.
- PV string calculatorModules per string, string current and isolator for PV.
- Motor starting method comparisonCompare DOL, star-delta, soft start and drive starts.
- Motor circuit calculatorCable, breaker, contactor and overload for one motor.
- Power factor correction calculatorFind the capacitor kvar to lift a power factor.
- Fault level calculatorProspective fault current at a board from its source.
- DC cable size calculatorSize a d.c. cable up to 1500 V for current and voltage drop.
- Voltage rise calculatorCalculate voltage rise for embedded generation or PV.
- Earth fault loop impedance calculatorCheck earth fault loop impedance against the maximum Zs.
- Voltage drop calculatorCalculate voltage drop on a cable run and check the limit.