What size cable for a 25 A circuit?

Cable size calculator

+2 references

Worked to AS/NZS 3008.1.2:2017 (NZ) and AS/NZS 3000:2018. Tables checked 27 Sept 2026.

Conductor size

4mm²

Derated capacity
29A
Voltage drop
3.05%
Earth conductor
2.5mm²
Open the calculator with these inputs

This result is a design aid. Verify it against the current standard.

A drawn result card from the Cable Size tool: conductor size 4 mm².

A 25 A single‑phase circuit takes 4 mm² copper cable on a typical New Zealand route. For 25 m of multicore PVC cable enclosed in air at 30 °C, the tool gives 29 A of derated capacity and a voltage drop of 3.05 %.

Why not 2.5 mm²

On the same route, 2.5 mm² has 23 A of derated capacity. That is below the 25 A breaker, so the breaker would not protect the cable. Cl 2.5.3.1 sets that comparison: the device rating must not exceed the cable's capacity.

The case

The circuit runs at 230 V with a curve C breaker and a design current of 25 A. The voltage drop limit is 5 % and Ze is 0.35 Ω. Table 5.1 gives a 2.5 mm² earth, and the earth fault loop impedance is 0.72 Ω.

Before you install

Grouping, a hot ceiling and thermal insulation all lower the capacity. Enter the real route and read the check the tool prints for each candidate size.

See also: What size breaker for 4 mm² cable and Ib, In and Iz.

Try it with these inputs

Ambient temperature
30 °C
Cores
Multicore
Device curve
Curve C
Check protective device
Yes
Grouped circuits
1
Insulation
PVC 75 °C
Run length
25 m
Design current
25 A
Material
Copper
Installation method
Enclosed in air
Power factor
1
Phases
Single phase
Device rating
25 A
Voltage drop limit
5 %
Voltage
230 V
External impedance Ze
0.35 Ω
Open the calculator with these inputs

Where next

The ideas behind it

More worked examples

AmpSize is a design aid. Verify results against the current standard.