How many amps can 6 mm² cable carry?

Existing circuit check

+2 references

Worked to AS/NZS 3008.1.2:2017 (NZ) and AS/NZS 3000:2018. Tables checked 27 Sept 2026.

Corrected rating Iz

38A

Largest curve C device the cable allows
32A
Voltage drop
2.09%
Maximum Zs for the device
0.96Ω
Open the calculator with these inputs

This result is a design aid. Verify it against the current standard.

A drawn result card from the Circuit Check tool: circuit on 6 mm² passes.

6 mm² copper multicore PVC cable carries 38 A enclosed in air at 30 °C in New Zealand. That is its corrected rating Iz from AS/NZS 3008.1.2:2017 Table 13. The largest curve C breaker it allows is 32 A, the size of a cooktop or EV charger circuit.

The case

The circuit is single‑phase at 230 V and runs 20 m at the full 32 A of the breaker. The voltage drop is 2.09 % and the earth fault loop impedance is 0.61 Ω, inside the 0.96 Ω that Table 8.1 allows.

The circuit check reads Passes.

What changes the rating

Clipped direct to a surface, the cable carries 42 A.

A hot garage ceiling lowers it. At 40 °C the cable carries 33.44 A, still above a 32 A breaker.

Bunched with two other circuits, it carries 26.6 A, and a 32 A circuit fails.

See also: What size cable for a 22 kW EV charger? and Current-carrying capacity and derating.

Try it with these inputs

Ambient temperature
30 °C
Cores
Multicore
Device curve
Curve C
Grouped circuits
1
Insulation
PVC 75 °C
Run length
20 m
Design current
32 A
Material
Copper
Installation method
Enclosed in air
Power factor
1
Phases
Single phase
Device rating
32 A
Installed cable size
6 mm²
Voltage
230 V
External impedance Ze
0.35 Ω