Three phase power calculator

Convert between power, current, voltage and power factor.

No standard

Inputs

A worked example with the default inputs.

Phases
Three phase
Voltage
400 V
Current
50 A
Power factor
0.9

Apparent power

34.64kVA

Real power
31.18kW
Reactive power
15.1kvar

This result is a design aid. Verify it against the current standard.

Calculation steps

  1. Apparent powerResult34.64kVA
  2. Real power31.18kW
  3. Reactive power15.1kvar

About this calculator

How this is calculated

The tool converts between current, apparent power, real power and reactive power. It works on one phase or on three. It does not read a standard. The method is the power triangle.

  1. Inputs. You pick one phase or three. You enter the voltage, the current and the power factor. On three phases the voltage is the line voltage.
  2. Apparent power. On three phases, S = √3 × V × I ÷ 1000. On one phase, S = V × I ÷ 1000. The result is in kVA.
  3. Real power. P = S × power factor. The result is in kW.
  4. Reactive power. Q = √(S² − P²). The result is in kvar.

Enter the line voltage on three phases, such as 400 V. Enter the phase voltage on one phase, such as 230 V.

Worked example

Limits

The tool assumes a balanced load. It assumes a sine wave. A load with harmonics needs a true RMS reading. The tool does not size a cable or a device. Use the cable size calculator for that. A motor has efficiency as well as power factor. Use the motor tool for its full load current.

Use the tool to check a meter reading, a motor plate or a supply request. For a load in kW, the full load current tool works the other way. A low power factor raises the kVA for the same kW. The power factor correction tool finds the capacitor size.

See also: kVA to amps at 400 V, Current and power factor to kW and Power factor and reactive power.

Questions

The result is a design aid. Verify against the current standard.

What does the three phase power calculator do?

The tool converts a voltage, a current and a power factor into apparent power, real power and reactive power. It works on one phase or on three phases. The three phase result uses the square root of three and the line voltage.

Which inputs matter most?

Voltage and current set the apparent power. The power factor splits that apparent power into real power and reactive power. A power factor of 1 gives no reactive power. On three phases, enter the line to line voltage, not the phase to neutral voltage.

What are the common gotchas?

The tool works out the reactive power from the magnitudes. It therefore does not show whether the load is leading or lagging. The result assumes the three phases carry equal, balanced loads. The inputs sit in the page address, so a link reproduces the same conversion.