Lighting lumen method calculator
Luminaire count and grid for a room by the lumen method.
Reads AS/NZS 1680.1:2006 and AS/NZS 1158.1.2:2010. Tables checked 1 Oct 2026.
Try a job 11
Each job fills in example values. Replace them with your values.
- Light a kitchen by the lumen methodHow many downlights a kitchen needs for its target lux, in a grid.
- Light a garage with battensHow many LED battens a garage needs, laid out in rows.
- Light an office to 320 lxHow many panels an office needs to AS/NZS 1680.1 Table 3.1, with the spacing check.
- Light a warehouse with high baysHow many 20 000 lm high bays a 30 by 20 m bay needs.
- Light a corridorHow many downlights a 12 by 1.5 m corridor needs.
- Light a bathroomHow many downlights a 3 by 2.4 m bathroom needs.
- Light a living roomHow many downlights a 6 by 4.5 m living room needs.
- Light a bedroomHow many downlights a 3.6 by 3.2 m bedroom needs.
- Light a switchroomHow many battens a 5 by 3 m switchroom needs.
- Light a classroom to 320 lxHow many panels a 9 by 7 m classroom needs at a target you set.
- Light a dusty workshopThe count with a maintenance factor from Table 14.4.
Inputs
A worked example with the default inputs.
- Room use
- Living room
- Room length
- 4 m
- Room width
- 3.5 m
- Ceiling height
- 2.4 m
- Luminaire height above the floor
- 0 m
- Working plane
- 0 m
- Target illuminance
- 0 lx
- Lumens per luminaire
- 800 lm
- Watts per luminaire
- 9 W
- Beam angle
- 90 °
- Reflectances, ceiling / walls / floor
- 70/50/20 %
- Luminaire maintenance factor from Table 14.4
- Own factor
- Maintenance factor
- 0.8
Luminaires
6
- Grid
- 3 by 2
- Spacing along
- 1.33m
- Spacing across
- 1.75m
- Illuminance the layout gives
- 156lx
- Lighting power density
- 3.86W/m²
This result is a design aid. Verify it against the current standard.
Calculation steps
- Floor area14m²
- Target illuminance150lx
Typical design value. Not a standard’s value.
- Working plane0.7m
AS/NZS 1680.1:2006 Table 3.2
- Luminaire height2.4m
The ceiling
- Height above the working plane1.7m
- Room index
K = L × W / (Hm × (L + W))
1.1 - Utilisation factor0.57
Typical value for a direct luminaire. Use the maker’s table when you have it. Reflectances 70/50/20 %.
- Maintenance factor0.8
- N = E × A / (Φ × UF × MF)5.76
- Grid3 by 2
- E' = N' × Φ × UF × MF / A156lx
- Spacing to height, greatest1.03
Spacing to height ratio for even light. Typical.
- Lighting power density3.86W/m²
About this calculator
How this is calculated
The tool finds how many luminaires a room needs. It uses the lumen method. The target lux comes from AS/NZS 1680.1:2006 where that Standard lists the room use.
- Room and plane. The tool finds the floor area. It reads the target illuminance and the working plane height for the room use (Tables 3.1 and 3.2).
- Room index. It works out K = L × W / (Hm × (L + W)). Hm is the luminaire height above the working plane.
- Utilisation factor. It reads a typical factor for the room index and the reflectances you pick. You can type your own factor from the maker's table.
- Maintenance factor. It uses the value you give. The helper reads the luminaire factor from Table 14.4 of AS/NZS 1158.1.2:2010. You type the lamp lumen factor.
- Number of luminaires. N = E × A / (Φ × UF × MF). The tool rounds up to a grid that fits the room shape.
- Check. It works the lux the grid gives, the spacing to height ratio and the lighting power density.
| Step | Table or clause | What it decides |
|---|---|---|
| Target illuminance | AS/NZS 1680.1 Table 3.1 | The lux for the room use |
| Working plane | AS/NZS 1680.1 Table 3.2 | The height of the task plane |
| Maintenance factor | AS/NZS 1158.1.2 Table 14.4 | The luminaire factor for dirt |
Worked example
- Office, 6 m by 5 m, 3000 lm luminaires. The ceiling is 2.7 m. The target is 320 lx. The tool gives 9 luminaires in a 3 by 3 grid. That layout gives 449 lx.
Limits
- For a living room and some other uses, the target is a typical design value. It is not a Standard value. Check it against your brief.
- The utilisation factor is typical for a direct luminaire. Use the maker's table when you have it.
- The tool does not model glare, uniformity or a photometric file. It does not replace a lighting design programme.
- The grid is an even layout. A room with obstructions or a feature may need a different layout.
- The tool does not read AS/NZS 3008 and has no edition select.
See also: Worked examples by tool and trade, Obtrusive light and the 4282 zones and Obtrusive light.
Questions
The result is a design aid. Verify against the current standard.
What does the lighting lumen method tool do?
It finds how many luminaires a room needs for a target illuminance. The count is the target times the floor area. It divides that by the lumens of one luminaire and the two factors. The tool lays the count out as a grid and checks the spacing against the mounting height.
Where does the target lux come from?
A workplace room, such as an office or a warehouse, reads AS/NZS 1680.1:2006 Table 3.1, and the step names it. A house’s rooms, its kitchen and garage too, are in the AS/NZS 1680.2 series, which AmpSize does not hold. They and outside areas use typical values, and the tool says so. Table 3.1’s 240 lx is for workplace food preparation.
What is the utilisation factor?
It is the part of the lamp light that reaches the working plane. The tool reads a typical value for a direct luminaire. It uses the room index and the ceiling, wall and floor reflectances. Use the maker’s table when you have it: choose Own utilisation factor and type the value.
Where does the maintenance factor come from?
Type your own, or take the luminaire maintenance factor from AS/NZS 1158.1.2:2010 Table 14.4. That table leaves out lamp lumen depreciation. So the tool asks for the lamp lumen maintenance factor from the data sheet: an L80 rating reads 0.8. The maintenance factor is the product of the two.
Worked examples
Background
Clauses and tables this tool reads
- AS/NZS 1680.1:2006 Table 3.1Recommended maintained illuminances for various types of tasks, activities or interiors
- AS/NZS 1680.1:2006 Table 3.2Lighting parameters for general lighting: recommendations
- AS/NZS 1158.1.2:2010 Table 14.4Typical luminaire maintenance factors
Every clause and table, with how each was verified
Tables last checked on 1 Oct 2026.