DC cable size calculator
DC cable size calculator for New Zealand and Australia, up to 1500 V d.c. It reads the AS/NZS 3008.1.1:2025 d.c. ratings and mV/A.m. For NZ, it corrects them to 30 °C and marks the result derived.
Inputs
Worked example with the default inputs. The live calculator replaces it when the page loads.
- Standard
- AU · AS/NZS 3008.1.1:2025
- Voltage
- 48 V d.c.
- Design current
- 100 A
- Supply type
- ELV, 120 V d.c. or less (10 %)
- Voltage drop limit
- 10 %
- Route length
- 5 m
- Installation method
- Unenclosed touching
- Air temperature
- 40 °C
- Grouped circuits
- 1
- Group arrangement
- Bunched on a surface or enclosed
- Cables
- Two single-core cables
- Material
- Copper
- Insulation
- PVC 75 °C
Conductor size
35mm²
- Corrected rating Iz
- 119A
- Voltage drop
- 0.64V
- Voltage drop percent
- 1.32%
- Voltage drop limit
- 10%
- Total correction factor
- 1x
- Size set by
- Current
This result is a design aid. Verify it against the current standard.
Calculation steps
- Ambient correction factor1xAS/NZS 3008.1.1:2025 Table 3.44 p.84
- Grouping correction factor1xOne circuit, no grouping factor
- Total correction factor1x
- Required current rating100AAS/NZS 3000:2018 Cl 3.4
- Voltage drop limit10%AS/NZS 3008.1.1:2025 Cl 4.1.1
- Voltage drop allowed4.8VAS/NZS 3008.1.1:2025 Cl 4.1.1
- Selected conductor size35mm²AS/NZS 3008.1.1:2025 Table 3.21 p.54–55
- Current rating119AAS/NZS 3008.1.1:2025 Table 3.21 p.54–55
- Corrected current rating Iz119AAS/NZS 3000:2018 Cl 3.4
- mV/A·m1.27mV/A·mAS/NZS 3008.1.1:2025 Table 4.16 p.123
- Voltage drop0.64VAS/NZS 3008.1.1:2025 Cl 4.7
- Voltage drop percent1.32%
About this calculator
How this is calculated
The tool tests every standard conductor size in turn. It reports the smallest size that passes the current check and the voltage drop check.
- Tabulated d.c. current. It reads the d.c. rating of each size for your cables, material, insulation and installation method. AS/NZS 3008.1.1:2025 prints these ratings for 40 °C air and 25 °C soil. The tool skips a size with no printed rating for the method.
- Correction factors. It multiplies the ambient, grouping, soil and burial depth factors into one correction factor (derating factor in 2017). One circuit alone takes no grouping factor. On a tray, ladder, rack or cleats, pick the cable support.
- Current check. It multiplies the rating by the correction factor to get Iz. The size passes when Iz is at or above the design current.
- Voltage drop. It multiplies the d.c. mV/A.m by the current and the route length, one way, and divides by 1000. The mV/A.m covers both conductors of the circuit.
- Limit. It compares the drop with the limit for the supply type. The limit follows the supply type until you type another one.
- Result. The candidate table shows each size, its Iz, its drop and the check it fails. The result says which check sets the size.
| Step | Table or clause | What it decides |
|---|---|---|
| d.c. rating, two single-core cables | Tables 3.21 and 3.22 | The current each size carries in your installation method |
| d.c. rating, one 2-core cable | Tables 3.24 and 3.25 | The current each size carries in your installation method |
| Ambient | Tables 3.44 and 3.45, Cl 3.5.3 | The correction factor: Table 3.44 for air, Table 3.45 for soil |
| Grouping | Tables 3.33 to 3.36, 3.38, 3.40 and 3.42 | The correction factor for circuits run together, on a support too |
| Buried cable | Tables 3.46, 3.47 and 3.48 | The correction factors for depth and soil resistivity |
| Required current | AS/NZS 3000 Cl 3.4 | The current the cable must carry after correction |
| Voltage drop | Tables 4.16, 4.18, 4.21 and 4.23, Cl 4.7 | The drop over the route |
| Limit | Cl 4.1.1 | The limit for the supply type |
Tables and clauses without a standard named are in AS/NZS 3008.1.1:2025.
Common circuits, worked with the tool
Each line states its route. Change one input and the size can change, so run your own circuit before you buy cable. Every line uses copper with PVC insulation and one circuit on the route. Each uses the Australian conditions, except where a line says otherwise.
- Caravan, 30 A at 12 V over 6 m. One 2-core cable, enclosed in air at 40 °C, against the 10 % ELV limit. It needs 10 mm² with a 0.8 V drop, 6.68 %. The drop sets the size, because 4 mm² carries the current but drops 16.8 %.
- Battery to inverter, 100 A at 48 V over 5 m. Two single-core cables, unenclosed and touching at 40 °C. It needs 35 mm² with a 0.64 V drop, 1.32 %. The current sets the size.
- PV array feed, 15 A at 600 V over 40 m. One 2-core XLPE cable, enclosed in air at 40 °C, against the 5 % network limit. It needs 1.5 mm² with a 20.82 V drop, 3.47 %. The drop sets the size, because 1 mm² carries the current but drops 5.41 %.
- NZ battery to inverter, 100 A at 48 V over 5 m. The same route at 30 °C in New Zealand. It needs 25 mm² with a 0.89 V drop, 1.84 %. The current sets the size. The result is derived.
New Zealand
AS/NZS 3008.1.2:2017 has no d.c. ratings. For New Zealand, the tool uses the AS/NZS 3008.1.1:2025 d.c. ratings. It corrects them from 40 °C to the air temperature you enter, 30 °C by default. A buried run corrects from 25 °C to the soil temperature, 15 °C by default. No NZ table prints these figures, so the result says Derived.
What the tool does not check
The tool does not check the d.c. protective device. Check its rating against Iz. It does not check the prospective short-circuit current of a battery. Check the cable and the device against the battery maker's fault current.
To size the battery bank itself, use the battery calculator. To check a 4-20 mA loop on a d.c. supply, use the loop power budget. For an a.c. circuit, use the cable size calculator or the voltage drop calculator.
Questions
Each answer describes what this tool calculates. The result is a design aid. Verify against the current standard.
What size cable for a 48 V battery at 100 A?
The run is 5 m of two single-core copper PVC cables, touching, at 40 °C in Australia. The tool selects 35 mm². Its corrected rating Iz is 119 A. The drop is 0.64 V, or 1.32 %. 25 mm² fails at 97 A. A different route gives a different answer.
What voltage drop is allowed on a d.c. circuit?
AS/NZS 3008.1.1:2025 Cl 4.1.1 sets the limit by the supply. The tool uses 10 % for ELV at 120 V d.c. or less. It uses 5 % for LV on a network and 7 % from a dedicated substation. It uses 11 % for a stand-alone system. You can type another limit.
Why is my NZ result marked derived?
AS/NZS 3008.1.2:2017 has no d.c. ratings. For NZ, the tool uses the AS/NZS 3008.1.1:2025 d.c. ratings. It corrects them from 40 °C to the NZ ambient, 30 °C by default. Tables 3.44 and 3.45 give the correction factor (derating factor in 2017). No NZ table prints the result, so the tool marks it derived.
Two single-core or 2-core?
Pick Two single-core cables for a positive and a negative run as separate cables. Tables 3.21 and 3.22 rate them. Pick One 2-core cable for one sheathed cable with both conductors. Tables 3.24 and 3.25 rate it. Tables 4.16, 4.18, 4.21 and 4.23 give the mV/A.m.
What does the DC cable size tool not check?
It does not check the d.c. protective device. Check the device rating against the corrected rating Iz. It does not check the prospective short-circuit current of a battery. Check the cable and the device against the battery maker’s fault current.
Worked examples
Clauses and tables this tool reads
- AS/NZS 3008.1.1:2025 Cl 3.5.3Ambient correction
- AS/NZS 3008.1.1:2025 Cl 4.1.1d.c. voltage drop limit
- AS/NZS 3008.1.1:2025 Cl 4.7d.c. voltage drop
- AS/NZS 3008.1.1:2025 Table 3.21Current ratings (d.c.), two single-core cables, thermoplastic 75 °C
- AS/NZS 3008.1.1:2025 Table 3.22Current ratings (d.c.), two single-core cables, cross-linked 90 °C
- AS/NZS 3008.1.1:2025 Table 3.24Current ratings (d.c.), 2-core cable, thermoplastic 75 °C
- AS/NZS 3008.1.1:2025 Table 3.25Current ratings (d.c.), 2-core cable, cross-linked 90 °C
- AS/NZS 3008.1.1:2025 Table 3.33, 3.36, 3.38, 3.40, 3.42Correction factors for bunched circuits, buried circuits and underground wiring enclosures
Every clause and table, with how each was verified
Tables last checked on 27 Sept 2026.
Related tools
- Cable size calculatorFind the smallest cable size that passes each check.AS/NZS 3008.1.2AS/NZS 3008.1.1AS/NZS 3000
- Voltage drop calculatorCalculate voltage drop on a cable run and check the limit.AS/NZS 3008.1.2AS/NZS 3008.1.1AS/NZS 3000
- Earth fault loop impedance calculatorCheck earth fault loop impedance against the maximum Zs.AS/NZS 3008.1.2AS/NZS 3008.1.1AS/NZS 3000