DC cable size calculator
DC cable size calculator for New Zealand and Australia, up to 1500 V d.c. It reads the AS/NZS 3008.1.1:2025 d.c. ratings and mV/A.m. For NZ, it corrects them to 30 °C and marks the result derived.
Reads AS/NZS 3008.1.1:2025 (AU). Tables checked 27 Sept 2026.
Try a job 8
Each job fills in example values. Replace them with your values.
- Size a battery cableThe d.c. cable size for a 3 m, 48 V battery run at 100 A.
- Size a PV string cableThe d.c. cable for 14 A at 600 V over 30 m.
- Size a 12 V run in a camperThe cable for 8 A at 12 V over 6 m at 3 %.
- Size a 24 V control supplyThe cable for 10 A at 24 V over 40 m.
- Size an array cable on a hot roofThe cable for 28 A at 1000 V and 60 °C.
- Size a battery inverter cableThe cable for 250 A at 48 V over 2 m.
- Size a buried array cableThe cable to a ground-mount array, buried 0.6 m.
- Size a 48 V telecom feedThe cable for 60 A at 48 V over 15 m.
Inputs
A worked example with the default inputs.
- Standard
- AU · AS/NZS 3008.1.1:2025
- Voltage
- 48 V d.c.
- Design current
- 100 A
- Supply type
- ELV, 120 V d.c. or less (10 %)
- Voltage drop limit
- 10 %
- Route length
- 5 m
- Installation method
- Unenclosed touching
- Air temperature
- 40 °C
- Grouped circuits
- 1
- Group arrangement
- Bunched on a surface or enclosed
- Cables
- Two single‑core cables
- Material
- Copper
- Insulation
- PVC 75 °C
Conductor size
35mm²
- Corrected rating Iz
- 119A
- Voltage drop
- 0.64V
- Voltage drop percent
- 1.32%
- Voltage drop limit
- 10%
- Total correction factor
- ×1.00
- Size set by
- Current
This result is a design aid. Verify it against the current standard.
Calculation steps
- Ambient correction factor×1.00
AS/NZS 3008.1.1:2025 Table 3.44 p.84
- Grouping correction factor×1.00
One circuit, no grouping factor
- Total correction factor×1.00
- Required current rating100A
AS/NZS 3000:2018 Cl 3.4
- Voltage drop limit10%
AS/NZS 3008.1.1:2025 Cl 4.1.1
- Voltage drop allowed4.8V
AS/NZS 3008.1.1:2025 Cl 4.1.1
- Selected conductor sizeResult35mm²
AS/NZS 3008.1.1:2025 Table 3.21 p.54–55
- Current rating119A
AS/NZS 3008.1.1:2025 Table 3.21 p.54–55
- Corrected current rating Iz119A
AS/NZS 3000:2018 Cl 3.4
- mV/A·m1.27mV/A·m
AS/NZS 3008.1.1:2025 Table 4.16 p.123
- Voltage drop0.64V
AS/NZS 3008.1.1:2025 Cl 4.7
- Voltage drop percent1.32%
About this calculator
How this is calculated
The tool tests every standard conductor size in turn. It reports the smallest size that passes the current check and the voltage drop check.
- Tabulated d.c. current. It reads the d.c. rating of each size for your cables, material, insulation and installation method. AS/NZS 3008.1.1:2025 prints these ratings for 40 °C air and 25 °C soil. The tool skips a size with no printed rating for the method.
- Correction factors. It multiplies the ambient, grouping, soil and burial depth factors into one correction factor (derating factor in 2017). One circuit alone takes no grouping factor. On a tray, ladder, rack or cleats, pick the cable support.
- Current check. It multiplies the rating by the correction factor to get Iz. The size passes when Iz is at or above the design current.
- Voltage drop. It multiplies the d.c. mV/A.m by the current and the route length, one way, and divides by 1000. The mV/A.m covers both conductors of the circuit.
- Limit. It compares the drop with the limit for the supply type. The limit follows the supply type until you type another one.
- Result. The candidate table shows each size, its Iz, its drop and the check it fails. The result says which check sets the size.
| Step | Table or clause | What it decides |
|---|---|---|
| d.c. rating, two single‑core cables | Tables 3.21 and 3.22 | The current each size carries in your installation method |
| d.c. rating, one 2‑core cable | Tables 3.24 and 3.25 | The current each size carries in your installation method |
| Ambient | Tables 3.44 and 3.45, Cl 3.5.3 | The correction factor: Table 3.44 for air, Table 3.45 for soil |
| Grouping | Tables 3.33 to 3.36, 3.38, 3.40 and 3.42 | The correction factor for circuits run together, on a support too |
| Buried cable | Tables 3.46, 3.47 and 3.48 | The correction factors for depth and soil resistivity |
| Required current | AS/NZS 3000 Cl 3.4 | The current the cable must carry after correction |
| Voltage drop | Tables 4.16, 4.18, 4.21 and 4.23, Cl 4.7 | The drop over the route |
| Limit | Cl 4.1.1 | The limit for the supply type |
Tables and clauses without a standard named are in AS/NZS 3008.1.1:2025.
Common circuits, worked with the tool
Each line states its route. Change one input and the size can change, so run your own circuit before you buy cable. Every line uses copper with PVC insulation and one circuit on the route. Each uses the Australian conditions, except where a line says otherwise.
- Caravan, 30 A at 12 V over 6 m. One 2‑core cable, enclosed in air at 40 °C, against the 10 % ELV limit. It needs 10 mm² with a 0.8 V drop, 6.68 %. The drop sets the size, because 4 mm² carries the current but drops 16.8 %.
- Battery to inverter, 100 A at 48 V over 5 m. Two single‑core cables, unenclosed and touching at 40 °C. It needs 35 mm² with a 0.64 V drop, 1.32 %. The current sets the size.
- PV array feed, 15 A at 600 V over 40 m. One 2‑core XLPE cable, enclosed in air at 40 °C, against the 5 % network limit. It needs 1.5 mm² with a 20.82 V drop, 3.47 %. The drop sets the size, because 1 mm² carries the current but drops 5.41 %.
- NZ battery to inverter, 100 A at 48 V over 5 m. The same route at 30 °C in New Zealand. It needs 25 mm² with a 0.89 V drop, 1.84 %. The current sets the size. The result is derived.
New Zealand
AS/NZS 3008.1.2:2017 has no d.c. ratings. For New Zealand, the tool uses the AS/NZS 3008.1.1:2025 d.c. ratings. It corrects them from 40 °C to the air temperature you enter, 30 °C by default. A buried run corrects from 25 °C to the soil temperature, 15 °C by default. No NZ table prints these figures, so the result says Derived.
What the tool does not check
The tool does not check the d.c. protective device. Check its rating against Iz. It does not check the prospective short-circuit current of a battery. Check the cable and the device against the battery maker's fault current.
To size the battery bank itself, use the battery calculator. To check a 4–20 mA loop on a d.c. supply, use the loop power budget. For an a.c. circuit, use the cable size calculator or the voltage drop calculator. To check the drop on a d.c. cable you have already chosen, use the d.c. mode of the voltage drop calculator. It works from the d.c. resistance, so its last digit can differ from this tool.
Questions
The result is a design aid. Verify against the current standard.
What size cable for a 48 V battery at 100 A?
The run is 5 m of two single‑core copper PVC cables, touching, at 40 °C in Australia. The tool selects 35 mm². Its corrected rating Iz is 119 A. The drop is 0.64 V, or 1.32 %. 25 mm² fails at 97 A. A different route gives a different answer.
What voltage drop is allowed on a d.c. circuit?
AS/NZS 3008.1.1:2025 Cl 4.1.1 sets the limit by the supply. The tool uses 10 % for ELV at 120 V d.c. or less. It uses 5 % for LV on a network and 7 % from a dedicated substation. It uses 11 % for a stand-alone system. You can type another limit.
Why is my NZ result marked derived?
AS/NZS 3008.1.2:2017 has no d.c. ratings. For NZ, the tool uses the AS/NZS 3008.1.1:2025 d.c. ratings. It corrects them from 40 °C to the NZ ambient, 30 °C by default. Tables 3.44 and 3.45 give the correction factor (derating factor in 2017). No NZ table prints the result, so the tool marks it derived.
Two single‑core or 2‑core?
Pick Two single‑core cables for a positive and a negative run as separate cables. Tables 3.21 and 3.22 rate them. Pick One 2‑core cable for one sheathed cable with both conductors. Tables 3.24 and 3.25 rate it. Tables 4.16, 4.18, 4.21 and 4.23 give the mV/A.m.
What does the DC cable size tool not check?
It does not check the d.c. protective device. Check the device rating against the corrected rating Iz. It does not check the prospective short-circuit current of a battery. Check the cable and the device against the battery maker’s fault current.
Worked examples
- Arc flash at a 48 V home batteryClass a 48 V lithium home battery with 6 kA at its terminals by AS/NZS 5139, find its arc flash energy and PPE level, then bring it down with fuses.
- DC isolator rating for a 10 kW solar arrayRate the d.c. isolator and size the frame earth for a four-string domestic array. Check one data sheet that passes and one that fails per pole.
- Solar string sizing for a 600 V inverterHow many 49.5 V modules fit a string on a 600 V inverter at −5 °C? Work cold Voc, hot Vmp, the string current, fuses and the d.c. isolator by AS/NZS 5033.
- 12 V caravan cable: d.c. voltage dropA 12 V caravan feed at 30 A over 6 m, checked on 4, 6 and 10 mm² twin against the 10 % ELV limit, then a 48 V battery-to-inverter run.
- Solar battery size for a family home: 25 kWh a daySize a solar battery for a home that uses 25 kWh a day with an 8 kW array. Usable and nominal kWh, the bank, the inverter, winter solar and where it can go.
- DC cable size: 48 V battery and 600 V PV arrayTwo d.c. circuits sized to AS/NZS 3008.1.1:2025, a 48 V battery-to-inverter run that current sizes and a 600 V array feed that voltage drop sizes.
Background
- Home batteries and AS/NZS 5139How a home solar battery is sized in kWh, what usable, nominal, depth of discharge and round-trip efficiency mean, and where AS/NZS 5139 lets one go.
- AS/NZS 3008.1.1:2025: what the AU part coversWhat AS/NZS 3008.1.1:2025 covers, a.c. to 0.6/1 kV and d.c. to 1500 V at 40 °C air and 25 °C soil, how its sections run, and where the d.c. tables are.
- DC voltage drop and conductor resistanceWhy d.c. drop is 2 × I × R × L, why it has no reactance or power factor, and how the hot resistance, the cable tables, the limit and parallel cables change it.
- PV array isolators and earthingHow parallel strings feed a fault, what Ithe, Ie and make and break mean for a d.c. isolator, and how AS/NZS 5033 earths and alarms a PV array.
- PV string voltage and temperatureWhy a PV string's voltage rises in the cold and falls in the heat, how AS/NZS 5033 limits it, and how the string current, fuses and isolator follow.
Clauses and tables this tool reads
- AS/NZS 3008.1.1:2025 Cl 3.5.3Ambient correction
- AS/NZS 3008.1.1:2025 Cl 4.1.1d.c. voltage drop limit
- AS/NZS 3008.1.1:2025 Cl 4.7d.c. voltage drop
- AS/NZS 3008.1.1:2025 Table 3.21Current ratings (d.c.), two single‑core cables, thermoplastic 75 °C
- AS/NZS 3008.1.1:2025 Table 3.22Current ratings (d.c.), two single‑core cables, cross-linked 90 °C
- AS/NZS 3008.1.1:2025 Table 3.24Current ratings (d.c.), 2‑core cable, thermoplastic 75 °C
- AS/NZS 3008.1.1:2025 Table 3.25Current ratings (d.c.), 2‑core cable, cross-linked 90 °C
- AS/NZS 3008.1.1:2025 Table 3.33, 3.36, 3.38, 3.40, 3.42Correction factors for bunched circuits, buried circuits and underground wiring enclosures
Every clause and table, with how each was verified
Tables last checked on 27 Sept 2026.
Related tools
- Battery bank calculatorCalculate battery bank capacity and autonomy for a load.No standard
- PV string calculatorModules per string, string current and isolator for PV.AS/NZS 5033AS/NZS 4777.2
- Voltage drop calculatorCalculate voltage drop on a cable run and check the limit.AS/NZS 3008.1.2AS/NZS 3008.1.1AS/NZS 3000
Was this useful?