Skip to content
AmpSize

Harmonics, neutral current and K-factor

THD, neutral current and K-factor from a spectrum.

AS/NZS 3008.1AS/NZS 3000

Reads AS/NZS 3000:2018, AS/NZS 3008.1.2:2017 (NZ) and AS/NZS 3008.1.1:2017 (AU). Tables checked 2 Oct 2026.

Try a job 4

Each job fills in example values. Replace them with your values.

Inputs

Worked example with the default inputs. The live calculator replaces it when the page loads.

Jurisdiction
NZ · AS/NZS 3008.1.2
Phase current, true rms
100 A
Third harmonic
35 %
Fifth harmonic
20 %
Seventh harmonic
10 %
Ninth harmonic
5 %
Eleventh harmonic
4 %
Thirteenth harmonic
3 %
Fifteenth harmonic
2 %
Share of the phase load that makes harmonics
100 %
Out-of-balance current
0 A

Triplen neutral

97.88A

Total harmonic distortion of the current
42.18%
K-factor
3.59
Table 2 reduction factor
0.86x
Cable picked on
The phase current
Current to pick the cable on
116.28A
Cl 3.5.2(b)(i) minimum for the neutral
38.86A

This result is a design aid. Verify it against the current standard.

Calculation steps

  1. Total harmonic distortion of the current42.18%
  2. Fundamental current92.14A
  3. Triplen harmonics, √(h3² + h9² + h15²)35.41%
  4. Triplen neutralResult97.88A
  5. Third harmonic, percent of the phase current32.25%

    AS/NZS 3008.1.2:2017 Table 2

  6. Table 2 reduction factor0.86x

    AS/NZS 3008.1.2:2017 Table 2

  7. Neutral current from the third harmonic alone96.75A

    AS/NZS 3008.1.2:2017 Cl 3.5.9

  8. Current to pick the cable on116.28A

    AS/NZS 3008.1.2:2017 Cl 3.5.9

  9. Harmonic current of one phase, third and higher38.86A
  10. Cl 3.5.2(b)(i) minimum for the neutral38.86A

    AS/NZS 3000:2018 Cl 3.5.2(b)(i)

  11. K-factor3.59

About this calculator

How this is calculated

Electronic loads draw current in pulses, not as a smooth wave. A power quality analyser splits that current into the fundamental and its harmonics, each shown as a percent of the fundamental. The tool takes the true rms phase current and that spectrum, from the third to the fifteenth order.

The total harmonic distortion is the rms of all the harmonic percents. The fundamental current is the rms current divided by the square root of one plus the distortion squared.

The third, ninth and fifteenth harmonics are the triplens. In the three phases they are in step, so they add in the neutral instead of cancelling. With equal phases the neutral carries three times one phase's triplen current. That is the tool's main answer.

AS/NZS 3008.1 Table 2 bands the third harmonic as a percent of the phase current. So the tool converts the analyser's percent of the fundamental to a percent of the rms current. It reads the band through the cable size tool's own path, and gives the reduction factor, whether the cable is picked on the phase or the neutral current, and the current to carry to cable size.

AS/NZS 3000 Cl 3.5.2(b)(i) gives a minimum for the neutral of a substantial harmonic load: the out-of-balance current plus one phase's harmonic current. Size the neutral for the larger of it and the triplen figure. AmpSize reads the harmonic current as the rms of the third and higher orders. Note 1 sets what substantial means.

The K-factor weights each harmonic by its order squared, because eddy current loss in a transformer rises with frequency squared. A clean load gives 1.

StepTable or clauseWhat it decides
DistortionThe rms of the harmonic percentsThe THD and the fundamental current
Triplen neutralThree times one phase's triplensThe neutral current of three equal phases
Third harmonic bandTable 2The reduction factor and the basis the cable is picked on
Neutral of the third harmonicCl 3.5.9The current the cable is picked on above the middle band
Clause neutralCl 3.5.2(b)(i)The out-of-balance current plus one phase's harmonic current
Substantial loadCl 3.5.2(b)(i) Note 1Whether the clause figure applies
K-factorEach order squared, weighted by its shareThe transformer K rating to pick at or above

Worked examples

Limits

The tool assumes three equal phases with the same spectrum. A real board has a mix. Enter the worst phase's readings for a safe answer.

It does not work voltage distortion, resonance with power factor capacitors or filter design. Those need the supply's impedance and a harmonic study.

See also: Neutral current, Cable size and Transformer.

Questions

Each answer describes what this tool calculates. The result is a design aid. Verify against the current standard.

How do you calculate harmonic neutral current?

The third, ninth and fifteenth harmonics of the three phases are in step, so they add in the neutral. With equal phases the neutral carries three times one phase’s triplen current. The tool works it from the phase current and the spectrum.

What is THD of current?

Total harmonic distortion is the rms of all the harmonic currents over the fundamental, as a percent. An analyser shows each order as a percent of the fundamental. The tool takes those and gives the THD and the fundamental current.

What is a K-factor?

It weights each harmonic by its order squared, because eddy current loss in a transformer rises with frequency squared. A clean load is K-1. Pick a transformer K rating at or above the figure. The rating steps are not in a standard AmpSize holds.

When does the cable size go on the neutral current?

AS/NZS 3008.1 Table 2 bands the third harmonic as a percent of the phase current. Above 33 % the cable is picked on the neutral current. The tool gives the factor, the basis and the current to carry to cable size.

What does AS/NZS 3000 ask of a harmonic load?

Cl 3.5.2(b)(i) adds the third and higher harmonic current to the out-of-balance current for the neutral, taking 100 % of the highest phase’s harmonic current. Note 1 calls a harmonic load of 40 % or more of a phase’s load substantial.

Clauses and tables this tool reads

Every clause and table, with how each was verified

Tables last checked on 2 Oct 2026.

Was this useful?

A question, or a value that looks wrong? Contact us.