Maximum circuit length calculator

Longest run that voltage drop and the fault loop allow.

Reads AS/NZS 3008.1.2:2017 (NZ) and AS/NZS 3000:2018. Tables checked 26 Sept 2026.

Inputs

A worked example with the default inputs.

Active conductor
2.5 mm²
Earth conductor
2.5 mm²
Insulation
PVC
Protective device
Type B circuit-breaker
Device rating
20 A
Phases
Single phase
Nominal phase voltage
230 V
Design current
20 A
Power factor
0.9
Voltage drop limit
5 %

Maximum route length

35.26m

Fault loop route length
128m
Voltage drop route length
35.26m
Governing check
Voltage drop

This result is a design aid. Verify it against the current standard.

Calculation steps

  1. Fault loop route length128m

    AS/NZS 3000:2018 Table B1

  2. Resistance of the copper conductor at operating temperature9.01Ω/km

    AS/NZS 3008.1.2:2017 Table 30, Tables 34 to 35

  3. Reactance0.1Ω/km

    AS/NZS 3008.1.2:2017 Table 30, Tables 34 to 35

  4. Voltage drop per amp metre16.31mV/A·m

    AS/NZS 3008.1.2:2017 Table 30, Tables 34 to 35

  5. Voltage the drop limit is taken from230V

    AS/NZS 3000:2018 Cl 3.6.2

  6. Voltage drop limit11.5V

    AS/NZS 3000:2018 Cl 3.6.2

  7. Voltage drop route length35.26m

    AS/NZS 3000:2018 Cl 3.6.2

  8. Governing lengthResult35.26m

    AS/NZS 3000:2018 Cl 3.6.2

About this calculator

How this is calculated

The tool finds the longest final subcircuit route that two limits each allow. It reports which limit governs. It reads AS/NZS 3000:2018 and AS/NZS 3008.1.2:2017.

  1. Fault loop length. The tool reads the route length for your breaker, size and earth size from Table B1.
  2. Resistance and reactance. It reads these for the active conductor. The tables are Table 30 and Tables 34 and 35, for copper at operating temperature.
  3. Millivolts per ampere metre. It combines both values with your power factor.
  4. Voltage drop limit. Cl 3.6.2 sets the limit. You enter it as a percentage of the supply voltage.
  5. Voltage drop length. It finds the route length at which the drop equals the limit for your design current.
  6. Governing length. The shorter of the two lengths is the maximum route length.
StepTable or clauseWhat it decides
Fault loop lengthAS/NZS 3000:2018 Table B1The longest route for the breaker to trip
Cable dataAS/NZS 3008.1.2:2017 Tables 30, 34 and 35Resistance and reactance
Voltage drop lengthAS/NZS 3000:2018 Cl 3.6.2The longest route within the drop limit

Worked example

  • 2.5 mm² on a 20 A type B breaker. The earth is 2.5 mm², with PVC insulation, on a single‑phase 230 V supply. The design current is 20 A at a power factor of 0.9. The fault loop route length is 128 m. The voltage drop route length is 35.26 m. The voltage drop governs, so the maximum route length is 35.26 m.

Limits

The tool assumes copper conductors. The reactance is the Table 30 value for a multicore cable. A single‑core run reads a higher reactance for its formation.

The tool does not check the current rating of the cable. It does not add correction factors. Use the cable size calculator for the full check.

See also: Maximum length of a 20 A final subcircuit, The voltage drop limit in Cl 3.6.2 and the voltage drop calculator.

Questions

The result is a design aid. Verify against the current standard.

What does the maximum circuit length tool do?

The tool reports two lengths. The first is the route length that still allows the protective device to disconnect in time. The second is the length at which the voltage drop reaches your limit. The shorter of the two governs the run.

Where do the two lengths come from?

The fault loop length comes from AS/NZS 3000:2018 Table B1 for a 0.4 s disconnection time at 230 V, scaled by your nominal voltage. The voltage drop length uses the resistance and reactance from AS/NZS 3008.1.2:2017 Tables 30, 34 and 35, against Clause 3.6.2.

Why does a combination show no fault loop length?

Table B1 tabulates a fixed list of conductor pairs and device ratings. A pair that is not printed has no tabulated length, so the tool reports the voltage drop length only. Use the loop impedance tool to check that combination instead.

Clauses and tables this tool reads

Every clause and table, with how each was verified

Tables last checked on 26 Sept 2026.