Skip to content
AmpSize

Correction factor calculator

Read each correction factor and the rating a cable needs.

Reads AS/NZS 3008.1.2:2017 (NZ), AS/NZS 3008.1.1:2017 and 2025 (AU) and AS/NZS 3000:2018. Tables checked 27 Sept 2026.

Try a job 7

Each job fills in example values. Replace them with your values.

Inputs

Worked example with the default inputs. The live calculator replaces it when the page loads.

Standard
NZ · AS/NZS 3008.1.2
Installation method
Enclosed in air
Ambient temperature
40 °C
Grouped circuits
3
Phases
Single phase
Design current
32 A
Cable size
6 mm²
Material
Copper
Insulation
PVC 75 °C
Cores
Multicore
Cables in parallel
1

Combined correction factor

0.62x

Required tabulated current
51.95A
Tabulated rating of 6 mm²
38A
Corrected rating Iz
23.41A
Ambient correction factor
0.88x
Grouping correction factor
0.7x

This result is a design aid. Verify it against the current standard.

Calculation steps

  1. Ambient correction factor0.88x

    AS/NZS 3008.1.2:2017 Table 27(1) p.88

  2. Grouping correction factor0.7x

    AS/NZS 3008.1.2:2017 Tables 22, 25(1), 25(2) p.79, p.84–85

  3. Combined correction factorResult0.62x
  4. Required tabulated current51.95A

    AS/NZS 3000:2018 Cl 3.4

  5. Tabulated rating of 6 mm²38A

    AS/NZS 3008.1.2:2017 Table 13 p.62–64

  6. Corrected rating Iz23.41A

    AS/NZS 3000:2018 Cl 3.4

About this calculator

How this is calculated

The tool reads every factor that lowers or raises the current a cable can carry on your route. It is the same code the cable size calculator runs before it tests each size.

  1. Ambient. It reads the factor for the air temperature, or the soil temperature on a buried route. AS/NZS 3008.1.2 rates New Zealand cables for 30 °C air and 15 °C soil. AS/NZS 3008.1.1 rates Australian cables for 40 °C air and 25 °C soil, so a cooler route gives a factor above 1.
  2. Grouping. It reads the factor for the circuits that share the route, by how they sit. On a tray, ladder, rack or cleats, pick the cable support. Each parallel cable set counts as a circuit.
  3. Buried cable. For a buried route it reads the soil thermal resistivity factor and the burial depth factor. Cable buried direct reads its depth factor by conductor size.
  4. Harmonics. On three phases with third harmonic current, it reads the reduction factor. Above 33 %, it sizes on the neutral current.
  5. Product. It multiplies the factors into one correction factor (derating factor in 2017). It divides the design current by that factor to give the tabulated current the cable needs.
  6. One size. It reads the tabulated rating of the size you pick and multiplies it by the factor. The result is Iz, which it checks against the design current.
StepTable or clauseWhat it decides
AmbientTables 27(1) and 27(2)The factor for the air or soil temperature
GroupingTables 22, 25(1) and 25(2)The factor for circuits run together
Cable supportTables 23 and 24The factor on a tray, ladder, rack or cleats
Buried cableTable 29, Tables 28(1) and 28(2)The factors for soil resistivity and depth
HarmonicsTable 2 and Cl 3.5.9The reduction for third harmonic current in the neutral
Required currentAS/NZS 3000 Cl 3.4The current the cable must carry in the table
Current ratingTable 13 or 14 for multicore, Tables 4, 5, 7 and 8 for single coreThe tabulated rating of the size you pick

Tables without a standard named are in the part of AS/NZS 3008.1 you pick. AS/NZS 3008.1.1:2025 numbers them by section, such as Table 3.44 for Table 27(1).

Common routes, worked with the tool

Each line states its route. Every line uses multicore copper cable with PVC insulation, except where a line names single-core cable.

New Zealand and Australia

The Standard select picks the part of AS/NZS 3008.1 the tool reads. For Australia, the Edition select picks 2025 or the superseded 2017 edition. The 2025 edition changed several ambient and grouping factors, so run both when you check an older design.

To size the cable from these factors, use the cable size calculator. To check a cable that is already installed, use the circuit check.

Questions

Each answer describes what this tool calculates. The result is a design aid. Verify against the current standard.

Is a correction factor the same as a derating factor?

Yes. AS/NZS 3008.1.1:2025 calls them correction factors. The 2017 parts call them derating factors. Both multiply the tabulated rating to give the current the cable carries on your route.

How do I combine the factors?

Multiply them. Ambient, grouping, soil resistivity, burial depth and the harmonic factor each apply to the rating. Divide the design current by the product to get the tabulated current the cable needs.

Why does an Australian cable at 30 °C get a factor above 1?

AS/NZS 3008.1.1 rates cables for 40 °C air and 25 °C soil. A cooler route lets the cable carry more. AS/NZS 3008.1.2 rates New Zealand cables for 30 °C air and 15 °C soil.

Do parallel cables count as grouped circuits?

Yes. Each cable set of a parallel circuit counts as a circuit in the group. Three circuits of two parallel sets read the factor for six circuits.

Why is the depth factor different for a bigger cable?

For a cable buried direct, the depth table bands the factor by conductor size: up to 50 mm², above 50 up to 300 mm², and above 300 mm². The tool reads the band of the size you pick.

Clauses and tables this tool reads

Every clause and table, with how each was verified

Tables last checked on 27 Sept 2026.

Was this useful?

A question, or a value that looks wrong? Contact us.