AS/NZS 3008.1.2:2017
Table 13
Current ratings, multicore cable with three or four cores, thermoplastic 75 °C
The cable size tool reads the printed rating here for a thermoplastic multicore cable, in copper or aluminium, for each installation method. That figure is the starting point, before any derating.
Verified: read against the printed standard, pages 62–64. Checked 24 Sept 2026.
Units: Rating A
These are the values AmpSize encodes. No text of the standard is reproduced. Verify against the current standard.
19 rows
| Size | Unenclosed spaced | Unenclosed touching | Unenclosed sun | Enclosed air | Insulation partial | Insulation partial enclosed | Insulation complete | Insulation complete enclosed | Buried direct | Underground enclosure | Al unenclosed touching | Al unenclosed spaced | Al unenclosed sun | Al enclosed air | Al insulation partial | Al insulation partial enclosed | Al insulation complete | Al insulation complete enclosed | Al buried direct | Al underground enclosure |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | 15 | 14 | 10 | 13 | 10 | 10 | 7 | 6 | 15 | 15 | — | — | — | — | — | — | — | — | — | — |
| 1.5 | 18 | 17 | 14 | 16 | 14 | 13 | 9 | 8 | 20 | 20 | — | — | — | — | — | — | — | — | — | — |
| 2.5 | 26 | 25 | 19 | 23 | 19 | 18 | 13 | 11 | 28 | 28 | — | — | — | — | — | — | — | — | — | — |
| 4 | 35 | 33 | 26 | 29 | 26 | 23 | 17 | 15 | 36 | 36 | — | — | — | — | — | — | — | — | — | — |
| 6 | 46 | 42 | 33 | 38 | 34 | 30 | 22 | 18 | 46 | 46 | — | — | — | — | — | — | — | — | — | — |
| 10 | 62 | 58 | 44 | 50 | 47 | 40 | 29 | 25 | 61 | 61 | — | — | — | — | — | — | — | — | — | — |
| 16 | 82 | 78 | 58 | 66 | 62 | 54 | 39 | 33 | 106 | 80 | 60 | 64 | 46 | 51 | 48 | 41 | 30 | 26 | 83 | 62 |
| 25 | 111 | 104 | 76 | 87 | 83 | 68 | 52 | 43 | 138 | 103 | 81 | 86 | 59 | 67 | 65 | 54 | 40 | 33 | 107 | 80 |
| 35 | 137 | 128 | 93 | 107 | 103 | 86 | 64 | 54 | 165 | 125 | 99 | 106 | 73 | 83 | 79 | 66 | 49 | 41 | 129 | 98 |
| 50 | 166 | 156 | 113 | 128 | 124 | 101 | — | — | 196 | 150 | 121 | 129 | 88 | 99 | 97 | 79 | — | — | 152 | 116 |
| 70 | 211 | 196 | 140 | 162 | 157 | 130 | — | — | 241 | 187 | 153 | 163 | 109 | 127 | 122 | 100 | — | — | 187 | 145 |
| 95 | 260 | 243 | 171 | 202 | 194 | 162 | — | — | 289 | 229 | 188 | 202 | 132 | 156 | 150 | 125 | — | — | 224 | 177 |
| 120 | 302 | 282 | 196 | 230 | 226 | 185 | — | — | 330 | 261 | 219 | 235 | 153 | 179 | 176 | 144 | — | — | 256 | 202 |
| 150 | 345 | 321 | 221 | 260 | 258 | 207 | — | — | 370 | 293 | 250 | 268 | 172 | 202 | 200 | 162 | — | — | 287 | 228 |
| 185 | 397 | 369 | 251 | 300 | 295 | 241 | — | — | 417 | 334 | 288 | 310 | 196 | 235 | 231 | 188 | — | — | 326 | 261 |
| 240 | 470 | 437 | 292 | 360 | 350 | 288 | — | — | 482 | 395 | 343 | 368 | 228 | 283 | 274 | 226 | — | — | 378 | 309 |
| 300 | 538 | 499 | 328 | — | — | — | — | — | 542 | 444 | 393 | 424 | 259 | — | — | — | — | — | 427 | 350 |
| 400 | 620 | 575 | 372 | — | — | — | — | — | 613 | 515 | 458 | 495 | 296 | — | — | — | — | — | 488 | 411 |
| 500 | 702 | 651 | 414 | — | — | — | — | — | 682 | 574 | 526 | 568 | 335 | — | — | — | — | — | 551 | 464 |
Tools that read it (4)
Guides and learn pages that cite it (25)
- Hot water cylinder cable size for a 3 kW element
- How many amps can 1.5 mm² cable carry?
- How many amps can 10 mm² cable carry?
- How many amps can 16 mm² cable carry?
- How many amps can 2.5 mm² cable carry?
- How many amps can 6 mm² cable carry?
- What size cable for a 22 kW EV charger?
- What size cable for a 25 A circuit?
- What size cable for a lighting circuit in NZ?
- What size cable for power points in NZ?
- Three circuits in a hot ceiling: correction factor
- What size breaker for 4 mm² cable
- Cable size for a 20 A heat pump circuit in summer
- AmpSize vs jCalc vs free cable sizing tools
- EV charger cable size for a 7 kW 32 A circuit
- AS/NZS 3008.1.2 Tables 22 to 29: derating
- AS/NZS 3008.1.1 vs 3008.1.2: AU and NZ conditions
- AS/NZS 3008.1.2 Tables 4 to 21: current ratings
- AS/NZS 3008 Table 13 (now 3.18): multicore ratings
- AS/NZS 3008 vs BS 7671: cable sizing compared
- AWG and the NEC for NZ and AU electricians
- Motor full load current: 11 kW 400 V DOL
- Cable size for a 32 A single‑phase 25 m run
- Current-carrying capacity and derating
- Checking an existing circuit