Skip to content
AmpSize

AS/NZS 3008.1.2:2017

Table 29

Rating factors for thermal resistivity of the soil

The cable size and correction factors tools read the factor for the thermal resistivity of the soil. It applies only to buried cables.

Verified: read against the printed standard, pages 90. Checked 24 Sept 2026.

Units: Resistivity K·m/W

These are the values AmpSize encodes. No text of the standard is reproduced. Verify against the current standard.

Back to its card on the AS/NZS 3008.1.2:2017 page

8 rows

Table 29, Rating factors for thermal resistivity of the soil
Resistivity (K·m/W)Multicore buried directSingle core buried directMulticore in enclosureTwo single core in enclosureThree single core in enclosureFactor
0.81.091.161.031.061.081.09
0.91.071.111.021.041.061.07
11.041.071.021.031.041.04
1.2111111
1.50.920.90.950.940.920.92
20.810.80.880.860.830.81
2.50.740.720.830.80.770.74
30.690.660.780.750.710.69

Tools that read it (3)

Guides and learn pages that cite it (4)