Transformer calculator

Calculate transformer full load current and impedance.

No standard

Inputs

A worked example with the default inputs.

Rating
500 kVA
Phases
Three phase
Primary voltage
11,000 V
Secondary voltage
400 V
Impedance
6 %

Secondary full load current

721.69A

Primary full load current
26.24A
Secondary fault current
12,028.13A

This result is a design aid. Verify it against the current standard.

Calculation steps

  1. Primary full load current26.24A
  2. Secondary full load currentResult721.69A
  3. Secondary fault current12,028.13A

About this calculator

How this is calculated

The tool gives the full load currents of a transformer and its secondary fault current. It uses the rating and the impedance from the nameplate.

  1. Inputs. You enter the rating in kVA and the number of phases. You also enter both voltages and the impedance in percent.
  2. Primary full load current. On three phases, I = kVA × 1000 ÷ (√3 × primary voltage). On one phase, it divides by the voltage alone.
  3. Secondary full load current. The tool applies the same formula at the secondary voltage.
  4. Secondary fault current. It divides the secondary full load current by the impedance as a fraction. For 6 %, that means dividing by 0.06.

The tool reads no table. You enter the voltages and the impedance.

Worked example

Limits

The fault current assumes an infinite upstream source. A real source has impedance, so the true fault current is lower. Use the fault level calculator to include the source. The tool does not model the cable after the transformer. It does not size the protection. Impedance is a nameplate value with a tolerance.

Use the primary current to check the supply side device. Use the secondary current to check the main switch and the busbar. Take the impedance from the nameplate, because it has a tolerance.

See also: Transformer full load current, 1000 kVA at 11 kV, Transformer secondary fault current, 500 kVA and Prospective fault current at a board.

Questions

The result is a design aid. Verify against the current standard.

What does the transformer calculator do?

The tool reports the primary full load current, the secondary full load current and the secondary fault current. It works from the rating in kilovolt amperes, the primary and secondary voltages, the impedance percent and the phase count.

Which inputs matter most?

The rating and the two voltages set the two full load currents. The impedance percent sets the secondary fault current: a lower impedance gives a higher fault current. The phase count applies the square root of three to both currents.

What are the common gotchas?

The fault current assumes an infinite upstream source, so it is a worst case figure and the tool says so with every result. Cable and network impedance are not included. The impedance percent is limited to 30. The inputs sit in the page address, so a link reproduces the result.