AS/NZS 3008.1.2:2017

Table 23

Grouping factors for single‑core circuits on trays, ladder supports, racks and cleats in air

The cable size and correction factors tools read the factor for single‑core circuits on a tray, a ladder, a rack or cleats. The factor depends on the support, the tiers, and whether the circuits touch.

Verified: read against the printed standard, pages 80. Checked 26 Sept 2026.

Units: Tiers count, Count circuits per tier or row

These are the values AmpSize encodes. No text of the standard is reproduced. Verify against the current standard.

Back to its card on the AS/NZS 3008.1.2:2017 page

22 rows

Table 23, Grouping factors for single-core circuits on trays, ladder supports, racks and cleats in air
ItemInstallationSpacingTiers (count)Factors
1unperforated-traystouching10.95, 0.85, 0.84
2unperforated-traystouching20.92, 0.83, 0.79
3unperforated-traystouching30.91, 0.82, 0.76
4perforated-traystouching10.97, 0.89, 0.87
5perforated-traystouching20.94, 0.85, 0.81
6perforated-traystouching30.93, 0.84, 0.79
7ladder-supports-racks-cleatstouching11, 0.95, 0.94
8ladder-supports-racks-cleatstouching20.95, 0.9, 0.88
9ladder-supports-racks-cleatstouching30.95, 0.89, 0.85
10vertical-perforated-traystouching10.94, 0.85, —
11vertical-perforated-traystouching20.92, 0.83, —
12unperforated-traysspaced10.95, 0.95, 0.94
13unperforated-traysspaced20.92, 0.91, 0.87
14unperforated-traysspaced30.91, 0.9, 0.85
15perforated-traysspaced10.97, 0.97, 0.96
16perforated-traysspaced20.94, 0.93, 0.89
17perforated-traysspaced30.93, 0.92, 0.86
18ladder-supportsspaced11, 1, 1
19ladder-supportsspaced20.95, 0.95, 0.93
20ladder-supportsspaced30.95, 0.94, 0.9
21vertical-perforated-traysspaced11, 0.91, 0.89
22vertical-perforated-traysspaced21, 0.9, 0.86