Voltage drop calculator

Voltage drop calculator for New Zealand and Australia. Conductor impedance comes from AS/NZS 3008.1.2 or 3008.1.1, and the limit from AS/NZS 3000 Clause 3.6.2.

Reads AS/NZS 3008.1.2:2017 (NZ), AS/NZS 3008.1.1:2017 and 2025 (AU) and AS/NZS 3000:2018. Tables checked 27 Sept 2026.

Inputs

A worked example with the default inputs.

Supply
a.c.
Phases
Three phase
Voltage
400 V
Design current
50 A
Run length
60 m
Power factor
0.9
Standard
NZ · AS/NZS 3008.1.2
Cable
16 mm² Copper PVC 75 °C
Cores
Multicore
Voltage drop limit
5 %
System
Low voltage (limit you set)
Neutral current
0 A

Voltage drop

1.69%

Voltage drop
6.74V
Drop per amp metre
2.25mV/A·m
Maximum length at limit
177.98m
Voltage drop limit
5%

This result is a design aid. Verify it against the current standard.

Calculation steps

  1. Resistance1.4Ω/km

    AS/NZS 3008.1.2:2017 Table 30 (Xc), Tables 34–35 (Rc) p.98, p.102–103

  2. Reactance0.09Ω/km

    AS/NZS 3008.1.2:2017 Table 30 (Xc), Tables 34–35 (Rc) p.98, p.102–103

  3. mV/A·m2.25mV/A·m

    AS/NZS 3008.1.2:2017 Cl 4.5

  4. Voltage drop6.74V
  5. Voltage drop percentResult1.69%
  6. Voltage drop limit5%

    AS/NZS 3000:2018 Cl 3.6.2

  7. Maximum length177.98m

About this calculator

How this is calculated

The tool works out the drop for one cable, one run length and one current. It compares the drop with the limit for the system.

  1. Resistance and reactance. It reads the conductor resistance at its operating temperature and the reactance for your size, material, insulation and core count. The Standard select decides which part it reads. It reads AS/NZS 3008.1.2 for New Zealand or AS/NZS 3008.1.1 for Australia. Cables in parallel divide both values.
  2. Drop per ampere metre. It combines the two with the power factor. On one phase it takes 2 × (R cos φ + X sin φ). On three phases it takes √3 × (R cos φ + X sin φ). The result is in mV/A·m.
  3. Drop. It multiplies that figure by the current and the run length. It divides the volts by the nominal voltage to get the percent.
  4. Unbalanced load. On three phases with a neutral current, it works the drop on one conductor. It adds the neutral current over the neutral length and compares the drop with the phase voltage.
  5. Limit. It compares the percent with the limit for the system. It also gives the run length at which the drop reaches the limit.
  6. Single‑core cable. If you do not know the formation, the tool uses the highest reactance for single‑core cable and says so.
StepTable or clauseWhat it decides
ResistanceTables 34 and 35The conductor resistance at its operating temperature
ReactanceTable 30The reactance for the cable and, for single core, its formation
Drop per ampere metreCl 4.5How resistance, reactance and power factor combine
Unbalanced loadCl 4.6The drop with a neutral current on three phases
Low voltage limitAS/NZS 3000 Cl 3.6.2The limit for a low voltage circuit
Extra-low voltage limitAS/NZS 3000 Cl 7.5.7The limit for an extra-low voltage circuit

Tables without a standard named are in the part of AS/NZS 3008.1 you pick. Each result step names the edition it read.

The limit

SystemLimit the tool appliesClause
Low voltageThe limit you set, 5 % by defaultAS/NZS 3000 Cl 3.6.2
Extra-low voltage10 % of the nominal voltageAS/NZS 3000 Cl 7.5.7

The tool checks one run at a time. When a submain feeds a final subcircuit, add the two drops and compare the total with the limit.

Common circuits, worked with the tool

Each line states its route. Every line uses multicore copper cable with PVC insulation and the New Zealand tables. The power factor is 0.9, except where a line names a different value.

New Zealand and Australia

The Standard select picks the part of AS/NZS 3008.1 the tool reads. The limits come from AS/NZS 3000, which is the same in both countries.

d.c. circuits

Set Supply to d.c. for a battery, PV or ELV d.c. run. The tool reads the d.c. resistance of each size from AS/NZS 3008.1.1:2025 Tables 4.6(A), 4.6(B), 4.8(A) and 4.8(B). These are encoded at the maximum conductor temperature: 75 °C for PVC and 90 °C for XLPE. Single‑core cable reads Table 4.6, multicore Table 4.8. The tool takes 2 × current × resistance × length for the two wires. It uses no reactance, no power factor and no phases. AS/NZS 3008.1.2:2017 prints no d.c. tables, so New Zealand reads the 2025 part too. The limit follows the System select, as on a.c.

The DC cable size calculator reads the printed d.c. mV/A.m of Tables 4.16 to 4.23 instead, which is twice the resistance rounded. Its drop can differ from this tool in the last digit.

Keep the result

Every input sits in the page address, so the link in your browser reproduces the calculation. The PDF button prints the result with its steps and table references. Saving a calculation to a project needs a free account.

See also: AS/NZS 3000 Clause 3.6.2: voltage drop limit, Voltage drop with the mV/A·m method and Voltage drop basics.

Questions

The result is a design aid. Verify against the current standard.

What does the voltage drop calculator do?

The tool reads the resistance and reactance of the conductor. It combines them at the power factor to get the drop in millivolts per amp metre. It then reports the drop in volts and the longest run that still meets the limit. It also gives the drop as a percent of the supply voltage.

What voltage drop limit does AS/NZS 3000 set?

The default limit is 5 % and you can change it. Choosing extra-low voltage sets the limit to 10 % from AS/NZS 3000:2018 Clause 7.5.7. A result above the limit is marked as a fail and a warning appears above 80 % of the limit. Impedance comes from AS/NZS 3008.1.2:2017 Table 30 and Tables 34 to 35.

Which inputs change the voltage drop most?

Design current and run length scale the drop directly. Conductor size, material and insulation set the resistance and reactance. Power factor sets how much reactance adds to the drop. Cables in parallel divide both resistance and reactance by the number of cables.

Why does a three phase result differ from a single phase result?

The tool multiplies by the square root of three for a three phase result. It multiplies by two for a single phase result, because the current flows out and back. The same cable and current therefore give a different drop on each supply type. For a d.c. circuit, use the DC cable size tool.

Can I work out d.c. voltage drop?

Yes. Set Supply to d.c. The tool reads the d.c. resistance of AS/NZS 3008.1.1:2025 at the maximum conductor temperature, in both countries. It takes 2 × current × resistance × length for the two wires, with no reactance or power factor. To size a d.c. cable, use the DC cable size calculator.

Worked examples

All 11 guides for this calculator

Background

Clauses and tables this tool reads

Every clause and table, with how each was verified

Tables last checked on 27 Sept 2026.