Skip to content
AmpSize

· 3 min read

Fault level at a sub-board, 300 kVA transformer

Fault level calculator

+1 reference

Worked to AS/NZS 3008.1.2:2017 (NZ) and AS/NZS 3000:2018. Tables checked 27 Sept 2026.

A drawn result card from the Fault Level at a Board tool: three-phase fault current at the board 7.59 kA.

Every circuit-breaker has a breaking capacity, in kA. The fault current at its terminals has to stay below it. This guide works the fault level at one sub-board with the fault level tool, then checks two breaker ranges against it. The method is explained in Prospective fault current at a board.

The tool is an estimate by the impedance method. The network operator's figure, or a measurement, rules where you have one.

The site

  • A 300 kVA, 400 V transformer with 4 % impedance, on the site.
  • A sub-board 45 m away, fed by a 50 mm² copper PVC multicore submain in New Zealand.
  • The protective conductor is 16 mm², from Table 5.1.
  • The board is planned with 6 kA miniature circuit-breakers.

Step 1. The transformer

The transformer impedance per phase is U² ÷ S × Z%:

400² ÷ 300 000 × 0.04 = 0.02133 Ω

The phase voltage is 400 ÷ √3 = 230.9 V. At the transformer terminals the fault current is 230.9 ÷ 0.02133 = 10.83 kA. The tool takes the network above the transformer as infinite, and the transformer impedance as all reactance. Both choices give the highest current for these figures.

Step 2. The submain

The impedance tables give the 50 mm² resistance at 75 °C and its reactance. A cold cable passes the most current, so the tool scales the resistance down to 20 °C for the maximum.

FigureValue
Phase resistance at 75 °C, 45 m0.0212 Ω
Phase resistance at 20 °C, 45 m0.01743 Ω
Phase reactance, 45 m0.00359 Ω
Protective conductor at 20 °C, 16 mm²0.0518 Ω

Step 3. The three-phase fault current

The resistance and the reactance add at right angles:

|Z| = √(0.01743² + (0.02133 + 0.00359)²) = 0.0304 Ω

230.9 ÷ 0.0304 = 7.59 kA at the board. The submain cut the fault current from 10.83 kA to 7.59 kA.

Step 4. The phase-earth fault current

The loop runs out on the phase conductor and back on the protective conductor. At a Dyn transformer, the tool takes the source loop as the phase impedance. The maximum, with the cable cold, is 3.14 kA. With the cable at 75 °C it is 2.63 kA. The lower figure is the one for disconnection time: take it to the loop impedance tool.

Step 5. Check the breakers

BreakersBreaking capacityFault levelResult
Planned6 kA7.59 kAFails
Next range up10 kA7.59 kAPasses, 2.41 kA margin

The 6 kA breakers are too small for this board. A 10 kA range passes. A longer submain lowers the fault level too: at 90 m the board sees 5.13 kA. Choose the breaker range for the board as built, not the cable you hope to run.

Step 6. Carry the figure on

The result carries a button, Check a cable's fault rating. It opens the fault rating tool with 7.59 kA filled in, for the cables that leave the board.

The result

BoardThree-phasePhase-earth, coldPhase-earth, hot
At the transformer10.83 kA10.83 kA10.83 kA
45 m of 50 mm²7.59 kA3.14 kA2.63 kA
90 m of 50 mm²5.13 kA1.63 kA1.35 kA

See also: Short-circuit withstand and the k factor and Industrial switchboards.

Try it with these inputs

Circuit-breaker breaking capacity
6
Transformer impedance
4
Transformer rating
300
Submain length
45
Conductor size
50
Open the calculator with these inputs

Where next

The ideas behind it

More worked examples

AmpSize is a design aid. Verify results against the current standard.

Was this useful?

A question, or a value that looks wrong? Contact us.