Skip to content
AmpSize

UPS size and battery run time

Size a UPS and its battery for a run time.

AS/NZS 3000

Reads AS/NZS 3000:2018. Tables checked 2 Oct 2026.

Try a job 4

Each job fills in example values. Replace them with your values.

Inputs

Worked example with the default inputs. The live calculator replaces it when the page loads.

Loads on the UPS
3 rows
Headroom for growth
25 %
UPS output power factor
0.9
Run time on battery
15 min
Battery bus voltage
96 V
Inverter efficiency on battery
92 %
Ageing factor
1.25
Recharge time
8 h
Input phases
Single phase
Input voltage
230 V
UPS efficiency on mains
94 %
Input power factor
0.99

UPS rating, at least

1.86kVA

Typical size
2 kVA
Load
1,340W
Battery energy
455Wh
Battery capacity at the bus
4.7Ah
Input current
6.5A

This result is a design aid. Verify it against the current standard.

Calculation steps

  1. Load, real power1,340W
  2. Load, apparent power1,424.6VA
  3. kVA for the load with 25 % headroom1.78kVA
  4. kVA for its kW at a UPS power factor of 0.91.86kVA
  5. UPS rating, at leastResult1.86kVA
  6. Typical size2 kVA
  7. Battery energy for 15 min, with ageing455Wh
  8. Battery capacity at 96 V4.7Ah
  9. Input power with recharge in 8 h1,488W
  10. Input current6.5A

About this calculator

How this is calculated

A UPS has two sizes that matter: the power its inverter can deliver, and the energy its battery holds. This tool works both from a list of what the UPS supplies, then the current it draws from the supply.

You list each load with how many there are, the real power each draws in watts and its power factor. The tool adds the watts, and it adds each load's apparent power. With your headroom for growth on top, the UPS needs at least that many kVA, and its kW rating, its kVA times its output power factor, must cover the watts. The larger of the two is the rating. The tool also names the next typical size up; the sizes are common ratings, not a standard's list.

The battery must hold the load's watts for the run time, divided by the inverter's efficiency, times an ageing factor so it still lasts when old. Divided by the bus voltage that gives Ah, but at the run time's rate: a battery gives far less than its 10 or 20 hour Ah over a short run, so the maker's discharge table decides the battery.

The input is the load through the UPS's efficiency plus the power to recharge the battery in the time you set. AmpSize does not hold AS 62040, so the headroom, efficiencies and ageing factor are your assumptions. The result names the AS/NZS 3000 rules for converters.

StepTable or clauseWhat it decides
LoadWatts added, and each load's apparent powerThe power the UPS supplies
RatingThe larger of the kVA and the kW at the output power factorThe UPS rating with headroom
Battery energyLoad times run time, over efficiency, times ageingThe energy at the battery bus
Battery capacityEnergy over the bus voltage, at the run time's rateThe Ah to look up in a maker's table
Input currentLoad over efficiency, plus rechargeThe current for the supply cable
InstallationAS/NZS 3000 Cl 4.12.4.2, Cl 4.12.5.1, Cl 4.12.5.2.2 and Cl 4.12.7The switch, protection, RCD and neutral rules

Worked examples

Limits

The battery figure is the energy and Ah at the run time's rate. It does not pick cells: read the maker's constant-power discharge table at your end voltage and temperature. The tool does not model a UPS in parallel, redundancy such as N+1, the bypass supply, or a generator behind the UPS; for that, size the generator for the UPS's input.

See also: Generator sizing, Battery and Cable size.

Questions

Each answer describes what this tool calculates. The result is a design aid. Verify against the current standard.

How do I size a UPS?

Add the watts of everything it supplies, and their VA. Add headroom for growth. The UPS kVA must cover the VA, and its kW rating, kVA times its output power factor, must cover the watts.

How much battery do I need for a run time?

The energy is the load in watts times the hours, divided by the inverter efficiency, times an ageing factor. Divide by the bus voltage for Ah, at the run time rate, then read the maker discharge table.

Why is the Ah so different from the battery label?

A label gives the Ah over 10 or 20 hours. Over 15 minutes the same battery gives much less, so a UPS battery is chosen from a constant-power discharge table, not the label.

What size cable feeds a UPS?

Size it for the input current: the load through the UPS efficiency, plus the power to recharge the battery. The tool gives that current to carry into the cable size tool.

What does AS/NZS 3000 say about a UPS?

Cl 4.12 covers converters, including UPS. The neutral to the load stays unbroken through bypass, the output protection sits within 15 m, and a switch beside the batteries breaks their supply.

Clauses and tables this tool reads

Every clause and table, with how each was verified

Tables last checked on 2 Oct 2026.

Was this useful?

A question, or a value that looks wrong? Contact us.