AmpSize

Glossary

The terms the calculators and the guides use, each in AmpSize's own words. A term names a clause or a table by number only. No text of a standard is reproduced here.

A

Adiabatic check
A fault check that assumes no heat leaves the conductor during the fault. It gives the minimum size from S = √(I²t) / k.
Fault rating calculatorShort-circuit withstand and the k factor
AWGAmerican Wire Gage
The North American system of wire sizes. A smaller gauge number is a larger wire.
AWG and the NEC for NZ and AU electriciansImperial cable calculator

C

Cable group
Circuits that run close enough together to heat one another. AS/NZS 3008.1.1:2025 defines the term, and a grouping factor applies to it.
GroupingAS/NZS 3008 Table 22 (now 3.33): bunched groupingCable size calculator
Circuit
The conductors that one protective device protects, from the switchboard to the load. The AS/NZS 3008.1 grouping tables count circuits.
Cable size calculatorCurrent-carrying capacity and derating
Consumer mains
The conductors between the point of supply and the main switchboard.
Cable size calculatorPoint of supply
Correction factorCF, derating factor, rating factor
A multiplier that adjusts a tabulated rating for a condition that differs from the reference. AS/NZS 3008.1.1:2025 uses this term, where 2017 said derating factor.
Current-carrying capacity and deratingAS/NZS 3008.1.1:2025: what changed from 2017AS/NZS 3008.1.2:2017 on the standards page
Current-carrying capacityCCC, current rating
The current a cable carries continuously before its insulation reaches its temperature limit. It changes with the installation and the site conditions.
Current-carrying capacity and deratingCable size calculator

D

d.c.direct current
Current that flows in one direction only, as from a battery or a PV array. AmpSize writes it as d.c.
Battery calculatorIEC 60364 and the Wiring Rules
Diversity
The allowance for loads that do not all run at full load at the same time. It makes the maximum demand less than the connected load.
Maximum demand and diversityMaximum demand calculator

E

ELVextra-low voltage
A voltage of 50 V a.c. or less, or 120 V ripple-free d.c. or less. AS/NZS 3000:2018 Cl 1.4.128 sets the bands.
Voltage drop calculator

F

Final subcircuit
A circuit that runs from a switchboard to points of use, such as socket-outlets and lights.
Cable size calculatorCable size for a 32 A single-phase 25 m run

G

Grouping
Cables that run close together heat each other, so each one carries less current. A grouping factor applies that reduction.
Current-carrying capacity and deratingCable size calculator

H

Harmonics
Currents at whole multiples of the supply frequency, drawn by electronic loads. Third harmonic currents add together in the neutral of a three-phase circuit.
Cable size calculator

I

Ib, In and Iz
Ib is the design current, In is the device rating and Iz is the cable capacity. A circuit needs Ib ≤ In ≤ Iz.
Ib, In and Iz
IEC 60364
The international series of standards for low voltage installations in buildings. AS/NZS 3000 stays aligned with it.
IEC 60364 and the Wiring RulesMEN system: multiple earthed neutral explained
Installation method
How and where a cable is installed, such as enclosed, unenclosed or buried. It sets the rating column that applies.
Conduit fill and installation methodsCable size calculator

K

k factor
A constant for a conductor and its insulation in the adiabatic check. It depends on the material and the start and final temperatures.
Short-circuit withstand and the k factorFault rating calculator

M

Maximum demand
The highest load that an installation or a circuit is expected to draw. AS/NZS 3000 gives methods to estimate it.
Maximum demand and diversityMaximum demand calculator
MEN systemmultiple earthed neutral
The earthing system of New Zealand and Australia. Neutral and earth join at the main switchboard, so an earth fault returns through the neutral.
MEN system: multiple earthed neutral explainedTN-C-S
mV/A·mmillivolts per ampere metre
The voltage drop of a cable for each ampere and each metre of route. Multiply it by the current and the length to get the drop.
The mV/A·m methodVoltage drop calculator

P

Point of supply
The point where the network conductors meet the consumer mains. AS/NZS 3000 measures voltage drop from this point.
AS/NZS 3000 Clause 3.6.2: voltage drop limit
Prospective fault current
The current that flows in a fault of negligible impedance at a point. The devices and the cables there must withstand it.
Prospective fault current at a main switchboardFault rating calculator

R

RCDresidual current device
A device that switches off when the current that leaks to earth goes above a set value. It protects people against electric shock.
RCD types and where they are requiredRCD selection calculator
Reference ambient
The air or soil temperature that a rating table assumes. NZ uses 30 °C air and 15 °C soil, and AU uses 40 °C and 25 °C.
AS/NZS 3008.1.1 vs 3008.1.2: AU and NZ conditionsCurrent-carrying capacity and derating
Route length
The length of a cable along its path, one way. AS/NZS 3008.1.1:2025 defines the term, and voltage drop and loop impedance grow with it.
Voltage drop calculatorDC cable size: 48 V battery and 600 V PV arrayMaximum circuit length calculator

S

Soil thermal resistivity
How strongly soil resists the flow of heat, in K·m/W. Both parts of AS/NZS 3008.1 assume 1.2 K·m/W.
AS/NZS 3008 vs BS 7671: cable sizing comparedUnderground cable calculator
Submain
A circuit that runs from one switchboard to another switchboard.
Cable size calculator

T

TN-C-S
One conductor does the neutral and protective jobs in part of the system, and separate conductors in the rest. MEN is a TN-C-S system.
IEC 60364 and the Wiring RulesMEN system: multiple earthed neutral explained

V

Voltage drop
The fall in voltage along a cable that carries current. AS/NZS 3000:2018 Cl 3.6.2 limits it to 5 % from the point of supply.
Voltage drop basicsVoltage drop calculator
Voltage rise
The increase in voltage along a cable when an inverter sends current out to the network. It is the opposite of voltage drop.
Voltage rise calculatorSolar inverter voltage rise at 5 kW

W

Wiring enclosure
A conduit, duct or trunking around a cable. A multicore cable in thermal insulation has a lower rating inside one.
Cable size calculatorConduit fill and installation methods

Z

Zeexternal earth fault loop impedance
The part of the earth fault loop impedance that is outside the installation. Zs is Ze plus the impedance of the circuit conductors.
Loop impedance calculatorZs
Zsearth fault loop impedance
The impedance of the path that an earth fault current takes, from the supply and back. A low Zs lets the device clear the fault in time.
Earth fault loop impedance and disconnection timeLoop impedance calculator