Skip to content
AmpSize

Transformer inrush and its breaker

Check a transformer’s switch-on inrush against its breaker.

AS/NZS 3000

Reads AS/NZS 3000:2018. Tables checked 2 Oct 2026.

Try a job 4

Each job fills in example values. Replace them with your values.

Inputs

Worked example with the default inputs. The live calculator replaces it when the page loads.

Rating
15 kVA
Phases
Three phase
Primary voltage
400 V
Secondary voltage
400 V
Circuits on the secondary
One, with no protection of its own
Inrush, × full load current
12
Inrush lasts
0.1 s
Breaker type
Curve C
Rating
32 A

The breaker at switch‑on

May trip

Inrush current
259.8A
Primary full load current
21.65A
Smallest Type B that holds
100 A
Smallest Type C that holds
63 A
Smallest Type D that holds
32 A
Secondary conductors, at least
21.7A

This result is a design aid. Verify it against the current standard.

Calculation steps

  1. Primary full load current21.65A
  2. Inrush, 12 × the full load current for 0.1 s259.8A
  3. Type C 32 A, typical instant band from160A
  4. Type C 32 A, typical instant band to320A
  5. The breaker at switch‑onResultMay trip
  6. Smallest Type B that holds100 A
  7. Smallest Type C that holds63 A
  8. Smallest Type D that holds32 A
  9. Secondary conductors, at least21.7A

    AS/NZS 3000:2018 Cl 4.14.2.2

About this calculator

How this is calculated

When a transformer is switched on, its core can draw a large current for a few cycles while the magnetic flux settles. This inrush can be ten or more times the full load current. It lasts about a tenth of a second, and it is often enough to trip the breaker on the primary. This tool checks whether it does, and finds a breaker that rides through it.

The tool takes the primary full load current from the transformer tool, then multiplies it by the inrush multiple you enter, for the time you enter. No standard on hand prints these two figures, so they are your assumptions. Take them from the maker's data sheet. The multiple is a peak, and the tool compares it with the breaker's band, which is given in RMS multiples of the rating, as if it were RMS: that errs towards a trip.

It then places that current on the trip band of the breaker, the same band the MCB trip curve tool draws. The breaker holds when the band's earliest trip is no sooner than the inrush lasts. It trips when the latest trip is sooner, and it may trip in between. For each type, B, C and D, the tool finds the smallest rating that carries the full load current and holds.

With one circuit on the secondary and no protection there, AS/NZS 3000 lets the secondary cable go without its own breaker if it carries the primary current scaled by the voltage ratio. The tool gives that current.

StepTable or clauseWhat it decides
Full load currentThe transformer toolThe current the inrush multiplies
InrushThe multiple and time you enterThe current and time the breaker sees
The breaker's bandAS/NZS 3000 Cl 2.5.3.1 and Table 8.1, and a typical bandHolds, may trip or trips
The secondary cableAS/NZS 3000 Cl 4.14.2.2 ExceptionThe least capacity of an unprotected secondary cable
An extra-low voltage transformerAS/NZS 3000 Cl 4.14.1 Exception 2Whether Cl 4.14 applies at all

Worked examples

Limits

The inrush depends on where on the wave the transformer is switched and on the flux left in the core, so it differs from one switch-on to the next. The tool uses one figure for the peak and one for the time. A toroidal transformer can draw much more than a laminated one. A soft-start or inrush limiter changes the figures; enter what the maker gives.

The breaker's band is typical of its type, not a maker's curve. The tool does not check a fuse or a moulded-case breaker.

See also: MCB trip curve, Transformer and Cable size.

Questions

Each answer describes what this tool calculates. The result is a design aid. Verify against the current standard.

Why does a transformer trip its breaker when switched on?

The core draws a large magnetising current for a few cycles while its flux settles. The inrush can be ten or more times the full load current. If it reaches the instant band of the breaker, the breaker may trip.

How big is transformer inrush current?

It depends on the design and on where on the wave it is switched. 10 to 12 times the full load current for about 0.1 s is a usual first guess. A toroidal transformer can draw more. The maker's data sheet gives the real figure.

Which breaker curve suits a transformer?

Often a Type D, whose typical instant band starts at 10 times its rating. A Type C needs a larger rating for the same inrush, and a Type B larger again. The tool finds the smallest of each that holds.

Does the secondary cable need its own breaker?

AS/NZS 3000 Cl 4.14.2.2 lets one unprotected secondary circuit go without, if its cable carries the primary rated current times the primary to secondary voltage ratio. With more circuits, protect each one.

Is the breaker band the maker's curve?

No. It is a typical band for the type, the same one the MCB trip curve tool draws. Where the result is May trip, check the maker's curve or pick the next rating up.

Clauses and tables this tool reads

Every clause and table, with how each was verified

Tables last checked on 2 Oct 2026.

Was this useful?

A question, or a value that looks wrong? Contact us.