Full load current calculator

Calculate full load current from power, voltage and phase.

No standard

Inputs

A worked example with the default inputs.

Phases
Three phase
Voltage
400 V
Rating unit
kW
Rating
15
Power factor
0.9
Efficiency
1

Full load current

24.06A

Apparent power drawn
16.67kVA
Output power
15kW

This result is a design aid. Verify it against the current standard.

Calculation steps

  1. Output power15kW
  2. Apparent power drawn16.67kVA
  3. Full load currentResult24.06A

About this calculator

How this is calculated

The tool works out the full load current of a load. It uses the power, the voltage, the power factor and the efficiency. It works on one phase or three. It reads no table, so it cites no clause.

  1. Supply. You pick one phase or three and enter the voltage. The voltage you enter sets the divisor in the last step.
  2. Output power. You enter the load in kW or kVA. For a kW load, the tool takes this as the output power.
  3. Apparent power drawn. It divides the output power by the efficiency and by the power factor. A kVA entry skips the power factor step.
  4. Full load current. On one phase, it divides the apparent power by the voltage. On three phases, it divides by the voltage and by the square root of three.

On three phases, enter the line voltage, such as 400 V. On one phase, enter the phase voltage, such as 230 V.

Worked example

Limits

The result is the steady running current. It is not the starting current. A motor draws more current at start. Use the motor tool for the starting current.

The tool assumes a balanced load on three phases. It does not add a margin for the cable or the breaker. Size the cable from the design current with the cable size calculator. The tool gives no harmonic or neutral current.

Efficiency is a value between 0 and 1. A kVA entry is already an apparent power, so the tool does not divide it by the power factor.

Check the efficiency you enter. A motor rating in kW is a shaft output, so enter the motor efficiency. A resistive heater has an efficiency of 1. Check the power factor on the nameplate. A low power factor raises the current for the same kW.

See also: Commercial kitchen kW to amps, Three‑phase power kVA to amps at 400 V and the three‑phase power tool.

Questions

The result is a design aid. Verify against the current standard.

What does the full load current calculator do?

The tool converts a load rating into a current. Enter the rating in kilowatts or in kilovolt amperes, the voltage and the phase count. It reports the load's full load current, its real power and its apparent power.

Which inputs matter most?

The rating and the voltage set the current. For a kilowatt rating, the power factor and the efficiency both raise the apparent power, so both raise the current. For a kilovolt ampere rating the efficiency is not applied. A three phase result divides by the square root of three.

What does this tool not do?

It does not size a cable or a protective device. It cites no standard table, because the result is a direct calculation. Use the current it gives as the design current in the cable size tool. The inputs sit in the page address, so a link reproduces the result.

Worked examples

Background

Was this useful?

A question, or a value that looks wrong? Contact us.