AS/NZS 3008.1.2:2017
Table 52, 53, 54, 55
Short-circuit K values and temperature limits
The fault rating tool reads the k factor for the conductor start temperature and the short-circuit temperature limit. The limit comes from the insulation class and the conductor size band, or from the joint in the run when the joint is the lower of the two.
Verified: read against the printed standard, pages 121–123 (PDF 125–127), with Table 1 on page 13. Checked 26 Sept 2026.
Units: K A*s^0.5/mm2, Initial temp C degC, Final temp C degC, Max size mm 2 mm2
These are the values AmpSize encodes. No text of the standard is reproduced. Verify against the current standard.
43 rows
| Kind | Material | Initial temp C (degC) | Final temp C (degC) | K (A*s^0.5/mm2) | Insulation class | Max size mm 2 (mm2) | Joint |
|---|---|---|---|---|---|---|---|
| k | Cu | 110 | 140 | 65.3 | |||
| k | Cu | 110 | 150 | 74.9 | |||
| k | Cu | 110 | 160 | 83.2 | |||
| k | Cu | 110 | 220 | 119 | |||
| k | Cu | 110 | 250 | 132 | |||
| k | Cu | 110 | 350 | 164 | |||
| k | Cu | 90 | 140 | 85.6 | |||
| k | Cu | 90 | 150 | 93.1 | |||
| k | Cu | 90 | 160 | 99.9 | |||
| k | Cu | 90 | 220 | 131 | |||
| k | Cu | 90 | 250 | 143 | |||
| k | Cu | 90 | 350 | 173 | |||
| k | Cu | 75 | 140 | 98.7 | |||
| k | Cu | 75 | 150 | 105 | |||
| k | Cu | 75 | 160 | 111 | |||
| k | Cu | 75 | 220 | 140 | |||
| k | Cu | 75 | 250 | 151 | |||
| k | Cu | 75 | 350 | 180 | |||
| k | Al | 110 | 140 | 43.2 | |||
| k | Al | 110 | 150 | 49.5 | |||
| k | Al | 110 | 160 | 55 | |||
| k | Al | 110 | 250 | 87.1 | |||
| k | Al | 90 | 140 | 56.6 | |||
| k | Al | 90 | 150 | 61.5 | |||
| k | Al | 90 | 160 | 66 | |||
| k | Al | 90 | 250 | 94.5 | |||
| k | Al | 75 | 140 | 65.2 | |||
| k | Al | 75 | 150 | 69.6 | |||
| k | Al | 75 | 160 | 73.6 | |||
| k | Al | 75 | 250 | 99.9 | |||
| insulation | 75 | 160 | thermoplastic-75 | 300 | |||
| insulation | 75 | 140 | thermoplastic-75 | ||||
| insulation | 90 | 250 | cross-linked-90 | ||||
| insulation | 110 | 250 | cross-linked-110 | ||||
| joint | 250 | exothermic-welded | |||||
| joint | 160 | soldered | |||||
| joint | 250 | compression | |||||
| sheath | thermoplastic | 200 | |||||
| sheath | polyethylene | 150 | |||||
| sheath | high-density-polyethylene | 180 | |||||
| sheath | polychloroprene-or-csp | 200 | |||||
| sheath | lead | 170 | |||||
| sheath | lead-alloy | 200 |