AS/NZS 3008.1.2:2017

Table 2

Reduction factors for harmonic currents in 4- and 5‑core cables

The correction factors tool reads the reduction factor for third harmonic current in a four‑core or five-core cable. Above 33 %, it sizes on the neutral current. The harmonics tool reads the same band from a spectrum.

Verified: read against the printed standard, pages 27–28. Checked 24 Sept 2026.

Units: Third harmonic percent %, Factor x

These are the values AmpSize encodes. No text of the standard is reproduced. Verify against the current standard.

Back to its card on the AS/NZS 3008.1.2:2017 page

4 rows

Table 2, Reduction factors for harmonic currents in 4- and 5-core cables
BandMin percentMax percentFactor (x)Basis
0–15 %0151phase
15–33 %15330.86phase
33–45 %33450.86neutral
> 45 %451neutral