Homeowner guides
What size cable a shed, a hot water cylinder or an EV charger needs.
- 3 min readWill a heat pump fit a 63 A supply?Check if a 3.5 kW heat pump fits a house with a 63 A main switch. Find the maximum demand by measurement, then cross-check it by limitation, per AS/NZS 3000.

- 5 min readWorked examples index by tool and tradeEvery AmpSize worked example in one place, grouped by calculator and tagged with the trade it was written for, from house circuits to industrial boards.

- 4 min readEV charger spare capacity on a 63 A main switchWill a 7 kW EV charger fit a house board with a 63 A main switch? Check the spare capacity, the load management case, the cable and the RCD, NZ and AU.

- 3 min readBattery bank for three days autonomy in winterBattery capacity for three days autonomy from a 6 kWh daily load at 48 V, with depth of discharge, inverter efficiency and a winter temperature factor.

- 3 min readElectricity Safety Regulations: reg 57 and 59What reg 57 and reg 59 of the Electricity (Safety) Regulations 2010 govern, and a house that reaches 100.26 A and crosses the reg 59(1) threshold of 80 A.

- 3 min readHomeowner shed supply voltage drop over 60 mA 20 A single-phase supply running 60 m to a shed on 6 mm² copper, with the drop, the percentage and the maximum length the AmpSize voltage drop engine returns.

- 5 min readOhm's law on a 3 kW water heater elementWork the current and working resistance of a 3 kW, 230 V water heater element with Ohm's law, why a cold meter reading is lower, then a 9 kW three-phase bank.

- 5 min readRCD tripping with no fault: add up the leakageAn RCD on a home office and kitchen trips with no fault found. Add up the standing leakage, check it against a third of 30 mA, and split it over two RCDs.

- 5 min readWhat size generator for a dairy shedSize a standby set for a dairy shed from its load list. The vacuum pump's start sets the size, then staggered steps, a drive and a soft starter shrink it.

- 3 min readFixed heating maximum demand with Table C1Adding 7.5 kW of fixed heating to a house under Table C1 group D, the demand each group contributes, and the 80 A line that reg 59 draws.

- 2 min readA circuit chart for a house board with solarThe circuit chart and labels for a six-circuit house board with a solar inverter: ways, devices, RCDs, MAIN SWITCH, MAIN SWITCH SOLAR and a shared neutral.

- 3 min readHot water cylinder cable size for a 3 kW elementA 16 A hot water circuit run 20 metres through wall insulation at 35 degrees, sized to 2.5 mm² with 17.86 A of derated capacity and 2.27 percent voltage drop.

- 2 min readIP ratings for an outdoor point and a hosed shedWhich IP code an outdoor power point, a milking shed light and a hosed switchboard need, and why an IP67 light can fail where IP65 passes.

- 3 min readReading the wiring in an older houseA 1970s New Zealand house with yellow actives, a green earth and a black neutral. What each colour can be, what may stay, and how to sleeve new terminations.

- 1 min readHow far can 1.5 mm² run on a 10 A circuit?1.5 mm² copper on a 10 A curve C circuit can run 34.85 m before it reaches the 5 % voltage drop limit. The fault loop alone would allow 82 m.

- 1 min readHow many amps can 1.5 mm² cable carry?1.5 mm² copper multicore PVC cable carries 16 A enclosed in air at 30 °C in NZ, so it takes a 16 A breaker. Clipped direct, it carries 17 A.

- 1 min readHow many amps can 2.5 mm² cable carry?2.5 mm² copper multicore PVC cable carries 23 A enclosed in air at 30 °C in NZ, so a 20 A breaker protects it. Grouped with two circuits, it carries 16.1 A.

- 1 min readHow many amps can 2.5 mm² carry in Australia?2.5 mm² copper multicore PVC cable carries 20 A enclosed in air at 40 °C on AS/NZS 3008.1.1:2025, exactly a 20 A breaker. Clipped direct, it carries 22 A.

- 1 min readHow many lights on a 10 A circuit?In a home, AS/NZS 3000 Table C9 fills a 10 A circuit at 20 lighting points. A 21st point takes the sum over the circuit-breaker rating.

- 1 min readHow many power points on a 20 A circuit?In a home, AS/NZS 3000 Table C9 fills a 20 A circuit at 20 single 10 A socket-outlets. A non-domestic installation counts each one at twice that.

- 1 min readMinimum cable size for a lighting circuitAS/NZS 3000 Table 3.3 sets a minimum of 1 mm² copper for circuits other than socket-outlets, lighting included. The load and the run often need more.

- 1 min readMinimum cable size for power pointsAS/NZS 3000 Table 3.3 sets a minimum of 2.5 mm² copper for a socket-outlet circuit. An exception can allow less, under conditions you must meet first.

- 1 min readWhat size cable for a 22 kW EV charger?A 22 kW three-phase EV charger on a 32 A circuit takes 6 mm² copper over 20 m, with 38 A of derated capacity and a 1.04 % drop. At 60 m it takes 10 mm².

- 1 min readWhat size cable for a lighting circuit in NZ?A 10 A lighting circuit in New Zealand takes 1.5 mm² copper over 30 m, with 16 A of derated capacity and a 4.3 % drop. A 16 A circuit takes 2.5 mm².

- 1 min readWhat size cable for power points in Australia?A 20 A power point circuit in Australia takes 2.5 mm² copper on AS/NZS 3008.1.1:2025, rated 20 A enclosed in air at 40 °C. Grouping pushes it to 6 mm².

- 1 min readWhat size cable for power points in NZ?A 20 A power point circuit in New Zealand takes 2.5 mm² copper enclosed in air, with 23 A of derated capacity. Ceiling insulation moves it to 4 mm².

- 3 min readWhere can a home battery go? Garage wallsA garage wall that backs onto a bedroom, with a hot water cylinder nearby. See which AS/NZS 5139 location rules fail for a home battery, then fix each one.

- 5 min readKitchen power points and the cooktop zonePlace power points and switches near a cooktop, an outdoor gas bottle and a gas vent. Check each distance to AS/NZS 3000 and hand the sink to the wet area tool.

- 4 min readDownlights in an insulated ceilingRe-insulate a NZ ceiling with downlights in it. Check which may be covered, which only abutted, which must come out, and the clearances and roof space sign.

- 5 min read12 V caravan cable: d.c. voltage dropA 12 V caravan feed at 30 A over 6 m, checked on 4, 6 and 10 mm² twin against the 10 % ELV limit, then a 48 V battery-to-inverter run.

- 3 min readShed earthing on a 16 mm² submainEarth a NZ shed 30 m from the house on a 16 mm² submain. Compare an earth with the submain and a separate MEN with its own rod, and when each is allowed.

- 4 min readSolar battery size for a family home: 25 kWh a daySize a solar battery for a home that uses 25 kWh a day with an 8 kW array. Usable and nominal kWh, the bank, the inverter, winter solar and where it can go.

- 5 min readWhat size breaker for 4 mm² cable4 mm² copper enclosed in air takes a 25 A breaker, and 32 A fails at an Iz of 29 A. Grouping, a hot ceiling, insulation and a long run lower it.

- 4 min readRCD arrangement for a house boardCheck a New Zealand house board of eight circuits on two RCDs. See what fails with a fourth circuit on one RCD or both lights on one, and the AU change.

- 4 min readTotal voltage drop: mains, submain and finalAdd the voltage drop of the consumer mains, a shed submain and a final subcircuit against the 5 % limit, and fix a long submain before the shed circuits fail.

- 5 min readWire a bathroom: zones, IP ratings and the RCDA New Zealand bathroom with a 1.6 m bath and an open shower, worked through the AS/NZS 3000 Section 6 zones, the IP each item needs, the RCD and bonding.

- 3 min readOff-grid battery bank autonomy at 48 VA bach load list of 7600 Wh per day at 48 V needs 703.7 Ah of battery for two days of autonomy at 0.5 depth of discharge, worked step by step.

- 3 min readEV charger cable size for a 7 kW 32 A circuitA 7 kW EV charger on a 32 A dedicated circuit over 30 m needs 6 mm², with 38 A derated capacity, 2.85 percent voltage drop and 0.73 Ω loop impedance.

- 4 min readDomestic maximum demand with Table C1Assess the maximum demand of a New Zealand house from Table C1, group by group, with a worked example that lands on 52.61 A on a single-phase supply.

Calculators these guides use
- Spare capacity calculatorSee if a new load fits the main switch of a supply.
- Cable size calculatorFind the smallest cable size that passes each check.
- EV charger circuit calculatorCheck EV chargers for spare capacity, cable size and RCD.
- Battery bank calculatorCalculate battery bank capacity and autonomy for a load.
- Maximum demand calculatorEstimate maximum demand for domestic or non‑domestic loads.
- Voltage drop calculatorCalculate voltage drop on a cable run and check the limit.
- Ohm's law and powerAny two of V, I, R and P give the other two.
- RCD standing leakage budgetHow much standing leakage one RCD can carry.
- Generator sizing from a load listSize a generator from a load list with motor starting.
- Switchboard circuit chartMake a board circuit chart and the labels it needs.
- IP rating chart and decoderDecode an IP code and find the least for a location.
- Electrical wire colour guideFind wire colours for fixed wiring and cords, old and new.
- Maximum circuit length calculatorLongest run that voltage drop and the fault loop allow.
- Existing circuit checkCheck an installed circuit: cable, device, drop and Zs.
- Circuit loading calculatorCount the points a final subcircuit can carry.
- Minimum conductor size lookupLook up the smallest conductor allowed for a circuit.
- Battery location checkerCheck where a home battery can go under AS/NZS 5139.
- Power point location checkPower points near a cooktop, gas cylinder, vent or sink.
- Downlight clearance checkIC, CA90 or Non‑IC: may insulation touch the light?
- Outbuilding earthingEarth a shed: earth with the submain, or its own MEN.
- Solar battery calculatorSize a home battery for the solar evening load.
- RCD arrangement checkCheck circuits per RCD and the lighting split.
- Total voltage drop calculatorAdd the drop of mains, submain and final against 5 %.
- Wet area zones checkerFind the Section 6 zone, IP and RCD near water.