Earth fault loop impedance calculator

Check Zs against the AS/NZS 3000 Table 8.1 maximum for your device, in New Zealand and Australia.

Reads AS/NZS 3008.1.2:2017 (NZ), AS/NZS 3008.1.1:2017 and 2025 (AU) and AS/NZS 3000:2018. Tables checked 27 Sept 2026.

Inputs

A worked example with the default inputs.

External impedance Ze
0.35 Ω
Voltage
230 V
Device curve
Curve C
Device rating
20 A
Measured Zs
0 Ω
Standard
NZ · AS/NZS 3008.1.2
Run length
30 m
Active conductor size
2.5 mm²
Earth conductor size
From Table 5.1
Material
Copper
Insulation
PVC 75 °C

Earth fault loop impedance

0.89Ω

Maximum permitted Zs
1.53Ω
Prospective fault current
258.25A
Earth conductor
2.5mm²
R1 + R2
0.54Ω
Maximum length at Zs
65.67m

This result is a design aid. Verify it against the current standard.

Calculation steps

  1. Earth conductor size2.5mm²

    AS/NZS 3000:2018 Table 5.1

  2. R1 + R2 per km at the conductor operating temperature18.02Ω/km

    AS/NZS 3008.1.2:2017 Table 30 (Xc), Tables 34–35 (Rc) p.98, p.102–103

  3. R1 + R20.54Ω
  4. Earth fault loop impedanceResult0.89Ω
  5. Maximum permitted Zs1.53Ω

    AS/NZS 3000:2018 Table 8.1

  6. Prospective fault current258.25A

About this calculator

How this is calculated

The tool works out the earth fault loop impedance of one circuit. It compares that impedance with the maximum for the protective device.

  1. Earth conductor. If you leave the earth size on From Table 5.1, the tool picks it from the active conductor size.
  2. R1 + R2. It reads the resistance of the active and the earth conductors at their operating temperature. The Standard select decides which part it reads. It reads AS/NZS 3008.1.2 for New Zealand or AS/NZS 3008.1.1 for Australia. It adds the two and multiplies by the run length.
  3. Zs. It adds the external impedance: Zs = Ze + (R1 + R2).
  4. Maximum Zs. It reads the maximum for the device curve and rating from AS/NZS 3000 Table 8.1. The circuit passes when Zs is at or below that maximum.
  5. Fault current. It divides the voltage by Zs to get the prospective fault current.
  6. Maximum length. It works out the run length at which Zs reaches the maximum.

Ze is a site value. Measure it, or ask the network operator for it. The tool warns when Ze alone takes 90 % or more of the limit. After you install the circuit, test it and compare the measured Zs with the calculated one.

StepTable or clauseWhat it decides
Earth conductorAS/NZS 3000 Table 5.1The earth size when you do not name one
Conductor resistanceTables 34 and 35R1 and R2 at the operating temperature
Maximum ZsAS/NZS 3000 Table 8.1The limit for the device curve and rating
Disconnection timeAS/NZS 3000 Cl 5.7.2The times behind the Table 8.1 limits
Failed checkAS/NZS 3000 Cl 5.7.4The clause a circuit over the limit cites

Tables without a standard named are in the part of AS/NZS 3008.1 you pick. The Table 8.1 guide explains why the B, C and D curve limits differ.

Common circuits, worked with the tool

Each line states its route. Every line uses copper cable with PVC insulation, a Ze of 0.35 Ω at 230 V and the New Zealand tables. The earth size comes from Table 5.1.

New Zealand and Australia

The Standard select picks the part of AS/NZS 3008.1 for the conductor resistance. Table 8.1 and Table 5.1 are in AS/NZS 3000, which is the same in both countries.

Keep the result

Every input sits in the page address, so the link in your browser reproduces the calculation. The PDF button prints the result with its steps and table references. Saving a calculation to a project needs a free account.

Questions

The result is a design aid. Verify against the current standard.

What does the loop impedance calculator do?

The tool takes the active and earth resistance over the run length, and adds the external impedance Ze. The sum is Zs, the loop impedance for an earth fault. It compares Zs with the maximum for the protective device. It also reports the prospective fault current and the longest run that still passes.

Which tables set the maximum Zs?

The maximum Zs comes from AS/NZS 3000:2018 Table 8.1 for the device curve and rating. The earth conductor size comes from Table 5.1. Conductor resistance comes from AS/NZS 3008.1.2:2017 Tables 34 to 35. A failed check cites AS/NZS 3000:2018 Clause 5.7.4.

What affects earth fault loop impedance the most?

Ze, run length and active conductor size change Zs the most. The device curve and rating set the limit that Zs is compared with. The earth conductor size is taken from Table 5.1 unless you enter one. Cables in parallel divide the active resistance only, not the earth resistance.

Does the loop impedance calculator measure Ze?

No. Ze is a site value and the tool does not measure it. A warning appears when Ze alone uses 90 % or more of the maximum Zs. The prospective fault current is worked out at the phase to earth voltage, which defaults to 230 V. Inputs sit in the page address for sharing.

Worked examples

Background

Clauses and tables this tool reads

Every clause and table, with how each was verified

Tables last checked on 27 Sept 2026.

Was this useful?

A question, or a value that looks wrong? Contact us.