How many amps can 16 mm² cable carry?

Existing circuit check

+2 references

Worked to AS/NZS 3008.1.2:2017 (NZ) and AS/NZS 3000:2018. Tables checked 27 Sept 2026.

Corrected rating Iz

66A

Largest curve C device the cable allows
63A
Voltage drop
1.53%
Maximum Zs for the device
0.49Ω
Open the calculator with these inputs

This result is a design aid. Verify it against the current standard.

A drawn result card from the Circuit Check tool: circuit on 16 mm² passes.

16 mm² copper multicore PVC cable carries 66 A enclosed in air at 30 °C in New Zealand. That is its corrected rating Iz from AS/NZS 3008.1.2:2017 Table 13. The largest curve C breaker it allows is 63 A.

The case

The circuit is single‑phase at 230 V and runs 20 m at the full 63 A of the breaker. Table 5.1 gives a 6 mm² earth. The voltage drop is 1.53 % and the earth fault loop impedance is 0.45 Ω, just inside the 0.49 Ω that Table 8.1 allows.

The circuit check reads Passes.

What changes the rating

Clipped direct to a surface, the cable carries 78 A.

At 40 °C ambient it carries 58.08 A, below a 63 A breaker. Bunched with two other circuits, it carries 46.2 A.

See also: Cable size for a 3‑phase 100 A submain and Current-carrying capacity and derating.

Try it with these inputs

Ambient temperature
30 °C
Cores
Multicore
Device curve
Curve C
Grouped circuits
1
Insulation
PVC 75 °C
Run length
20 m
Design current
63 A
Material
Copper
Installation method
Enclosed in air
Power factor
1
Phases
Single phase
Device rating
63 A
Installed cable size
16 mm²
Voltage
230 V
External impedance Ze
0.35 Ω
Open the calculator with these inputs