Fire detector spacing calculator

Detector spacing and count for a room or corridor.

Reads NZS 4512:2010. Tables checked 26 Sept 2026.

Inputs

A worked example with the default inputs.

Detector type
Point-type smoke detector
Room length
20 m
Room width
12 m
Corridor
No
Beams or joists on the ceiling
No

Detectors, lines or beams

4

Spacing along
10m
Spacing across
10m
Greatest distance from a wall
5m
Setback from the wall used in the layout
5m
Limit on the distance from a detector, line or beam
7m
Worst distance this layout leaves
7.07m
Grid
2 by 2
Floor area
240m²

This result is a design aid. Verify it against the current standard.

Calculation steps

  1. Spacing along the room10m

    NZS 4512:2010 Cl 405.3

  2. Spacing across the room10m

    NZS 4512:2010 Cl 405.3

  3. Greatest distance from a wall5m

    NZS 4512:2010 Cl 405.3

  4. Setback from the wall used in the layout5m

    NZS 4512:2010 Cl 405.3

  5. Limit on the distance from a detector, line or beam7m

    NZS 4512:2010 Cl 405.3

  6. Worst distance this layout leaves7.07m

    NZS 4512:2010 Cl 405.3

  7. Floor area240m²
  8. Detectors, lines or beamsResult4

    NZS 4512:2010 Cl 405.3

  9. Distance from the apex of a sloping roof500mm

    NZS 4512:2010 Cl 405.3

About this calculator

How this is calculated

The tool lays out fire detectors in a rectangular room or a corridor. It reads NZS 4512:2010 Clause 405.3 for point heat, line heat, point smoke and beam smoke detectors.

  1. Spacing. The tool reads the spacing for the detector type along and across the room.
  2. Wall distance. It reads the greatest distance from a wall. It uses that as the setback in the layout.
  3. Grid. It divides each room side by the spacing and rounds up. That gives the grid.
  4. Count. It multiplies the two grid numbers. The result is the number of detectors, lines or beams.
  5. Worst distance. It finds the point furthest from any detector. It compares that distance with the limit in Cl 405.3.
  6. Sloping roof. The tool gives the distance from the apex of a sloping roof.

Cl 405.2.1 keeps a detector at least 200 mm from a wall or partition.

Worked example

Limits

The tool does not check ceiling height or obstructions. It does not place detectors in voids. NZS 4512:2021 supersedes the 2010 edition. Check the current edition before you rely on a layout.

See also: Sounder level calculator, Fire alarm cabling and Fire alarm battery.

Questions

The result is a design aid. Verify against the current standard.

What does the detector spacing tool do?

The tool reports the spacing between detectors, the greatest distance from a wall where the clause states one, and the grid and count for a room or corridor. For point heat detectors it also applies the coverage rule of one detector for each 30 square metres of floor area.

What is the spacing for smoke and heat detectors?

NZS 4512:2010 Clause 405.3 gives 6 m between point heat detectors and 3 m from a wall, or 9 m and 4.5 m in a corridor. Point smoke detectors are 10 m apart and 5 m from a wall. Smoke beams are 14 m apart. Line heat detectors are 8 m apart.

Why does the tool say the spacing misses the 7 m rule?

Clause 405.3.3 gives 10 m between point smoke detectors and 5 m from a wall, and it also holds every point within 7 m of a detector. A full 10 m grid leaves a corner 7.072 m away, so AmpSize measures the layout and tells you to close the spacing.

How do beams and joists change the layout?

Clause 405.2.1(m) reduces the spacing across the beams to two thirds where the beams are 100 mm or deeper. Where the depth is over 460 mm and the spacing is over 2400 mm, each beam acts as a wall. The normal spacing then applies inside every bay.

How large can a zone be?

AmpSize compares the floor area with the 750 square metre zone limit of NZS 4512:2010 Clause 401.2.3 and warns you where the area is above it. Four cases in that clause raise the limit to 900 or 2000 square metres. Read the clause and check them.

Background

Clauses and tables this tool reads

Every clause and table, with how each was verified

Tables last checked on 26 Sept 2026.