AS/NZS 3008.1.2:2017
Table 28(1), 28(2)
Rating factors for depth of laying
The cable size and correction factors tools read the factor for how deep the cable is buried. It applies only to buried cables.
Verified: read against the printed standard, pages 89. Checked 24 Sept 2026.
Units: Depth m
These are the values AmpSize encodes. No text of the standard is reproduced. Verify against the current standard.
10 rows
| Depth (m) | Buried direct up to 50 | Buried direct 50 to 300 | Buried direct over 300 | Underground enclosure single core | Underground enclosure multicore | Factor |
|---|---|---|---|---|---|---|
| 0.5 | 1 | 1 | 1 | 1 | 1 | 1 |
| 0.6 | 0.99 | 0.98 | 0.97 | 0.98 | 0.99 | 0.99 |
| 0.8 | 0.97 | 0.96 | 0.94 | 0.95 | 0.97 | 0.97 |
| 1 | 0.95 | 0.94 | 0.92 | 0.93 | 0.96 | 0.95 |
| 1.25 | 0.94 | 0.92 | 0.9 | 0.9 | 0.95 | 0.94 |
| 1.5 | 0.93 | 0.91 | 0.89 | 0.89 | 0.94 | 0.93 |
| 1.75 | 0.92 | 0.89 | 0.87 | 0.88 | 0.94 | 0.92 |
| 2 | 0.91 | 0.88 | 0.86 | 0.87 | 0.93 | 0.91 |
| 2.5 | 0.9 | 0.87 | 0.85 | 0.86 | 0.93 | 0.9 |
| 3 | 0.89 | 0.86 | 0.83 | 0.85 | 0.92 | 0.89 |