Worked to AS/NZS 3008.1.2:2017 (NZ) and AS/NZS 3000:2018. Tables checked 27 Sept 2026.

Conductor size

2.5mm²

Derated capacity
23A
Voltage drop
3.92%
Earth conductor
2.5mm²
Open the calculator with these inputs

This result is a design aid. Verify it against the current standard.

A drawn result card from the Cable Size tool: conductor size 2.5 mm².

A power point circuit on a 20 A breaker in New Zealand takes 2.5 mm² copper cable on a typical route. The route is 25 m of multicore PVC cable, enclosed in air at 30 °C, with no other circuit beside it. The tool gives 23 A of derated capacity and a voltage drop of 3.92 %.

The case

The circuit is single‑phase at 230 V. The design current is the full 20 A of the curve C breaker, at a power factor of 1. The voltage drop limit is 5 % and Ze is 0.35 Ω. Table 5.1 gives a 2.5 mm² earth, and the earth fault loop impedance is 0.8 Ω.

What changes the answer

Ceiling insulation changes it most. With the cable partly surrounded by insulation, the tool selects 4 mm² with 26 A of capacity.

Length is next. On a run of 40 m, voltage drop sets the size, and the tool selects 4 mm² with a drop of 3.9 %.

Before you install

Enter the real route: the installation method, the longest run and the circuits that share it. The tool prints each check with its clause or table.

See also: What size breaker for 4 mm² cable and Current-carrying capacity and derating.

Try it with these inputs

Ambient temperature
30 °C
Cores
Multicore
Device curve
Curve C
Check protective device
Yes
Grouped circuits
1
Insulation
PVC 75 °C
Run length
25 m
Design current
20 A
Material
Copper
Installation method
Enclosed in air
Power factor
1
Phases
Single phase
Device rating
20 A
Voltage drop limit
5 %
Voltage
230 V
External impedance Ze
0.35 Ω
Open the calculator with these inputs

Where next

The ideas behind it

More worked examples

AmpSize is a design aid. Verify results against the current standard.

Was this useful?

A question, or a value that looks wrong? Contact us.