Skip to content
AmpSize

Neutral current of an unbalanced load

The neutral current of an unbalanced three-phase load.

AS/NZS 3000

Reads AS/NZS 3000:2018. Tables checked 2 Oct 2026.

Try a job 4

Each job fills in example values. Replace them with your values.

Inputs

Worked example with the default inputs. The live calculator replaces it when the page loads.

Line voltage
400 V
Phase A current
32 A
Phase B current
20 A
Phase C current
10 A
Phase A power factor
1
Phase B power factor
1
Phase C power factor
1

Neutral current

19.08A

Neutral as a share of the largest phase
59.6%
Largest phase current
32A
Real power, three phases
14.32kW

This result is a design aid. Verify it against the current standard.

Calculation steps

  1. Phase A current, at 0° from phase A volts32A
  2. Phase B current, at -120° from phase A volts20A
  3. Phase C current, at 120° from phase A volts10A
  4. Formula: one power factor, so

    I_N = √(Ia² + Ib² + Ic² − Ia·Ib − Ib·Ic − Ic·Ia)

    19.08 A
  5. Neutral currentResult19.08A

    AS/NZS 3000:2018 Cl 3.5.2(b)(ii)

  6. Neutral current angle from phase A-27
  7. Neutral as a share of the largest phase59.6%
  8. Real power, three phases14.32kW

About this calculator

How this is calculated

In a star load each phase current returns through the neutral. The three phase voltages are 120° apart, so the three currents are too. When the currents are equal and at one power factor, they cancel and the neutral carries nothing. When they are not equal, the neutral carries what is left over.

The tool works that left-over current as a phasor sum. It sets phase A at 0°, phase B at −120° and phase C at +120°. It then turns each current back by its own power factor angle, because a lagging load draws its current after its voltage. The three currents are added as vectors, and the size of the sum is the neutral current. The tool also gives the angle of the sum from the phase A voltage.

When all three power factors are the same, the angles cancel out of the sum. The tool then shows the short formula: the square root of the sum of the three squares, less the three products of pairs.

The neutral can carry more than the largest phase. That happens when the power factors differ a lot, so two currents line up. The tool warns when it does.

The answer is the current at the supply frequency only. Third harmonic currents from electronic loads add in the neutral, not cancel. The harmonics tool works those.

StepTable or clauseWhat it decides
Phasor of each phaseThe phase angle less the power factor angleWhere each current points
Neutral currentThe phasor sum of the threeThe current the neutral carries
One power factorI_N = √(Ia² + Ib² + Ic² − Ia·Ib − Ib·Ic − Ic·Ia)The short form of the sum
Neutral sizeCl 3.5.2(b)(ii)A neutral at least the size of the largest active
A smaller neutralCl 3.5.2 Exception 3Allowed for a mostly multiphase load that still carries the out-of-balance current
HarmonicsCl 3.5.2(b)(i)Third harmonic currents add to the out-of-balance current

Worked examples

Limits

The tool takes three phase currents and their power factors, all lagging. It does not take a leading load, such as a capacitor bank, or a load connected between two phases.

It gives the current, not the conductor size. Take the larger of the neutral current and the largest phase current to the cable size tool.

See also: Three phase power, Max demand by phase and Cable size.

Questions

Each answer describes what this tool calculates. The result is a design aid. Verify against the current standard.

How do you work out the neutral current of a three-phase load?

Add the three phase currents as phasors, 120° apart, each turned by its power factor angle. The size of the sum is the neutral current. With one power factor on all phases it is √(Ia² + Ib² + Ic² − Ia·Ib − Ib·Ic − Ic·Ia).

Why is the neutral current not the difference between the phases?

The phase currents are 120° apart, so they do not add or subtract in a straight line. 32 A, 20 A and 10 A give 19.08 A in the neutral, not 22 A or 12 A.

Can the neutral carry more than a phase?

Yes. With very different power factors the phasors can line up, and the neutral can carry more than the largest phase. Third harmonic currents from electronic loads also add in the neutral. The tool warns when the sum passes the largest phase.

How big must the neutral of a three-phase circuit be?

AS/NZS 3000 Cl 3.5.2(b)(ii) asks for a neutral at least as large as the largest active. Exception 3 allows a smaller one where most of the load is multiphase and the neutral still carries the out-of-balance current with its harmonics.

Does a balanced load need a neutral?

Three equal currents at one power factor cancel, so the neutral carries no current at the fundamental. A star load with single-phase items still needs it, as the balance changes when a load switches off.

Clauses and tables this tool reads

Every clause and table, with how each was verified

Tables last checked on 2 Oct 2026.

Was this useful?

A question, or a value that looks wrong? Contact us.