Tasks
Pick the job. The calculator opens with example values. Replace them with your values. To pick a calculator by name, use all tools.
Trade
502 tasks
Cables
149Cable size24
- Size a cable for a shedThe smallest cable that carries the load over the run to a shed.
- Size a cable for an EV chargerThe cable size for a 32 A charger on a 25 m run.
- Size a submain for a tenancyThe smallest three phase submain that passes each check, on AU 3008.1.1:2025.
- Price a cable runA size and a length you can take to a price.
- Size the cable for an ovenThe cable for a 32 A cooking circuit on a 15 m run.
- Size a hot water cylinder circuitThe cable for a 3 kW cylinder on a 20 m run.
- Size a heat pump circuitThe cable for a 20 A heat pump on an 18 m run.
- Size the mains for a houseThe consumer mains for 63 A over 25 m underground.
- Size a three‑phase EV charger circuitThe cable for a 22 kW charger on a 30 m run.
- Size an aluminium submainThe smallest aluminium submain for 250 A over 80 m.
- Size a cable in ceiling insulationThe cable for 16 A where insulation surrounds it.
- Size a cable on a hot roofThe cable for 25 A at 50 °C ambient.
- Size a buried cable in dry soilThe cable for 100 A at 2.5 K·m/W and 0.8 m deep.
- Size six circuits on one trayThe cable for 40 A grouped with five other circuits.
- Size parallel cables for 800 ATwo cables per phase for an 800 A feeder.
- Size a cable for a harmonic loadThe cable for 63 A with 35 % third harmonic.
- Size a 22 kW motor cableThe cable for a 41 A motor over 60 m on a 50 A D‑curve breaker.
- Size a submain to a sleep-outThe submain for 40 A over 35 m.
- Size a cable with a fault checkThe cable for 32 A that also withstands 6 kA for 0.1 s.
- Size a pool pump circuitThe cable for a 1.5 kW pump on a 30 m run.
- Size a welder outlet circuitThe cable for a 32 A three‑phase outlet in a workshop.
- Size a workshop submainThe three‑phase submain for 63 A over 45 m.
- Size a supply to a tiny homeThe cable for a 16 A supply over 30 m.
- Size a submain to the 2025 editionA 100 A run of 50 m, read on AS/NZS 3008.1.1:2025 for Australia.
Voltage drop13
- Check a long run for voltage dropThe voltage drop on the run, against the limit.
- Check a 12 V d.c. run for dropThe voltage drop on a 30 A caravan feed over 6 m, against the 10 % ELV limit.
- Check the drop on a PV array cableThe d.c. drop of a 15 A string at 600 V over 40 m on 4 mm².
- Check the drop on a submainThe voltage drop on a 100 A three‑phase submain over 80 m.
- Check the drop on a lighting circuitThe drop on an 8 A lighting circuit over 45 m.
- Check the drop to a rural pumpThe drop on 10 A over a 250 m run.
- Check the drop on aluminium mainsThe drop on 200 A over 60 m of aluminium mains.
- Check a 24 V control circuitThe drop on 2 A at 24 V over 60 m.
- Check a 48 V battery cableThe drop on 100 A over 3 m at 48 V.
- Check the drop with a loaded neutralThe drop on an unbalanced circuit with 20 A in the neutral.
- Check an extension leadThe drop on 10 A through a 30 m lead.
- Estimate a 160 A submain for a tenderThe drop on 160 A over 90 m, three phase.
- Check the drop at a 3 % limitThe drop on 32 A over 40 m against a 3 % limit you set.
Loop impedance7
- Check disconnection timeThe loop impedance of a 32 A circuit on a 45 m run, against the maximum Zs.
- Check Zs on a socket circuitThe loop impedance of a 20 A circuit on 2.5 mm² over 30 m.
- Check Zs on a lighting circuitThe loop impedance of a 10 A circuit on 1.5 mm² over 40 m.
- Check Zs on a motor circuitThe loop impedance of a 25 A D‑curve circuit over 35 m.
- Check Zs on a shed submainThe loop impedance of a 63 A submain on 16 mm² over 60 m.
- Check Zs on a weak rural supplyThe loop impedance of a 20 A circuit with 0.8 Ω at the supply.
- Check Zs in AustraliaThe loop impedance of a 20 A circuit against the Australian tables.
Fault rating6
- Check a conductor against fault currentWhether a 35 mm² XLPE conductor withstands 10 kA for 0.2 s.
- Check consumer mains against 6 kAWhether 16 mm² mains withstand 6 kA for 0.1 s.
- Check a final circuit against 3 kAWhether 2.5 mm² withstands 3 kA for 0.1 s.
- Check an aluminium feederWhether 95 mm² aluminium withstands 20 kA for 0.3 s.
- Check a one-second withstandWhether 120 mm² withstands 25 kA for 1 s.
- Check a cable with a soldered jointThe lower limit a soldered joint sets on a 25 mm² cable.
Conduit fill7
- Fill a conduitThe space factor of a 4 mm² single core circuit in a 25 mm conduit.
- Fit a submain in a conduitWhether four 16 mm² singles fit in a 32 mm conduit.
- Fit two flat cables in a conduitWhether two 2.5 mm² twin and earth cables fit in 20 mm.
- Fit PV string cablesWhether six 6 mm² singles fit in a 32 mm conduit.
- Fit a 35 mm² submainWhether four 35 mm² singles fit in a 50 mm conduit.
- Fit a motor circuitWhether four 6 mm² singles fit in a 25 mm conduit.
- Fit cables in an Australian conduitWhether four 4 mm² singles fit in a 25 mm conduit on the Australian sizes.
Voltage rise6
- Check solar voltage riseThe voltage rise on a 45 m cable from a 5 kW inverter.
- Check rise on a three‑phase inverterThe rise on a 10 kW three‑phase inverter cable of 30 m.
- Check rise on a long rural runThe rise on 5 kW over 80 m.
- Check rise against a 2 % limitThe rise on a 3 kW inverter in Australia against 2 %.
- Check rise on a battery inverterThe rise on a 5 kW battery inverter over 15 m.
- Check rise on a 30 kW arrayThe rise on a 30 kW commercial inverter over 40 m.
Underground cable7
- Bury a cable out to a shedThe depth of cover for a sheathed cable in heavy duty conduit.
- Bury a cable under a drivewayThe depth of cover under 75 mm of concrete.
- Bury a cable directThe category and depth for an armoured cable buried direct.
- Cross a water pipeThe separation from a water pipe of DN65 or less.
- Run a cable beside a gas pipeThe separation from a gas service.
- Bury a cable near an earth electrodeThe separation a conductive enclosure needs from the electrode.
- Run a conduit under a slabThe cover a conduit needs within a building.
Segregation and separation6
- Separate power from signalThe separation the two circuits need on the route.
- Run data beside power in a wallThe separation between a power cable and a data cable.
- Put extra-low voltage in a switchboardWhat may share the enclosure at a switchboard.
- Share a conduit between two tenanciesWhether circuits of two occupancies may share a wiring system.
- Run a cable near a gas pipeThe separation from a gas pipe above ground.
- Separate fire alarm cable from powerThe separation a fire alarm circuit needs from low voltage.
Maximum circuit length6
- Find the longest run for a lighting circuitThe longest route a 1.5 mm² lighting circuit on a 10 A breaker can take.
- Find the longest socket circuitThe longest run for a 20 A circuit on 2.5 mm².
- Find the longest oven circuitThe longest run for a 32 A circuit on 6 mm², by voltage drop.
- Find the longest motor circuitThe longest three‑phase run on a 16 A D‑curve breaker.
- Find the longest run at 3 %The longest run when the drop limit is 3 %.
- Find the longest heat pump runThe longest run for a 16 A C‑curve circuit on 2.5 mm².
Simplified selector6
- Match a breaker to a 2.5 mm² cableThe largest breaker for a 2.5 mm² cable partly in ceiling insulation over 30 m.
- Match a breaker to lighting cableThe largest breaker for 1.5 mm² over 35 m.
- Match a breaker to 4 mm²The largest breaker for 4 mm² over 25 m.
- Match a breaker to oven cableThe largest breaker for 6 mm² over 15 m.
- Check a three‑phase 10 mm² circuitThe largest breaker for 10 mm², three phase, over 40 m.
- Match a breaker in full insulationThe largest breaker for 2.5 mm² fully in insulation.
Minimum conductor size5
- Find the smallest control conductor allowedThe minimum copper size for a signal and relay control circuit.
- Find the smallest aerial conductorThe minimum aluminium size for an aerial run.
- Find the smallest flexible cordThe minimum size for a flexible cord.
- Find the smallest bare conductorThe minimum size for a bare conductor.
- Find the smallest parallel conductorThe minimum size a conductor in parallel may be.
Comms cable selector8
- Add an instrument loopA cable for the signal over a 150 m route.
- Select a comms cableA PROFINET cable for a 60 m run through a drag chain.
- Check an RS-485 runWhether 400 m at 115.2 kbps is in the limit.
- Check a long Modbus trunkWhether 1200 m at 9.6 kbps is in the limit.
- Check an Ethernet run past 90 mWhether a 110 m Ethernet run is in the limit.
- Pick a 24 V field supply cableA cable for a 24 V d.c. supply over 80 m.
- Pick a screened cable beside a driveA screened signal cable for a noisy area.
- Pick an outdoor Ethernet cableAn Ethernet cable for an outdoor run.
Site cord length5
- Check the length of a site leadWhether a 50 m, 15 A lead of 2.5 mm² is in the limit on site.
- Check a light-duty site leadWhether a 25 m, 10 A lead of 1.0 mm² is in the limit.
- Check two leads joinedWhether two joined leads stay in the limit.
- Check a coiled leadWhat a coiled lead does to the limit.
- Check a lead from a socket assemblyA lead that runs from a portable socket‑outlet assembly.
Loop power budget6
- Check a 4–20 mA loop's power budgetThe supply, the series resistance and the cable give the voltage left at the transmitter.
- Check a loop with a HART resistorThe voltage left with a 250 Ω HART resistor in the loop.
- Check a loop through a barrierThe voltage left with 300 Ω of barrier in series.
- Check a 2 km loopThe voltage left on 1 mm² cable over 2000 m.
- Check a loop on a 12 V supplyWhether a 12 V supply drives the loop.
- Check a loop at fault currentThe voltage left at 22 mA.
DC cable size8
- Size a battery cableThe d.c. cable size for a 3 m, 48 V battery run at 100 A.
- Size a PV string cableThe d.c. cable for 14 A at 600 V over 30 m.
- Size a 12 V run in a camperThe cable for 8 A at 12 V over 6 m at 3 %.
- Size a 24 V control supplyThe cable for 10 A at 24 V over 40 m.
- Size an array cable on a hot roofThe cable for 28 A at 1000 V and 60 °C.
- Size a battery inverter cableThe cable for 250 A at 48 V over 2 m.
- Size a buried array cableThe cable to a ground-mount array, buried 0.6 m.
- Size a 48 V telecom feedThe cable for 60 A at 48 V over 15 m.
Correction factors7
- Find the correction factors in a hot ceilingThe factor for four circuits in a 50 °C ceiling space, and the rating the cable needs.
- Find the correction factors for a buried cableThe soil, depth and grouping factors for two buried three‑phase circuits.
- Find the factor for nine circuitsThe grouping factor for nine circuits on a tray.
- Find the factor on a 50 °C roofThe ambient factor at 50 °C.
- Find the factors in poor soilThe soil and depth factors at 2.5 K·m/W and 1 m.
- Find the factor for a harmonic loadThe factor for 40 % third harmonic in a four‑core cable.
- Compare the factors in AustraliaThe factors for 45 °C and four grouped circuits on the Australian tables.
Total voltage drop4
- Check the total voltage drop to a shedThe mains, the shed submain and a final subcircuit added against 5 %.
- Find the drop left for a new circuitWhat 25 m of mains and a 40 m submain leave for a final subcircuit.
- Add a three phase submain to a finalThree phase mains and submain with a single phase final, added by percent.
- Use the 7 % substation limitA factory fed from its own transformer, checked against 7 %.
Conductor colours4
- Find the wire colours for an AU houseActive, neutral and earth colours for Australian domestic wiring.
- Find out what a black wire isEvery function a black conductor can carry, and where.
- Read the colours of an older houseBare or green earths and yellow actives, and how to sleeve them.
- Check the cores of a three‑phase cordPhase, neutral and earth cores of a five-core cord.
Cable tray fill4
- Fill a plant room trayTen multicore cables on a perforated tray, with the factor for cable size.
- Lay trefoil submains on a ladderTwo single‑core circuits in trefoil, their width and kg/m.
- Find the tiers for ten feedersHow many tiers ten multicore feeders need on a narrow tray.
- Space flat mains on a ladderThree flat circuits spaced on an Australian ladder, with the grouping factor.
Cable loss cost4
- What a size up saves on a feederThe yearly saving of 120 over 95 mm² on a 200 A feeder that never stops.
- Running cost of a heat pump circuitThe energy a 6 mm² heat pump circuit loses a year, against 10 mm².
- Payback of a larger submainHow fast 35 mm² pays back over 25 mm² on a busy 80 m submain.
- CO2 saved by a larger aluminium cableThe kWh and CO2 a year of 120 over 95 mm² aluminium at 150 A.
Protection
51IDMT protection6
- Grade two relaysThe operating times of a feeder and an incomer relay at 4 kA.
- Grade a very inverse pairThe operating times of two very inverse relays at 6 kA.
- Grade three relays in seriesThe margins between three relays at 5 kA.
- Find a relay's time at ten times pick-upThe operating time of one relay at 2 kA.
- Check an instantaneous settingWhether a 4 kA instantaneous element clears an 8 kA fault.
- Grade an extremely inverse feederAn extremely inverse relay under a standard inverse incomer.
RCD selection8
- Choose the RCD for an EV chargerThe RCD a 32 A home EV charger circuit needs in NZ.
- Check the RCD for house lightingThe RCD a lighting circuit needs in Australia.
- Check the RCD for a classroomThe RCD rule for socket‑outlets in a school.
- Check the RCD for a child-care centreThe 10 mA rule where young children are.
- Check a measured RCD trip timeWhether 28 ms at rated current and 12 ms at five times pass.
- Choose the RCD for a patient areaThe residual current and times for a patient-protection RCD.
- Choose the RCD for a fixed machineWhether a fixed appliance in a workshop needs an RCD.
- Choose the RCD for a vending machineThe RCD rule for a ride or a vending machine.
Switchboard form5
- Check the access to a main switchboardThe access clearances and separation rules for an 800 A main switchboard.
- Check access to a house switchboardThe clear space a domestic switchboard needs.
- Check a long board for two exitsWhether a 3.6 m board needs two exits.
- Check a board in a cupboardThe access for a 400 A board that is not in a room.
- Check the impulse clearancesThe clearance for a 6 kV impulse withstand.
Circuit check7
- Check the breaker on a 4 mm² circuitWhether a 32 A breaker suits 4 mm² cable, and the largest breaker the cable allows.
- Check an existing three‑phase submainWhether 16 mm² on a 63 A breaker over 80 m passes the cable, drop and Zs checks.
- Check a 20 A breaker on 2.5 mm²Whether a 20 A breaker suits a 2.5 mm² circuit.
- Check a 32 A breaker on 6 mm²Whether a 32 A breaker suits a 6 mm² circuit.
- Check a 16 A breaker on 1.5 mm²Whether a 16 A breaker suits a 1.5 mm² circuit.
- Check a 63 A breaker on 16 mm²Whether a 63 A breaker suits 16 mm² mains.
- Check a 10 A breaker on 1 mm²Whether a 10 A breaker suits a 1 mm² lighting circuit.
Fault level at a board8
- Find the fault level at a sub‑boardThe fault current at a board 45 m from a 300 kVA transformer, against 6 kA breakers.
- Check breakers beside a 1000 kVA transformerWhether 25 kA breakers suit a main board 20 m from a 1000 kVA transformer.
- Find the fault level at a house boardThe fault current at the end of 20 m of 16 mm² mains.
- Find the fault level at a shedThe fault current 60 m down a 16 mm² submain.
- Find the fault level at an MCCThe fault current 30 m from a 500 kVA transformer.
- Check 6 kA breakers at a tenancy boardWhether 6 kA devices suit the fault level at the board.
- Find the fault level on parallel feedersThe fault current with two cables per phase.
- Find fault level from a 10 kA serviceThe fault current at a board in Australia.
RCD arrangement4
- Find an RCD with too many circuitsA house board with four circuits on one RCD.
- Split a large board onto three RCDsNine circuits and three lighting circuits spread over three RCDs.
- Check an Australian board of RCBOsEvery final subcircuit on its own RCBO in an AU home.
- Check the lighting split in an officeOffice lighting circuits spread over two RCDs.
Circuit chart4
- Make a circuit chart for a house boardSix circuits charted by way, with the main switch label.
- Label a board with solarA shop board with the main switchboard and solar main switch labels.
- Chart a sub‑board in a workshopWays for single and three‑phase circuits on a distribution board.
- Mark a shared neutralTwo lighting circuits on one neutral, named with their ways.
RCD leakage budget4
- Check the leakage on a home office RCDWhether a heat pump, four computers and a fridge stay within budget.
- Find why a workshop RCD tripsFour Class I tools at their test limit against a 30 mA RCD.
- Split an office over RCDs by leakageHow many RCDs six computers and six monitors need.
- Check a 10 mA RCD for childcareWhether a heat pump and chargers fit one 10 mA RCD.
MCB trip curve4
- Check a breaker clears a long circuitA long lighting run with little fault current against its breaker and cable.
- See a D curve on a motor circuitHow long a D curve breaker can take at a modest fault, against the cable.
- Check a small cable near the boardWhether a high fault current outruns a small cable before the breaker trips.
- Compare a B and C curve breakerThe instant trip current of a Type B breaker on a socket‑outlet circuit.
Loads
90Maximum demand8
- Size a house mainThe maximum demand of a house with a heat pump, from Table C1.
- Work out commercial maximum demandThe maximum demand of a tenancy from Table C2.
- Work out demand for a block of unitsThe demand of twelve units, four on each phase.
- Work out demand with spa and floor heatingThe demand of a house with heating and a spa pool.
- Work out demand for a caféThe demand of a café with cooking and refrigeration.
- Work out demand for a small factoryThe demand of a workshop with lighting, sockets and motors.
- Work out demand for a three‑phase houseThe demand per phase of a large house.
- Work out demand for an office floorThe demand of a 400 m² office with air-conditioning.
Full load current6
- Find a 22 kW motor's full load currentThe line current a 22 kW three phase motor takes at 400 V.
- Find the current of a 7.2 kW chargerThe current of a single‑phase 7.2 kW load.
- Find the current of 100 kVAThe line current of a 100 kVA load at 400 V.
- Find the current of a 3 kW heaterThe current of a 3 kW heater at 230 V.
- Find the current of a chillerThe current of a 45 kW chiller at 0.85 power factor.
- Find the current of a commercial ovenThe current of a 15 kW three‑phase oven.
Motor6
- Size a motor circuitThe full load current of an 11 kW motor at 400 V.
- Find starting current of a 55 kW motorThe direct-on-line starting current at 400 V.
- Find the speed of a six-pole motorThe shaft speed of a six-pole motor at 3 % slip.
- Find the torque of a 7.5 kW motorThe full load torque of a four‑pole 7.5 kW motor.
- Check a single‑phase pump motorThe current of a 2.2 kW single‑phase motor.
- Find the speed of a two‑pole motorThe speed of a 4 kW two‑pole motor at 50 Hz.
Battery6
- Size a battery bankThe bank capacity the loads need for the autonomy days.
- Size a 12 V battery for a camperThe Ah for a fridge and lights for one day.
- Size a 24 V PLC panel backupThe Ah to hold a 120 W panel for four hours.
- Size a bank for three winter daysThe Ah for three days of autonomy.
- Size a lithium bankThe Ah at 90 % depth of discharge.
- Size a bank for a cold siteThe Ah with a cold-temperature factor.
Circuit loading6
- Load a control panelThe load on each circuit in the panel.
- Count sockets on a house circuitThe loading of twelve 10 A socket‑outlets on a 20 A circuit.
- Count lights on a circuitThe loading of thirty lighting points on a 10 A circuit.
- Load a kitchen circuit with a hobThe demand of a 7.2 kW hob on its circuit.
- Load an office socket circuitThe loading of eight 10 A socket‑outlets on a 20 A office circuit.
- Apply diversity upstreamThe loading of a submain that feeds six circuits.
Max demand by phase4
- Balance a house demand across three phasesThe maximum demand on each phase of a three phase house, from Table C1.
- Balance an office fit-outThe demand on each phase of an office, from Table C2.
- Balance a block of unitsThe demand on each phase of nine units.
- Balance a workshop with a welderThe imbalance a single‑phase 32 A welder outlet makes.
Lighting lumen method11
- Light a kitchen by the lumen methodHow many downlights a kitchen needs for its target lux, in a grid.
- Light a garage with battensHow many LED battens a garage needs, laid out in rows.
- Light an office to 320 lxHow many panels an office needs to AS/NZS 1680.1 Table 3.1, with the spacing check.
- Light a warehouse with high baysHow many 20 000 lm high bays a 30 by 20 m bay needs.
- Light a corridorHow many downlights a 12 by 1.5 m corridor needs.
- Light a bathroomHow many downlights a 3 by 2.4 m bathroom needs.
- Light a living roomHow many downlights a 6 by 4.5 m living room needs.
- Light a bedroomHow many downlights a 3.6 by 3.2 m bedroom needs.
- Light a switchroomHow many battens a 5 by 3 m switchroom needs.
- Light a classroom to 320 lxHow many panels a 9 by 7 m classroom needs at a target you set.
- Light a dusty workshopThe count with a maintenance factor from Table 14.4.
EV charger circuit9
- Charge an EV from a home socket‑outletThe circuit a mode 2 charging lead needs on a home socket‑outlet.
- Check spare capacity for an EV chargerWhether a 7 kW charger fits a 63 A board that already carries 40 A.
- Add EV chargers to an Australian car parkWhether four 22 kW chargers fit a 400 A board, with and without load management.
- Add a 22 kW charger to a houseThe cable, RCD and headroom for a three‑phase charger.
- Add a charger with load managementThe headroom when the charger is limited to 16 A.
- Add a second charger to a houseThe headroom with two 32 A chargers.
- Choose a charger RCD without d.c. detectionThe RCD type when the station has no 6 mA d.c. detection.
- Size a long charger runThe cable for a 32 A charger 40 m from the board.
- Add six chargers to an apartment car parkThe demand and supply for six chargers in New Zealand.
Power factor correction10
- Correct a factory power factorThe kvar and bank steps to lift a 250 kW load from 0.78 to 0.95.
- Free supply capacity with power factor correctionThe kVA a 400 kVA site gets back when its power factor rises to 0.98.
- Correct a motor boardThe kvar to lift a 75 kW motor load from 0.82 to 0.95.
- Choose the capacitor stepsThe bank in 25 kvar steps for a 300 kVA load.
- Check a bank for resonanceThe bank against the fault level and 20 % harmonic load.
- Correct a single‑phase loadThe kvar for a 15 kW single‑phase load at 0.7.
- Size a capacitor at a motorThe largest capacitor a pump motor can take, and its new line current.
- Correct a small motor at the motorWhy a small motor capacitor stops short of the target power factor.
- Cut the line current of a large motorThe current a capacitor at a large motor takes off its cable and starter.
- Check a motor capacitor for self-excitationThe no-load limit on a capacitor at a small conveyor motor.
Max demand by floor area4
- Estimate demand for a shop by floor areaThe demand of a 600 m² shop with airconditioning, from Table C3.
- Estimate demand for a warehouseA 3000 m² warehouse with ventilation and 40 kVA of special equipment.
- Estimate demand for a basement carparkA 4000 m² basement carpark with EV charging on a quarter of it.
- Estimate demand for an office floorAn 800 m² office with reverse cycle air, at the top of the range.
Spare capacity4
- Check a heat pump fits the supplyA heat pump drawing 2.5 kW against a 63 A main that logged 41 A.
- Check a spa fits a three‑phase boardA 25 A spa on the lightest phase of an 80 A supply.
- Find submain demand by limitationA submain demand from the breakers it feeds, against its 100 A main.
- Check a 22 kW charger fits a factoryA 22 kW three‑phase load on a 200 A supply limited to 160 A.
Motor circuit4
- Kit out a pump motor circuitCable, breaker, contactor and overload for a 7.5 kW pump 40 m away.
- Kit a star-delta starter for a fanThe three contactors and the relay for a 37 kW fan.
- Size a soft starter circuitA 22 kW conveyor motor on a soft starter limited to 3 × FLC.
- Kit a single‑phase motor circuitA 2.2 kW compressor at 230 V, 25 m from the board.
Motor starting methods4
- Compare starters for a centrifugal pumpStart current and torque of six methods for a 15 kW pump.
- Check star-delta on a loaded conveyorWhich starts a 22 kW conveyor that needs high breakaway torque.
- Estimate the dip of a fan startThe voltage dip of each method for a 37 kW fan.
- Start a bore pump on a weak supplyThe dip of a 5.5 kW pump at the end of a rural line.
VSD motor lead4
- Check a drive motor leadWhether a pump on a drive needs an output filter for its motor lead.
- Check a long fan lead on a VSDA fan motor far from its drive, against the drive maker limit.
- Size a conveyor drive lead with a filterA long conveyor lead on a sine filter and the current for its cable.
- Check an inverter-rated motor on a driveWhether an inverter-rated motor takes the reflected peak without a filter.
Load schedule4
- Schedule a workshop site with four boardsThe demand of a main board, two boards and a mezzanine board by Table C4.
- Demand of a house with a garage boardThe single‑phase demand of a house board feeding a garage board.
- Check a submain device against its boardWhether a 160 A submain device covers a busy board of 14 circuits.
- Site demand for a supply applicationThe site demand in kVA of a shop with a main board and two boards.
Power
51Three phase power5
- Convert amps to three phase powerThe kW and kVA of a 63 A three phase load at 400 V.
- Find kW from a clamp readingThe kW of 100 A at 0.8 power factor.
- Find the kVA of a single‑phase loadThe kVA of 40 A at 230 V.
- Find the reactive power of a loadThe kvar of 50 A at 0.7 power factor.
- Turn a meter reading into kWThe kW from a metered current and power factor.
Transformer5
- Check a transformer secondaryThe secondary current and the fault level of a 1000 kVA unit.
- Find the currents of a 500 kVA transformerThe primary and secondary currents of a 500 kVA unit.
- Find fault level of a 300 kVA unitThe secondary fault current at 4 % impedance.
- Check an isolating transformerThe currents of a 5 kVA single‑phase unit.
- Check a 22 kV transformerThe primary current of a 1500 kVA, 22 kV unit.
Generator current5
- Check a 60 kVA standby generatorThe full load current and the fault current of a 60 kVA set at 400 V.
- Check a 200 kVA generatorThe full load current of a 200 kVA set at 400 V.
- Check a portable generatorThe current of a 10 kVA single‑phase set.
- Find a generator's fault currentThe fault current of a 500 kVA set at 15 % reactance.
- Check a holiday park backup setThe current and fault level of a 150 kVA set.
Ohm's law4
- Find the resistance of a heater elementThe working resistance and current of a 2 kW heater on 230 V.
- Find the current of a 12 V lampThe current a 50 W lamp draws on 12 V d.c.
- Find the power of a three‑phase heater bankThe kW of a star heater bank of 20 Ω per phase on 400 V.
- Find the voltage across a resistorThe volts across 470 Ω carrying 20 mA d.c.
Generator sizing4
- Size a generator for a bore pumpThe set for a 5.5 kW bore pump started direct on line after the lights.
- Size a generator with a star-delta startHow much smaller the set is when the pump starts star-delta.
- Size a standby set for a dairy shedThe set for milking plant, vacuum pump and hot water started in turn.
- Size a generator for a building chillerThe set for lighting, a chiller on a drive and lifts, derated for heat.
Transformer inrush4
- Stop a transformer tripping its breakerWhy an isolation transformer trips a Type B breaker at switch-on, and what holds.
- Pick a breaker for a site transformerThe breaker and cable for a portable site transformer.
- Check a control transformer breakerWhether a small control transformer on an extra-low voltage secondary holds its breaker.
- Size the breaker for a step-down transformerThe smallest breaker of each type for a single‑phase step-down transformer.
Transformer sizing4
- Size a transformer for a new siteThe rating, loading and losses for a site demand with room to grow.
- Size a transformer from a kW demandA demand in kilowatts turned into the transformer rating at its power factor.
- Check a rural single‑phase transformerThe size and voltage drop of a single‑phase transformer for a farm supply.
- Check a plant transformer regulationThe voltage a large transformer drops at a low power factor.
UPS sizing4
- Size a UPS for a comms rackThe UPS and battery to keep a comms rack and security system up for half an hour.
- Find the battery for an hour on UPSHow much battery an office rack needs to run for an hour.
- Size a UPS for a small data hallA three‑phase UPS for forty racks for ten minutes, and its input current.
- Pick a UPS for a home officeThe UPS for a computer and router to ride a short outage.
Neutral current4
- Find the neutral current of a shop boardThe neutral current of a board with 45, 30 and 25 A on its phases.
- Neutral current with heaters and a motorHeaters on one phase and a motor on another: the neutral with two power factors.
- Neutral current of a farm on one phaseMost of the load on one phase: how close the neutral comes to that phase.
- Check the neutral of a mostly three‑phase loadThe out-of-balance current a reduced neutral must still carry.
Voltage unbalance4
- Check the voltage unbalance at a motorThe unbalance of 415, 402 and 409 V at a motor starter.
- Voltage unbalance of a rural supplyHow far out a long rural line is at 400, 384 and 396 V.
- Check the current unbalance of a motorThe current unbalance of a motor drawing 31, 27 and 29 A.
- Find the motor heating from unbalanceHow much a 3 % unbalance adds to the winding temperature rise, by the rule of thumb.
Harmonics4
- Find the harmonic neutral current of an officeThe neutral current of an office floor full of computers, from its spectrum.
- Find the K-factor for a drive transformerThe K-factor of six-pulse drives, for the transformer that feeds them.
- Check an LED lighting circuit for harmonicsWhether a cable for LED drivers is picked on its neutral current.
- Neutral current with some electronic loadThe neutral of a board where electronics are 30 % of the load.
Battery duty cycle4
- Size a substation battery by duty cycleThe Ah and charger of a 125 V battery for a trip and three hours of load.
- Size a 48 V radio site batteryThe Ah and charger for four hours of radio load and a transmit burst.
- Size a 24 V control panel batteryThe Ah for two hours of PLC load and a valve close at the end.
- Find the charger for a faster rechargeThe charger current to put a 110 V battery back in 8 h, not 12.
Solar
26PV string sizing8
- Size solar strings for a 600 V inverterThe modules per string for 49.5 V modules on a 600 V inverter at −5 °C.
- Check string fuses on three parallel stringsWhether three parallel strings of 13.9 A modules call for string fuses, and their rating.
- Size strings for a 1000 V inverterThe modules per string for a commercial inverter.
- Size strings for a cold inland siteThe modules per string at a record low of −8 °C, on a 600 V inverter.
- Check a string on a hot roofWhether the hot voltage stays above the tracker's minimum.
- Check two strings need no fuseWhether two strings in parallel need string fuses.
- Check the array current at the inverterThe array's short-circuit current against the inverter input.
- Size strings for a house trackerThe modules per string for a 450 V window.
Home battery6
- Size a solar battery for a family homeThe kWh a 25 kWh a day home needs to run its evenings on an 8 kW array.
- Check where a home battery can goThe AS/NZS 5139 rules for a battery on a garage wall backing onto a bedroom.
- Size a battery for the evening peakThe kWh to carry 60 % of 22 kWh a day into the evening.
- Size a battery for 6.6 kW of solarThe battery for a 6.6 kW array and a home using 18 kWh a day.
- Size a battery for a day of backupThe battery for one day of backup with a 5 kW peak.
- Size a battery in 5 kWh modulesThe number of 5 kWh modules a home using 24 kWh a day needs.
PV array isolator and earthing4
- Rate the d.c. isolator for a solar arrayCheck an isolator data sheet against two strings at 520 V in the sun.
- Size the earth for a PV array frameThe frame earth for a powered-neutral inverter on 6 mm² array cable.
- Find the currents in a commercial arrayString, sub-array and array currents for 12 strings in three fused sub-arrays.
- Set the earth fault interrupterThe detection setting for a 60 kW array with direct functional earthing.
Battery location check4
- Check a battery beside a hot water unitA garage battery 450 mm from the hot water cylinder.
- Check a battery on a bedroom wallThe barrier an outdoor battery needs on a weatherboard wall to a bedroom.
- Check a battery in a corridorThe egress width left past a battery in an apartment corridor.
- Check the working space at a batteryA 700 mm space against the maker’s 1 m clearance.
Battery arc flash and class4
- Check a 48 V home battery's arc flashThe energy, PPE level and home limit for a 48 V lithium battery.
- See what inter-string fuses saveThe arc flash of a 48 V battery when a fuse clears the arc in 0.1 s.
- Class a lead acid bank in a shedA 24 V lead acid bank in a battery room away from the house.
- Class a high voltage home batteryThe decisive voltage class and energy of a pre-assembled lithium battery.
Safety
50Arc flash7
- Estimate arc flash energy at an MCCThe incident energy at 455 mm from a 25 kA MCC, cleared in 0.15 s.
- Estimate arc flash at a main switchboardThe incident energy at 40 kA cleared in 0.3 s.
- Estimate arc flash at a distribution boardThe incident energy at 10 kA cleared in 0.1 s.
- Estimate arc flash in open airThe incident energy with no enclosure.
- Estimate arc flash at 11 kV switchgearThe incident energy at 11 kV and 12 kA.
- Find the boundary at a longer reachThe incident energy and arc flash boundary at a 600 mm working distance.
- Compare a faster clearing timeThe incident energy of a 25 kA fault cleared in 0.05 s.
Construction site supply6
- Supply a building site from a generatorThe RCD protection for tools on a construction site generator.
- Supply a site from the house boardThe rules when the permanent switchboard feeds the site.
- Supply site wiring from an inverterThe rules for an RCD-protected inverter supply.
- Supply a welder from a generating setThe rule for an arc welder built into a generating set.
- Use hire equipment on a siteThe inspection and RCD rules for hired equipment.
- Supply a site in AustraliaThe supply and RCD rules for a construction site in Australia.
Show and carnival wiring6
- Supply a show ring from a generatorThe RCD and wiring rules for 32 A circuits at a show on a generator.
- Supply a food stallThe RCD rules for a 16 A stall circuit from the network.
- Check a buried cable at a fair groundWhether 0.5 m of cover is enough where pegs are driven.
- Check an aerial over a walkwayWhether a 3 m aerial height passes.
- Supply an amusement rideThe rules for a 63 A circuit that feeds a ride.
- Supply a market in AustraliaThe show rules in Australia for a 20 A circuit.
Wet area zones12
- Check a downlight over a showerWhether an IP20 downlight 0.5 m from a 2.4 m ceiling rose passes.
- Put a socket‑outlet by a basinThe zone and the conditions for a socket‑outlet 0.1 m from a basin.
- Light a spa poolThe zone and IP rating for a light 1 m from a 1500 L spa.
- Put a socket‑outlet beside a bathThe zone and the conditions 0.4 m from a bath.
- Put a switch in a bathroomThe zone for a light switch 0.7 m from a shower.
- Put a socket‑outlet by a kitchen sinkThe zone and the conditions 0.2 m from a sink.
- Light a swimming pool surroundThe zone and IP rating for a light 2 m from a pool.
- Put a socket‑outlet near a poolWhether a socket‑outlet 3 m from a pool passes.
- Fit a light in a saunaThe zone for a luminaire above a sauna heater.
- Light a fountainThe zone and IP rating for a light in a fountain.
- Check a communal shower roomThe IP rating a communal shower asks for.
- Check a bathroom in AustraliaThe zone and IP rating for a light near an open shower, to the Australian rules.
Obtrusive light7
- Check a car-park floodlight at a boundaryWhether a 20 000 lm floodlight 15 m from an upstairs window passes after the curfew.
- Check a bollard path at a boundaryWhether a 500 lm bollard 5 m from a neighbour’s window passes in zone A3.
- Check a tennis court floodlightWhether a 40 000 lm floodlight 20 m from a window passes.
- Check a security light on a houseWhether a 2000 lm wall light 8 m from a neighbour passes.
- Check a light in a rural zoneThe limits for a 5000 lm floodlight 30 m from the boundary in dark zone A1.
- Check a loading dock before the curfewA dock floodlight against the pre-curfew limit.
- Check the upward light of an uplightThe upward light ratio of a façade uplight.
Downlight clearance4
- Check a CA90 downlight against insulationA CA90 light with insulation against its sides, and its clearances.
- Read an old IC-F downlightAn IC-F marking read as IC-4 under insulation.
- Check a CA135 downlight in AustraliaA CA135 light in an Australian home.
- Check a Non‑IC light in a shopA 50 W Non‑IC downlight with insulation kept clear.
Accessory location4
- Check a power point beside a cooktopA socket‑outlet 100 mm from the cooktop edge.
- Place a power point near a gas bottleA socket‑outlet 1.2 m from an exchange gas cylinder outdoors.
- Check a light near a gas relief ventA light 1 m ahead of a 20 mm gas relief vent.
- Place the cooktop isolating switchThe cooktop switch 600 mm from the cooktop edge.
IP rating4
- Read what IP44 meansEach digit of an IP code, by AS 60529.
- Check an outdoor power point codeAn IP44 socket‑outlet outside the eave area against IP33.
- Choose a code for a hosed areaThe least code for high-pressure hosing, and an IP66 light checked.
- Check a light for a sauna roomAn IPX4 light against the IPX4B or IP24 a sauna needs.
Earthing
15Earthing and bonding6
- Size the earth for a shed submainThe protective earth for a 6 mm² copper submain to a shed.
- Size the main earth for large mainsThe main earthing conductor for 95 mm² consumer mains.
- Size the earth for an aluminium submainThe protective earth for a 120 mm² aluminium submain.
- Check an earth by the adiabatic equationThe earth conductor for a 6 kA fault cleared in 0.4 s, by calculation.
- Size the bond at a telecom terminalThe bonding conductor at a telecommunications earth.
- Size a bare copper earthThe earth with the k value of bare copper.
Screen and drain earthing5
- Earth a cable screenWhere to earth the screen and the drain wire.
- Earth an armoured cableWhere the armour of a power cable is earthed.
- Earth a drive cable's screenWhere the braid of a motor cable is earthed for EMC.
- Earth an instrument screen at one endHow a foil screen avoids a hum loop.
- Earth a drain wireWhere the drain wire of a signal cable is earthed.
Outbuilding earthing4
- Earth a shed through the submainThe earth to run with a 10 mm² submain to a shed.
- Set up a shed as its own MENThe PEN, main earth and rod depth for a 16 mm² submain.
- Check a sleep-out with a metal water pipeA separate MEN where a metal pipe joins the buildings.
- Earth a farm shed in AustraliaA separate MEN on a strip electrode for a 25 mm² three phase submain.
Testing
17Test results6
- Check the test results of a new circuitWhether the insulation, earth, Zs and RCD readings pass on a 16 A circuit.
- Check a low insulation readingWhether 0.5 MΩ passes on a final subcircuit.
- Check Zs on a 32 A circuitWhether 0.6 Ω passes on a 32 A C‑curve circuit.
- Check a slow RCDWhether a 30 mA RCD that trips in 45 ms passes.
- Check a five-second circuitThe Zs limit for a submain with a 5 s disconnection time.
- Check earth continuity on a lighting circuitWhether 0.9 Ω passes on 1.5 mm².
Test and tag7
- Tag a workshop angle grinderThe retest interval and the pass marks for a Class I tool in a workshop.
- Tag a kettle in an officeThe retest interval for a Class I appliance in an office kitchen.
- Tag a double-insulated drillThe interval and insulation limit for a Class II tool.
- Tag a hire extension leadThe interval for hire equipment.
- Test a portable RCDWhether a portable RCD that trips in 25 ms passes.
- Tag cleaning equipmentThe interval for commercial cleaning equipment.
- Check a leakage readingWhether 3 mA of leakage passes on a Class I heater.
Test schedule4
- Print the test sheet for a house boardSix circuits with their tests in order and the pass limits.
- Test a workshop board with three‑phase socketsAdds the phase sequence test to the three‑phase socket circuit.
- Make an Australian test sheetA house board where each RCD must operate, with no trip time.
- Mark a circuit for the reduced test voltageA data rack circuit tested at the lower insulation voltage.
Fire
21Sounder level6
- Set the sounder level in a plant roomThe alarm level a sounder must reach over 78 dB of plant noise.
- Set the sounder level in a bedroomThe level at the bedhead in sleeping accommodation.
- Set the level where ear protection is wornWhether a visual device is needed with ear protection.
- Set the level for a voice systemThe level over ambient for a voice alarm.
- Set the level on a balconyThe level a sounder must reach on a balcony.
- Set the level in a quiet officeThe level a sounder must reach over 45 dB of ambient sound.
Fire alarm cabling4
- Choose the cable for a sounder circuitThe minimum conductor size for a fire alarm alerting device circuit.
- Choose the cable for a detector circuitThe minimum conductor for a four‑core detector circuit.
- Choose the cable for a transmission pathThe fire rating a transmission path needs.
- Choose the cable for staged evacuationThe cable for a staged evacuation circuit.
Fire alarm battery5
- Size a fire panel batteryThe battery capacity for 0.35 A on standby and 2.5 A in alarm.
- Size a battery for an unmonitored panelThe capacity for 72 hours of standby.
- Size a battery with ageingThe capacity with ageing and temperature factors.
- Size a small panel batteryThe capacity for 0.1 A standby and 0.8 A alarm.
- Size a 24-cell panel batteryThe capacity of a 48 V panel.
Detector spacing6
- Space smoke detectors in an officeThe number of point smoke detectors for a 24 by 9 m office.
- Space heat detectors in a kitchenThe number of point heat detectors for a 6 by 5 m kitchen.
- Space smoke detectors in a corridorThe detectors for a 30 by 1.8 m corridor.
- Space detectors under deep beamsThe count with 400 mm beams at 1.2 m centres.
- Space beam detectors in a warehouseThe beam smoke detectors for a 60 by 30 m warehouse.
- Space line heat detection in a car parkThe runs of line heat detection for a 40 by 16 m bay.
Regulatory
21Regulatory pathway12
- Find the paperwork for a home solar jobThe work category and the certificates a home PV alteration needs in NZ.
- Find the paperwork for a job in NSWThe CCEW, the eCert portal and the 7 day deadline.
- Find the paperwork for a job in VictoriaThe certificate of electrical safety, where it goes and when.
- Find the paperwork for a job in QueenslandThe certificate of testing and compliance and how long to keep it.
- Find the notices for a job in WAThe preliminary notice, the completion notice and the safety certificate.
- Find the paperwork for a new houseThe certificates a new domestic installation needs.
- Find the paperwork for a like-for-like repairThe category of a replacement in an existing installation.
- Find what a homeowner may doThe limits on a homeowner's own wiring work.
- Find the paperwork for mains workThe inspection mains work needs.
- Find the paperwork for a hazardous areaThe category and inspection for a hazardous area job.
- Find the paperwork for a medical fit-outThe category and inspection for a patient area.
- Find the paperwork for a generator connectionThe category for mains-parallel generation.
Assessment intervals6
- Find the inspection interval for a marinaHow often a marina installation must have an assessment in NZ.
- Find the interval for a construction siteThe verification intervals for a construction site.
- Find the interval for a carnivalHow often show wiring must have an assessment.
- Find the interval for a hazardous areaThe inspection standard for a hazardous area.
- Find the interval for a medical areaThe assessment a medical installation must have.
- Find the fire alarm test intervalsThe monthly and annual checks NZS 4512 lists.
Builders and guides
11Builders8
- Wire a houseRooms and points become circuits, cable sizes and a maximum demand.
- Plan a house layoutRooms and points become circuits, cable sizes and a maximum demand.
- Draw a plan of the jobRooms and devices on a plan become points, circuits and a schedule.
- Lay out fire detectors in a roomThe spacing calculator sets the grid, and the plan places the detectors.
- Lay out luminaires for a target luxA stated lumen estimate places a grid of luminaires in a room.
- Draw an instrument loop with tagsInstruments, runs and a controller become a loop with a cable check.
- Build an asset listAssets, their interfaces and the cables that link them, each checked by a calculator.
- Size the submains of a siteBoards and their loads become submains sized from each board's demand.