AS/NZS 3008.1.2:2017

Table 27(1), 27(2)

Rating factors for air and soil ambient temperature

The cable size and correction factors tools read the factor for the air or ground temperature on the route. A hot route lowers the current the cable can carry.

Verified: read against the printed standard, pages 88. Checked 24 Sept 2026.

Units: Temp °C

These are the values AmpSize encodes. No text of the standard is reproduced. Verify against the current standard.

Back to its card on the AS/NZS 3008.1.2:2017 page

41 rows

Table 27(1), 27(2), Rating factors for air and soil ambient temperature
InsulationMediumConductor temp CTemp (°C)Factor
PVCair75151.18
PVCair75201.12
PVCair75251.06
PVCair75301
PVCair75350.94
PVCair75400.88
PVCair75450.8
PVCair75500.72
PVCair75550.63
PVCair75600.53
PVCair75650.43
PVCair75700.32
XLPEair90151.15
XLPEair90201.09
XLPEair90251.05
XLPEair90301
XLPEair90350.95
XLPEair90400.91
XLPEair90450.85
XLPEair90500.8
XLPEair90550.74
XLPEair90600.66
XLPEair90650.59
XLPEair90700.52
XLPEair90750.43
XLPEair90800.31
XLPEair90850.17
PVCsoil75101.04
PVCsoil75151
PVCsoil75200.95
PVCsoil75250.91
PVCsoil75300.86
PVCsoil75350.81
PVCsoil75400.75
XLPEsoil90101.04
XLPEsoil90151
XLPEsoil90200.96
XLPEsoil90250.93
XLPEsoil90300.91
XLPEsoil90350.87
XLPEsoil90400.83