Earth fault loop impedance calculator

Suriin ang Zs laban sa maximum sa AS/NZS 3000 Table 8.1 para sa iyong device, sa New Zealand at Australia.

Reads AS/NZS 3008.1.2:2017 (NZ), AS/NZS 3008.1.1:2017 and 2025 (AU) and AS/NZS 3000:2018. Tables checked 27 Sept 2026.

Mga input

Worked example gamit ang mga default na input.

External impedance Ze
0.35 Ω
Voltage
230 V
Curve ng device
Curve C
Device rating
20 A
Sinukat na Zs
0 Ω
Standard
NZ · AS/NZS 3008.1.2
Haba ng run
30 m
Laki ng aktibong konduktor
2.5 mm²
Laki ng earth conductor
Mula sa Table 5.1
Material
Tanso
Insulation
PVC 75 °C

Earth fault loop impedance

0.89Ω

Pinakamataas na pinapayagang Zs
1.53Ω
Prospective fault current
258.25A
Earth conductor
2.5mm²
R1 + R2
0.54Ω
Pinakamahabang haba sa Zs
65.67m

Design aid lang ang resultang ito. I-verify ito laban sa kasalukuyang standard.

Mga hakbang ng kalkulasyon

  1. Laki ng earth conductor2.5mm²

    AS/NZS 3000:2018 Table 5.1

  2. R1 + R2 kada km sa operating temperature ng conductor18.02Ω/km

    AS/NZS 3008.1.2:2017 Table 30 (Xc), Tables 34–35 (Rc) p.98, p.102–103

  3. R1 + R20.54Ω
  4. Earth fault loop impedanceResulta0.89Ω
  5. Pinakamataas na pinapayagang Zs1.53Ω

    AS/NZS 3000:2018 Table 8.1

  6. Prospective fault current258.25A

Tungkol sa calculator na ito

How this is calculated

The tool works out the earth fault loop impedance of one circuit. It compares that impedance with the maximum for the protective device.

  1. Earth conductor. If you leave the earth size on From Table 5.1, the tool picks it from the active conductor size.
  2. R1 + R2. It reads the resistance of the active and the earth conductors at their operating temperature. The Standard select decides which part it reads. It reads AS/NZS 3008.1.2 for New Zealand or AS/NZS 3008.1.1 for Australia. It adds the two and multiplies by the run length.
  3. Zs. It adds the external impedance: Zs = Ze + (R1 + R2).
  4. Maximum Zs. It reads the maximum for the device curve and rating from AS/NZS 3000 Table 8.1. The circuit passes when Zs is at or below that maximum.
  5. Fault current. It divides the voltage by Zs to get the prospective fault current.
  6. Maximum length. It works out the run length at which Zs reaches the maximum.

Ze is a site value. Measure it, or ask the network operator for it. The tool warns when Ze alone takes 90 % or more of the limit. After you install the circuit, test it and compare the measured Zs with the calculated one.

StepTable or clauseWhat it decides
Earth conductorAS/NZS 3000 Table 5.1The earth size when you do not name one
Conductor resistanceTables 34 and 35R1 and R2 at the operating temperature
Maximum ZsAS/NZS 3000 Table 8.1The limit for the device curve and rating
Disconnection timeAS/NZS 3000 Cl 5.7.2The times behind the Table 8.1 limits
Failed checkAS/NZS 3000 Cl 5.7.4The clause a circuit over the limit cites

Tables without a standard named are in the part of AS/NZS 3008.1 you pick. The Table 8.1 guide explains why the B, C and D curve limits differ.

Common circuits, worked with the tool

Each line states its route. Every line uses copper cable with PVC insulation, a Ze of 0.35 Ω at 230 V and the New Zealand tables. The earth size comes from Table 5.1.

New Zealand and Australia

The Standard select picks the part of AS/NZS 3008.1 for the conductor resistance. Table 8.1 and Table 5.1 are in AS/NZS 3000, which is the same in both countries.

Keep the result

Every input sits in the page address, so the link in your browser reproduces the calculation. The PDF button prints the result with its steps and table references. Saving a calculation to a project needs a free account.

Mga tanong

Design aid ang resulta. I-verify ito laban sa kasalukuyang standard.

Ano ang ginagawa ng loop impedance calculator?

Kinukuha ng tool ang active at earth resistance sa haba ng run, at dinadagdag ang external impedance Ze. Ang kabuuan ay ang Zs, ang loop impedance para sa earth fault. Ikinukumpara nito ang Zs sa maximum para sa protective device. Iniuulat din nito ang prospective fault current at ang pinakamahabang run na pumapasa pa rin.

Aling mga table ang nagtatakda ng maximum Zs?

Galing ang maximum Zs sa AS/NZS 3000:2018 Table 8.1 para sa device curve at rating. Galing ang laki ng earth conductor sa Table 5.1. Galing ang conductor resistance sa AS/NZS 3008.1.2:2017 Tables 34 hanggang 35. Ang bumagsak na check ay tumutukoy sa AS/NZS 3000:2018 Clause 5.7.4.

Ano ang pinakanakakaapekto sa earth fault loop impedance?

Ang Ze, haba ng run at laki ng active conductor ang pinakamalaking nagbabago sa Zs. Ang device curve at rating ang nagtatakda ng limit na pinaghahambingan ng Zs. Kinukuha ang laki ng earth conductor mula sa Table 5.1 maliban kung mag-e-enter ka ng isa. Ang mga cable na parallel ay naghahati lang sa active resistance, hindi sa earth resistance.

Nasusukat ba ng loop impedance calculator ang Ze?

Hindi. Site value ang Ze at hindi ito sinusukat ng tool. Lalabas ang babala kapag ang Ze lamang ay gumagamit ng 90 porsyento o higit pa ng maximum Zs. Kinakalkula ang prospective fault current sa phase to earth voltage, na 230 V bilang default. Nasa page address ang mga input para sa pag-share.

Mga worked example

Background

Mga clause at table na binabasa ng tool na ito

Bawat clause at table, kasama kung paano ito na-verify

Huling na-check ang mga table noong 27 Sept 2026.