接地故障回路阻抗计算器

在新西兰和澳大利亚,按 AS/NZS 3000 Table 8.1 中您的装置的最大值检查 Zs。

Reads AS/NZS 3008.1.2:2017 (NZ), AS/NZS 3008.1.1:2017 and 2025 (AU) and AS/NZS 3000:2018. Tables checked 27 Sept 2026.

输入

使用默认输入值的示例计算。

外部阻抗 Ze
0.35 Ω
电压
230 V
装置曲线
C 型曲线
保护装置额定值
20 A
实测 Zs
0 Ω
标准
NZ · AS/NZS 3008.1.2
敷设长度
30 m
有源导体规格
2.5 mm²
接地导体规格
取自 Table 5.1
材料
铜
绝缘
PVC 75 °C

接地故障回路阻抗

0.89Ω

允许的最大 Zs
1.53Ω
预期短路电流
258.25A
接地导体
2.5mm²
R1 + R2
0.54Ω
Zs 下的最大长度
65.67m

此结果仅供设计参考。请对照现行标准进行核验。

计算步骤

  1. 接地导体规格2.5mm²

    AS/NZS 3000:2018 Table 5.1

  2. 导体工作温度下每公里的 R1 + R218.02Ω/km

    AS/NZS 3008.1.2:2017 Table 30 (Xc), Tables 34–35 (Rc) p.98, p.102–103

  3. R1 + R20.54Ω
  4. 接地故障回路阻抗结果0.89Ω
  5. 允许的最大 Zs1.53Ω

    AS/NZS 3000:2018 Table 8.1

  6. 预期故障电流258.25A

关于此计算器

How this is calculated

The tool works out the earth fault loop impedance of one circuit. It compares that impedance with the maximum for the protective device.

  1. Earth conductor. If you leave the earth size on From Table 5.1, the tool picks it from the active conductor size.
  2. R1 + R2. It reads the resistance of the active and the earth conductors at their operating temperature. The Standard select decides which part it reads. It reads AS/NZS 3008.1.2 for New Zealand or AS/NZS 3008.1.1 for Australia. It adds the two and multiplies by the run length.
  3. Zs. It adds the external impedance: Zs = Ze + (R1 + R2).
  4. Maximum Zs. It reads the maximum for the device curve and rating from AS/NZS 3000 Table 8.1. The circuit passes when Zs is at or below that maximum.
  5. Fault current. It divides the voltage by Zs to get the prospective fault current.
  6. Maximum length. It works out the run length at which Zs reaches the maximum.

Ze is a site value. Measure it, or ask the network operator for it. The tool warns when Ze alone takes 90 % or more of the limit. After you install the circuit, test it and compare the measured Zs with the calculated one.

StepTable or clauseWhat it decides
Earth conductorAS/NZS 3000 Table 5.1The earth size when you do not name one
Conductor resistanceTables 34 and 35R1 and R2 at the operating temperature
Maximum ZsAS/NZS 3000 Table 8.1The limit for the device curve and rating
Disconnection timeAS/NZS 3000 Cl 5.7.2The times behind the Table 8.1 limits
Failed checkAS/NZS 3000 Cl 5.7.4The clause a circuit over the limit cites

Tables without a standard named are in the part of AS/NZS 3008.1 you pick. The Table 8.1 guide explains why the B, C and D curve limits differ.

Common circuits, worked with the tool

Each line states its route. Every line uses copper cable with PVC insulation, a Ze of 0.35 Ω at 230 V and the New Zealand tables. The earth size comes from Table 5.1.

New Zealand and Australia

The Standard select picks the part of AS/NZS 3008.1 for the conductor resistance. Table 8.1 and Table 5.1 are in AS/NZS 3000, which is the same in both countries.

Keep the result

Every input sits in the page address, so the link in your browser reproduces the calculation. The PDF button prints the result with its steps and table references. Saving a calculation to a project needs a free account.

问题

结果仅供设计参考。请依据现行标准核对。

回路阻抗计算器有什么作用?

工具取线路上相线和接地导体的电阻,并加上外部阻抗 Ze。其和为 Zs,即接地故障回路阻抗。它将 Zs 与保护装置的最大值进行比较。它还报告预期短路电流以及仍能通过校核的最长线路。

哪些表格规定最大 Zs?

最大 Zs 取自 AS/NZS 3000:2018 Table 8.1,依据保护装置曲线和额定值。接地导体截面取自 Table 5.1。导体电阻取自 AS/NZS 3008.1.2:2017 Tables 34 至 35。校核不合格时,引用 AS/NZS 3000:2018 Clause 5.7.4。

什么对接地故障回路阻抗影响最大?

Ze、线路长度和相线截面对 Zs 影响最大。保护装置的曲线和额定值决定 Zs 所比较的限值。除非您自行输入,否则接地导体截面取自 Table 5.1。并联电缆只分担相线电阻,不分担接地导体电阻。

回路阻抗计算器是否测量 Ze?

否。Ze 为现场数值,工具不进行测量。当 Ze 单独占最大 Zs 的 90% 或以上时,将出现警告。预期短路电流按相对地电压计算,默认值为 230 V。输入值保存在页面地址中,便于分享。

计算示例

背景

本工具读取的条款和表格

所有条款和表格,及各自的核验方式

表格最后核对于 27 Sept 2026。

这是否有用?