How far can 4 mm² run on a 25 A circuit?

Maximum circuit length calculator

+1 reference

Worked to AS/NZS 3000:2018. Tables checked 26 Sept 2026.

Maximum route length

41m

Fault loop route length
67m
Governing check
Voltage drop
Open the calculator with these inputs

This result is a design aid. Verify it against the current standard.

A drawn result card from the Maximum Circuit Length tool: maximum route length 41 m.

A 4 mm² copper circuit on a 25 A curve C breaker can run 41 m at its full load. Voltage drop sets that length: at 41 m the drop reaches the 5 % limit of AS/NZS 3000:2018 Cl 3.6.2.

The case

The circuit is single‑phase at 230 V with a 2.5 mm² earth and a design current of 25 A at a power factor of 1. AS/NZS 3000:2018 Table B1 gives a fault loop length of 67 m for this cable and device.

What changes the answer

The length scales with the load. With 20 A of design current on the same breaker, the run can reach 51.25 m. The fault loop length does not change with the load. It depends on the cable and the breaker.

See also: What size cable for a 25 A circuit? and Voltage drop basics.

Try it with these inputs

Active conductor
4 mm²
Design current
25 A
Protective device
Type C circuit-breaker
Earth conductor
2.5 mm²
Insulation
PVC
Phases
Single phase
Power factor
1
Device rating
25 A
Voltage drop limit
5 %
Nominal phase voltage
230 V
Open the calculator with these inputs