Skip to content
AmpSize

· 5 min read

What size generator for a dairy shed

Generator sizing from a load list

Worked to AS/NZS 3000:2018.

A drawn result card from the Generator Sizing tool: generator rating, at least 50 kVA.

When the network goes down at milking time, the cows still need milking. A standby set has to run the shed, and it has to start the motors without the voltage falling so far that contactors drop out. This guide sizes one set with the generator sizing calculator. The ideas behind it are explained in Generator sizing for motor starting.

The shed

  • A 7.5 kW vacuum pump, direct on line.
  • A 5.5 kW milk vat chiller, direct on line.
  • A 1.5 kW milk pump, direct on line.
  • 6 kW of hot water and 3 kW of lights and sockets.
  • A three‑phase 400 V supply. Each motor at a power factor of 0.85.

The set's figures are your inputs, not rules. This guide keeps the tool's defaults: a largest dip of 15 %, a subtransient reactance of 15 % and a rated power factor of 0.8. Take the reactance and the derating from the alternator's data sheet, and set the dip to what your loads can ride through. AmpSize holds no generator standard, so it does not check these against one.

Step 1. The running load

The tool adds the real power and the reactive power of every load, then takes the kVA from both.

LoadRunning kVAStarting kVA, direct on line
Vacuum pump, 7.5 kW9.858.82
Milk vat chiller, 5.5 kW7.1943.15
Milk pump, 1.5 kW1.9611.76
Hot water, 6 kW66
Lights and sockets, 3 kW33

The shed draws 25.11 kW and 9.99 kvar running, so the running load is 27.02 kVA. The set must also give the 25.11 kW at its rated power factor of 0.8. That takes a set of at least 31.39 kVA, which is more than 27.02 kVA. On running load alone, the shed needs 31.39 kVA.

A motor's running kVA comes from the motor tool's full load current. The tool takes a direct-on-line start as 6 times that current. It is an assumption, stated on every result.

Step 2. Everything starts at once

After an outage, everything on the board may come back together. Put every load in step 1 and the three motors start at once. The set needs 104.32 kVA to hold that start to a 15 % dip, more than three times the running load. The tool warns that starting the motors in turn can make the set smaller. Open the shed with every load in one step.

Step 3. Start the loads in turn

Bring the loads on in steps after the changeover: the vacuum pump first, then the chiller, then the milk pump with the hot water and lights. A timer on each starter can do it.

Now the vacuum pump starts on its own. It is the largest start, so it sets the size: 50 kVA, as Starting step 1. The chiller's step needs 36.68 kVA and the last step 17.65 kVA. At 50 kVA the full load current is 72.16 A and the fault current at the terminals is 481.1 A. Open the shed with the loads in steps.

Step 4. Soften the vacuum pump's start

The vacuum pump's start still asks for a set far bigger than the running load. Change how it starts. The tool takes star-delta as a third of the direct-on-line current, a soft starter at the multiple you enter (3 by default), and a variable speed drive at its running current.

Vacuum pump startStep 1 needsSet sizeSet by
Direct on line50 kVA50 kVAStarting step 1
Star-delta16.67 kVA36.68 kVAStarting step 2
Soft starter, 3 × FLC25 kVA36.68 kVAStarting step 2
Variable speed drive8.33 kVA36.68 kVAStarting step 2

Any of the three takes the vacuum pump out of the running. The chiller's direct-on-line start now sets the size at 36.68 kVA. Open the shed with the pump on star-delta, on a soft starter or on a drive.

Some sheds already run the vacuum pump on a drive to hold the vacuum steady. If yours does, enter it as a variable speed drive.

Step 5. Soften the chiller too

Put the chiller on a soft starter as well, with the vacuum pump on its drive. The chiller's step now needs 18.34 kVA, and no start needs more than the running load. The running load sets the size at 31.39 kVA. At that size the largest dip is 9.3 %, the full load current is 45.31 A and the fault current is 302.05 A. Open the shed with both motors softened.

Past this point a smaller set needs a smaller running load, not a gentler start.

A hot engine room

A set gives less than its rating in heat and at altitude. Take the reduction from the maker's derating data. With 10 % off, the shed in Step 5 needs a set rated 34.88 kVA, and its full load current at that rating is 50.34 A. Open the shed derated 10 %.

The result

ShedSet sizeSet by
Everything in one step104.32 kVAStarting step 1
Loads in steps, all direct on line50 kVAThe vacuum pump's start
Vacuum pump softened36.68 kVAThe chiller's start
Both motors softened31.39 kVAThe running load

Use the size as a first pick. The tool works the dip from the reactance alone. It leaves out the voltage regulator's recovery, the engine's speed dip and the loads already running, which the maker's sizing program models. Check the pick on the maker's data before you order the set.

Installing the set is covered by AS/NZS 3000 Cl 7.3, not by this tool. For the current and fault level of a set you have already chosen, use the generator calculator. For the shed's demand on the network supply, use the maximum demand calculator.

Try it with these inputs

Loads, with the step each starts in
[{"name":"Vacuum pump","kind":"motor","kw":7.…
Open the calculator with these inputs

Where next

The ideas behind it

More worked examples

AmpSize is a design aid. Verify results against the current standard.

Was this useful?

A question, or a value that looks wrong? Contact us.