How many amps can 2.5 mm² carry in Australia?

Existing circuit check

+2 references

Worked to AS/NZS 3008.1.1:2025 (AU) and AS/NZS 3000:2018. Tables checked 27 Sept 2026.

Corrected rating Iz

20A

Largest curve C device the cable allows
20A
Voltage drop
3.13%
Maximum Zs for the device
1.53Ω
Open the calculator with these inputs

This result is a design aid. Verify it against the current standard.

A drawn result card from the Circuit Check tool: circuit on 2.5 mm² passes.

2.5 mm² copper multicore PVC cable carries 20 A enclosed in air in Australia. The tool reads AS/NZS 3008.1.1:2025 Table 3.18 at its 40 °C air reference, with no derating. The largest curve C breaker it allows is 20 A, with no margin to spare.

The case

The circuit is single‑phase at 230 V and runs 20 m at the full 20 A of the breaker. The voltage drop is 3.13 % and the earth fault loop impedance is 0.71 Ω, inside the 1.53 Ω that Table 8.1 allows.

The circuit check reads Passes.

What changes the rating

Clipped direct to a surface, the cable carries 22 A.

The enclosed rating equals the breaker, so any derating fails a 20 A circuit on enclosed 2.5 mm². A grouped or insulated run needs the next size, or a smaller breaker.

See also: What size cable for power points in Australia? and AS/NZS 3008.1.1:2025 overview.

Try it with these inputs

Ambient temperature
40 °C
Cores
Multicore
Device curve
Curve C
Edition
AS/NZS 3008.1.1:2025
Grouped circuits
1
Insulation
PVC 75 °C
Standard
AU · AS/NZS 3008.1.1
Run length
20 m
Design current
20 A
Material
Copper
Installation method
Enclosed in air
Power factor
1
Phases
Single phase
Device rating
20 A
Installed cable size
2.5 mm²
Voltage
230 V
External impedance Ze
0.35 Ω
Open the calculator with these inputs

Where next

The ideas behind it

More worked examples

AmpSize is a design aid. Verify results against the current standard.