Voltage drop calculator

Voltage drop calculator para sa New Zealand at Australia. Galing ang impedance ng conductor sa AS/NZS 3008.1.2 o 3008.1.1, at ang limit sa AS/NZS 3000 Clause 3.6.2.

Reads AS/NZS 3008.1.2:2017 (NZ), AS/NZS 3008.1.1:2017 and 2025 (AU) and AS/NZS 3000:2018. Tables checked 27 Sept 2026.

Mga input

Worked example gamit ang mga default na input.

Supply
a.c.
Mga phase
Three phase
Voltage
400 V
Design current
50 A
Haba ng run
60 m
Power factor
0.9
Standard
NZ · AS/NZS 3008.1.2
Cable
16 mm² Tanso PVC 75 °C
Mga core
Multicore
Limit ng voltage drop
5 %
System
Mababang boltahe (limitasyong itinakda mo)
Neutral current
0 A

Voltage drop

1.69%

Voltage drop
6.74V
Drop kada amp-metre
2.25mV/A·m
Pinakamahabang haba sa limit
177.98m
Limit ng voltage drop
5%

Design aid lang ang resultang ito. I-verify ito laban sa kasalukuyang standard.

Mga hakbang ng kalkulasyon

  1. Resistance1.4Ω/km

    AS/NZS 3008.1.2:2017 Table 30 (Xc), Tables 34–35 (Rc) p.98, p.102–103

  2. Reactance0.09Ω/km

    AS/NZS 3008.1.2:2017 Table 30 (Xc), Tables 34–35 (Rc) p.98, p.102–103

  3. mV/A·m2.25mV/A·m

    AS/NZS 3008.1.2:2017 Cl 4.5

  4. Voltage drop6.74V
  5. Voltage drop percentResulta1.69%
  6. Limitasyon ng voltage drop5%

    AS/NZS 3000:2018 Cl 3.6.2

  7. Pinakamahabang haba177.98m

Tungkol sa calculator na ito

How this is calculated

The tool works out the drop for one cable, one run length and one current. It compares the drop with the limit for the system.

  1. Resistance and reactance. It reads the conductor resistance at its operating temperature and the reactance for your size, material, insulation and core count. The Standard select decides which part it reads. It reads AS/NZS 3008.1.2 for New Zealand or AS/NZS 3008.1.1 for Australia. Cables in parallel divide both values.
  2. Drop per ampere metre. It combines the two with the power factor. On one phase it takes 2 × (R cos φ + X sin φ). On three phases it takes √3 × (R cos φ + X sin φ). The result is in mV/A·m.
  3. Drop. It multiplies that figure by the current and the run length. It divides the volts by the nominal voltage to get the percent.
  4. Unbalanced load. On three phases with a neutral current, it works the drop on one conductor. It adds the neutral current over the neutral length and compares the drop with the phase voltage.
  5. Limit. It compares the percent with the limit for the system. It also gives the run length at which the drop reaches the limit.
  6. Single‑core cable. If you do not know the formation, the tool uses the highest reactance for single‑core cable and says so.
StepTable or clauseWhat it decides
ResistanceTables 34 and 35The conductor resistance at its operating temperature
ReactanceTable 30The reactance for the cable and, for single core, its formation
Drop per ampere metreCl 4.5How resistance, reactance and power factor combine
Unbalanced loadCl 4.6The drop with a neutral current on three phases
Low voltage limitAS/NZS 3000 Cl 3.6.2The limit for a low voltage circuit
Extra-low voltage limitAS/NZS 3000 Cl 7.5.7The limit for an extra-low voltage circuit

Tables without a standard named are in the part of AS/NZS 3008.1 you pick. Each result step names the edition it read.

The limit

SystemLimit the tool appliesClause
Low voltageThe limit you set, 5 % by defaultAS/NZS 3000 Cl 3.6.2
Extra-low voltage10 % of the nominal voltageAS/NZS 3000 Cl 7.5.7

The tool checks one run at a time. When a submain feeds a final subcircuit, add the two drops and compare the total with the limit.

Common circuits, worked with the tool

Each line states its route. Every line uses multicore copper cable with PVC insulation and the New Zealand tables. The power factor is 0.9, except where a line names a different value.

New Zealand and Australia

The Standard select picks the part of AS/NZS 3008.1 the tool reads. The limits come from AS/NZS 3000, which is the same in both countries.

d.c. circuits

Set Supply to d.c. for a battery, PV or ELV d.c. run. The tool reads the d.c. resistance of each size from AS/NZS 3008.1.1:2025 Tables 4.6(A), 4.6(B), 4.8(A) and 4.8(B). These are encoded at the maximum conductor temperature: 75 °C for PVC and 90 °C for XLPE. Single‑core cable reads Table 4.6, multicore Table 4.8. The tool takes 2 × current × resistance × length for the two wires. It uses no reactance, no power factor and no phases. AS/NZS 3008.1.2:2017 prints no d.c. tables, so New Zealand reads the 2025 part too. The limit follows the System select, as on a.c.

The DC cable size calculator reads the printed d.c. mV/A.m of Tables 4.16 to 4.23 instead, which is twice the resistance rounded. Its drop can differ from this tool in the last digit.

Keep the result

Every input sits in the page address, so the link in your browser reproduces the calculation. The PDF button prints the result with its steps and table references. Saving a calculation to a project needs a free account.

See also: AS/NZS 3000 Clause 3.6.2: voltage drop limit, Voltage drop with the mV/A·m method and Voltage drop basics.

Mga tanong

Design aid ang resulta. I-verify ito laban sa kasalukuyang standard.

Ano ang ginagawa ng voltage drop calculator?

Binabasa ng tool ang resistance at reactance ng conductor. Pinagsasama nito ang mga ito sa power factor para makuha ang voltage drop sa millivolts kada amp metre. Pagkatapos, iniuulat nito ang voltage drop sa volts at ang pinakamahabang run na nakakatugon pa rin sa limit. Ibinibigay din nito ang voltage drop bilang porsyento ng supply voltage.

Anong voltage drop limit ang itinatakda ng AS/NZS 3000?

Ang default na limit ay 5 porsyento at puwede mo itong baguhin. Kapag extra-low voltage ang pinili, ang limit ay nagiging 10 porsyento mula sa AS/NZS 3000:2018 Clause 7.5.7. Ang resulta na higit sa limit ay minarkahang fail, at lalabas ang babala kapag higit sa 80 porsyento ng limit. Galing ang impedance sa AS/NZS 3008.1.2:2017 Table 30 at Tables 34 hanggang 35.

Aling mga input ang pinakanakakaapekto sa voltage drop?

Direktang nakakaapekto sa drop ang design current at haba ng run. Tinutukoy ng laki, materyal at insulation ng conductor ang resistance at reactance. Tinutukoy ng power factor kung gaano karaming reactance ang nadadagdag sa drop. Kapag naka-parallel ang mga cable, hinahati ng bilang ng cable ang resistance at reactance.

Bakit magkaiba ang resulta ng three phase sa resulta ng single phase?

Pinaparami ng tool sa square root ng tatlo para sa three phase na resulta. Pinaparami nito sa dalawa para sa single phase na resulta, dahil dumadaloy ang current papunta at pabalik. Kaya magkaiba ang drop ng parehong cable at current sa bawat uri ng supply. Para sa d.c. circuit, gamitin ang DC cable size tool.

Kaya ba nitong kalkulahin ang d.c. voltage drop?

Oo. Itakda ang Supply sa d.c. Binabasa ng tool ang d.c. resistance ng AS/NZS 3008.1.1:2025 sa maximum conductor temperature, sa parehong bansa. Kinukuha nito ang 2 × current × resistance × length para sa dalawang wire, nang walang reactance o power factor. Para i-size ang d.c. cable, gamitin ang DC cable size calculator.

Mga worked example

Lahat ng 11 na guide para sa calculator na ito

Background

Mga clause at table na binabasa ng tool na ito

Bawat clause at table, kasama kung paano ito na-verify

Huling na-check ang mga table noong 27 Sept 2026.

Nakatulong ba ito?

May tanong, o may value na mukhang mali? Makipag-ugnayan sa amin.