Tātaitai heke voltage

Tātaitai heke voltage mō Aotearoa me Ahitereiria. Ka ahu mai te impedance o te kaikawe i AS/NZS 3008.1.2, i AS/NZS 3008.1.1 rānei, ā, ko te tepe i AS/NZS 3000 Clause 3.6.2.

Reads AS/NZS 3008.1.2:2017 (NZ), AS/NZS 3008.1.1:2017 and 2025 (AU) and AS/NZS 3000:2018. Tables checked 27 Sept 2026.

Ngā whakauru

He tauira mahi me ngā whakauru taunoa.

Puna hiko
a.c.
Ngā wāhanga
Wāhanga toru
Voltage
400 V
Iahiko hoahoa
50 A
Roa rerenga
60 m
Power factor
0.9
Paerewa
NZ · AS/NZS 3008.1.2
Taura
16 mm² Parahi PVC 75 °C
Ngā matua
Multicore
Rohe heke voltage
5 %
Pūnaha
Iti-rawa hiko (rohe i whakatakotoria e koe)
Te au neutral
0 A

Heke voltage

1.69%

Heke voltage
6.74V
Hinga mō ia amepia mītera
2.25mV/A·m
Roa teitei rawa i te rohe
177.98m
Rohe heke voltage
5%

He āwhina hoahoa tēnei hua. Manatokohia ki te paerewa o nāianei.

Ngā hīkoi tātaitanga

  1. Ōkeroa1.4Ω/km

    AS/NZS 3008.1.2:2017 Table 30 (Xc), Tables 34–35 (Rc) p.98, p.102–103

  2. Reactance0.09Ω/km

    AS/NZS 3008.1.2:2017 Table 30 (Xc), Tables 34–35 (Rc) p.98, p.102–103

  3. mV/A·m2.25mV/A·m

    AS/NZS 3008.1.2:2017 Cl 4.5

  4. Heke whakahiato6.74V
  5. Heke whakahiato ōrauHua1.69%
  6. Rohe heke whakahiato5%

    AS/NZS 3000:2018 Cl 3.6.2

  7. Roa teitei rawa177.98m

Mō tēnei tātaitai

How this is calculated

The tool works out the drop for one cable, one run length and one current. It compares the drop with the limit for the system.

  1. Resistance and reactance. It reads the conductor resistance at its operating temperature and the reactance for your size, material, insulation and core count. The Standard select decides which part it reads. It reads AS/NZS 3008.1.2 for New Zealand or AS/NZS 3008.1.1 for Australia. Cables in parallel divide both values.
  2. Drop per ampere metre. It combines the two with the power factor. On one phase it takes 2 × (R cos φ + X sin φ). On three phases it takes √3 × (R cos φ + X sin φ). The result is in mV/A·m.
  3. Drop. It multiplies that figure by the current and the run length. It divides the volts by the nominal voltage to get the percent.
  4. Unbalanced load. On three phases with a neutral current, it works the drop on one conductor. It adds the neutral current over the neutral length and compares the drop with the phase voltage.
  5. Limit. It compares the percent with the limit for the system. It also gives the run length at which the drop reaches the limit.
  6. Single‑core cable. If you do not know the formation, the tool uses the highest reactance for single‑core cable and says so.
StepTable or clauseWhat it decides
ResistanceTables 34 and 35The conductor resistance at its operating temperature
ReactanceTable 30The reactance for the cable and, for single core, its formation
Drop per ampere metreCl 4.5How resistance, reactance and power factor combine
Unbalanced loadCl 4.6The drop with a neutral current on three phases
Low voltage limitAS/NZS 3000 Cl 3.6.2The limit for a low voltage circuit
Extra-low voltage limitAS/NZS 3000 Cl 7.5.7The limit for an extra-low voltage circuit

Tables without a standard named are in the part of AS/NZS 3008.1 you pick. Each result step names the edition it read.

The limit

SystemLimit the tool appliesClause
Low voltageThe limit you set, 5 % by defaultAS/NZS 3000 Cl 3.6.2
Extra-low voltage10 % of the nominal voltageAS/NZS 3000 Cl 7.5.7

The tool checks one run at a time. When a submain feeds a final subcircuit, add the two drops and compare the total with the limit.

Common circuits, worked with the tool

Each line states its route. Every line uses multicore copper cable with PVC insulation and the New Zealand tables. The power factor is 0.9, except where a line names a different value.

New Zealand and Australia

The Standard select picks the part of AS/NZS 3008.1 the tool reads. The limits come from AS/NZS 3000, which is the same in both countries.

d.c. circuits

Set Supply to d.c. for a battery, PV or ELV d.c. run. The tool reads the d.c. resistance of each size from AS/NZS 3008.1.1:2025 Tables 4.6(A), 4.6(B), 4.8(A) and 4.8(B). These are encoded at the maximum conductor temperature: 75 °C for PVC and 90 °C for XLPE. Single‑core cable reads Table 4.6, multicore Table 4.8. The tool takes 2 × current × resistance × length for the two wires. It uses no reactance, no power factor and no phases. AS/NZS 3008.1.2:2017 prints no d.c. tables, so New Zealand reads the 2025 part too. The limit follows the System select, as on a.c.

The DC cable size calculator reads the printed d.c. mV/A.m of Tables 4.16 to 4.23 instead, which is twice the resistance rounded. Its drop can differ from this tool in the last digit.

Keep the result

Every input sits in the page address, so the link in your browser reproduces the calculation. The PDF button prints the result with its steps and table references. Saving a calculation to a project needs a free account.

See also: AS/NZS 3000 Clause 3.6.2: voltage drop limit, Voltage drop with the mV/A·m method and Voltage drop basics.

Pātai

He āwhina hoahoa te hua. Manatokohia ki te paerewa o nāianei.

He aha te mahi a te tātaitai heke voltage?

Ka pānui te taputapu i te aukati me te reactance o te kaikawe. Ka whakakotahi ia ki te power factor kia riro ai te heke i ngā millivolt ia amp mita. Kātahi ka whakaatu i te heke i ngā volts me te roa rawa o te ara e tutuki tonu ana i te tepe. Ka hoatu anō te heke hei ōrau o te voltage o te puna hiko.

He tepe heke voltage pēhea e whakatakoto ana a AS/NZS 3000?

The default limit is 5 % and you can change it. Choosing extra-low voltage sets the limit to 10 % from AS/NZS 3000:2018 Clause 7.5.7. A result above the limit is marked as a fail and a warning appears above 80 % of the limit. Impedance comes from AS/NZS 3008.1.2:2017 Table 30 and Tables 34 to 35.

Ko ēhea ngā uruhanga e tino panoni ana i te heke voltage?

Ko te iahiko hoahoa me te roa o te ara e ine tika ana i te heke. Ko te rahi kaikawe, te rawa me te insulation e whakatau ana i te aukati me te reactance. Ko te power factor e whakatau ana te nui o te reactance e tāpiri ana ki te heke. Ko ngā taura parallel e wehe ana i te aukati me te reactance ki te maha o ngā taura.

He aha te putanga wāhanga toru e rerekē ai i te putanga wāhanga kotahi?

Ka whakareatia e te taputapu ki te pūtakere o te toru mō te putanga wāhanga toru. Ka whakareatia ki te rua mō te putanga wāhanga kotahi, nā te mea ka rere te iahiko ki waho, ki muri anō. Nō reira ka hoatu te taura me te iahiko ōrite i tētahi heke rerekē i ia momo puna hiko. Mō tētahi ara d.c., whakamahia te taputapu Rahi Taura DC.

Ka taea e au te tātaitai i te heke voltage d.c.?

Āe. Whakatakotoria te Supply ki d.c. Ka pānui te taputapu i te aukati d.c. o AS/NZS 3008.1.1:2025 i te pāmahana taura nui rawa, i ngā whenua e rua. Ka tango ia i te 2 × iahiko × aukati × roa mō ngā waea e rua, kāore he reactance, he power factor. Hei rahi i tētahi taura d.c., whakamahia te tātaitai Rahi Taura DC.

Ngā tauira mahi

Ngā aratohu 11 katoa mō tēnei tātaitai

Kōrero o muri

Ngā Clause me ngā Table e pānuitia ana e tēnei taputapu

Ia Clause me Table, me te pēhea i manatokotia ai ia tētahi

Ngā tūtohi i arotakehia whakamutunga i te 27 Sept 2026.

He whai hua tēnei?

He pātai, he uara rānei e kitea ana he hē? Whakapā mai.