AmpSize

电压降计算器

新西兰和澳大利亚电压降计算器。导体阻抗取自 AS/NZS 3008.1.2 或 3008.1.1,限值取自 AS/NZS 3000 Clause 3.6.2。

Reads AS/NZS 3008.1.2:2017 (NZ), AS/NZS 3008.1.1:2017 and 2025 (AU) and AS/NZS 3000:2018. Tables checked 27 Sept 2026.

输入

使用默认输入值的示例计算。

供电
a.c.
相
三相
电压
400 V
设计电流
50 A
敷设长度
60 m
功率因数
0.9
标准
NZ · AS/NZS 3008.1.2
电缆
16 mm² 铜 PVC 75 °C
芯线
多芯
电压降限值
5 %
系统
低压(您设定的限值)
中性线电流
0 A

电压降

1.69%

电压降
6.74V
每安培米压降
2.25mV/A·m
限值下的最大长度
177.98m
电压降限值
5%

此结果仅供设计参考。请对照现行标准进行核验。

计算步骤

  1. 电阻1.4Ω/km

    AS/NZS 3008.1.2:2017 Table 30 (Xc), Tables 34–35 (Rc) p.98, p.102–103

  2. 电抗0.09Ω/km

    AS/NZS 3008.1.2:2017 Table 30 (Xc), Tables 34–35 (Rc) p.98, p.102–103

  3. mV/A·m2.25mV/A·m

    AS/NZS 3008.1.2:2017 Cl 4.5

  4. 电压降6.74V
  5. 电压降百分比结果1.69%
  6. 电压降限值5%

    AS/NZS 3000:2018 Cl 3.6.2

  7. 最大长度177.98m

关于此计算器

How this is calculated

The tool works out the drop for one cable, one run length and one current. It compares the drop with the limit for the system.

  1. Resistance and reactance. It reads the conductor resistance at its operating temperature and the reactance for your size, material, insulation and core count. The Standard select decides which part it reads. It reads AS/NZS 3008.1.2 for New Zealand or AS/NZS 3008.1.1 for Australia. Cables in parallel divide both values.
  2. Drop per ampere metre. It combines the two with the power factor. On one phase it takes 2 × (R cos φ + X sin φ). On three phases it takes √3 × (R cos φ + X sin φ). The result is in mV/A·m.
  3. Drop. It multiplies that figure by the current and the run length. It divides the volts by the nominal voltage to get the percent.
  4. Unbalanced load. On three phases with a neutral current, it works the drop on one conductor. It adds the neutral current over the neutral length and compares the drop with the phase voltage.
  5. Limit. It compares the percent with the limit for the system. It also gives the run length at which the drop reaches the limit.
  6. Single‑core cable. If you do not know the formation, the tool uses the highest reactance for single‑core cable and says so.
StepTable or clauseWhat it decides
ResistanceTables 34 and 35The conductor resistance at its operating temperature
ReactanceTable 30The reactance for the cable and, for single core, its formation
Drop per ampere metreCl 4.5How resistance, reactance and power factor combine
Unbalanced loadCl 4.6The drop with a neutral current on three phases
Low voltage limitAS/NZS 3000 Cl 3.6.2The limit for a low voltage circuit
Extra-low voltage limitAS/NZS 3000 Cl 7.5.7The limit for an extra-low voltage circuit

Tables without a standard named are in the part of AS/NZS 3008.1 you pick. Each result step names the edition it read.

The limit

SystemLimit the tool appliesClause
Low voltageThe limit you set, 5 % by defaultAS/NZS 3000 Cl 3.6.2
Extra-low voltage10 % of the nominal voltageAS/NZS 3000 Cl 7.5.7

The tool checks one run at a time. When a submain feeds a final subcircuit, add the two drops and compare the total with the limit.

Common circuits, worked with the tool

Each line states its route. Every line uses multicore copper cable with PVC insulation and the New Zealand tables. The power factor is 0.9, except where a line names a different value.

New Zealand and Australia

The Standard select picks the part of AS/NZS 3008.1 the tool reads. The limits come from AS/NZS 3000, which is the same in both countries.

d.c. circuits

Set Supply to d.c. for a battery, PV or ELV d.c. run. The tool reads the d.c. resistance of each size from AS/NZS 3008.1.1:2025 Tables 4.6(A), 4.6(B), 4.8(A) and 4.8(B). These are encoded at the maximum conductor temperature: 75 °C for PVC and 90 °C for XLPE. Single‑core cable reads Table 4.6, multicore Table 4.8. The tool takes 2 × current × resistance × length for the two wires. It uses no reactance, no power factor and no phases. AS/NZS 3008.1.2:2017 prints no d.c. tables, so New Zealand reads the 2025 part too. The limit follows the System select, as on a.c.

The DC cable size calculator reads the printed d.c. mV/A.m of Tables 4.16 to 4.23 instead, which is twice the resistance rounded. Its drop can differ from this tool in the last digit.

Keep the result

Every input sits in the page address, so the link in your browser reproduces the calculation. The PDF button prints the result with its steps and table references. Saving a calculation to a project needs a free account.

See also: AS/NZS 3000 Clause 3.6.2: voltage drop limit, Voltage drop with the mV/A·m method and Voltage drop basics.

问题

结果仅供设计参考。请依据现行标准核对。

电压降计算器有什么作用?

工具读取导体的电阻和电抗。将二者结合并计入功率因数,得出每安培每米的电压降(毫伏)。随后报告以伏特表示的电压降,以及仍满足限值的最长线路。它还给出占供电电压百分比的电压降。

AS/NZS 3000 规定的电压降限值是多少?

默认限值为 5%,可以更改。选择特低电压时,依据 AS/NZS 3000:2018 Clause 7.5.7 将限值设为 10%。超过限值的结果标记为不合格,并在限值的 80% 以上时显示警告。阻抗取自 AS/NZS 3008.1.2:2017 Table 30 以及 Tables 34 至 35。

哪些输入对电压降影响最大?

设计电流和线路长度与压降成正比。导体截面、材料和绝缘决定电阻与电抗。功率因数决定电抗对压降的影响程度。并联电缆将电阻和电抗均除以电缆根数。

为何三相结果与单相结果不同?

三相结果乘以根号三。单相结果乘以二,因为电流需往返流动。因此,相同的电缆和电流在不同供电类型下产生的电压降不同。直流回路请使用直流电缆截面工具。

可以计算直流电压降吗?

是的。将供电设为直流。工具在两国均依据 AS/NZS 3008.1.1:2025,按导体最高温度读取直流电阻。两根导线按 2 × 电流 × 电阻 × 长度计算,不计电抗及功率因数。如需为直流电缆选型,请使用直流电缆截面计算器。

计算示例

本计算器的全部 11 篇指南

背景

本工具读取的条款和表格

所有条款和表格,及各自的核验方式

表格最后核对于 27 Sept 2026。