Table 8.1, maximum Zs

Maximum earth fault-loop impedance for the total circuit

The test results and test schedule tools read the highest earth fault-loop impedance for the device and its rating. The measured Zs is compared with it.

Verified: read against the printed standard, pages 427. Checked 26 Sept 2026.

Units: Rating A A, Type B Ω, Type C Ω, Type D Ω, Fuse 0.4 s Ω, Fuse 5 s Ω

These are the values AmpSize encodes. No text of the standard is reproduced. Verify against the current standard.

Back to its card on the AS/NZS 3000:2018 page

14 rows

Table 8.1, Maximum earth fault-loop impedance for the total circuit
Rating AType B (Ω)Type C (Ω)Type D (Ω)Fuse 0.4 s (Ω)Fuse 5 s (Ω)
69.65.13.111.515.3
105.83.11.86.49.2
163.61.91.23.15
202.91.50.92.13.6
252.31.20.71.62.7
321.810.61.32.2
401.40.80.511.6
501.20.60.40.71.3
630.90.50.30.60.9
800.70.40.20.40.7
1000.60.30.20.30.5
1250.50.20.10.20.4
1600.40.20.10.20.3
2000.30.20.10.10.2