Engineer أدلة
فحص تصميم، وإعداد الأدلة، ومقارنة مقاسات الكابلات المرشحة لمهمة.
- قراءة 4 دقيقةCar-park floodlight: obtrusive light at a boundaryTwo 10 000 lm floodlights 10 m from a neighbour's window in zone A2, checked against AS/NZS 4282 for lux at the window, candela and the upward light ratio.

- قراءة 3 دقيقةGenerator fault current calculation at 400 VA 500 kVA 400 V standby set at 12 % subtransient reactance gives 721.69 A full load and 6014.07 A fault current, with the decay the figure leaves out.

- قراءة 3 دقيقةIEEE 1584-2002: arc flash model and limitsWhat the IEEE 1584-2002 empirical model governs, where it stops applying, and a 400 V switchboard study that lands on 7.54 cal/cm² at 455 mm.

- قراءة 5 دقيقةArc flash at a 48 V home batteryClass a 48 V lithium home battery with 6 kA at its terminals by AS/NZS 5139, find its arc flash energy and PPE level, then bring it down with fuses.

- قراءة 3 دقيقةIEC 60255-151: IDMT curve constantsWhat IEC 60255-151 governs, which curve sets the IDMT tool carries, and a worked grading pair on standard inverse that clears in 0.21 s and 0.74 s.

- قراءة 3 دقيقةArc flash boundary at a motor control centreArcing current, incident energy and arc flash boundary for a 400 V MCC at 25 kA with a 0.1 s clearing time, and why the equipment type moves the result.

- قراءة 4 دقيقةSwitchboard fault rating at 25 kA for 1 sA 1 second withstand check at 25 kA on 185 mm² copper XLPE, returning a 174.83 mm² minimum size and a 26.46 kA withstand, with a thin margin explained.

- قراءة 3 دقيقةDC isolator rating for a 10 kW solar arrayRate the d.c. isolator and size the frame earth for a four-string domestic array. Check one data sheet that passes and one that fails per pole.

- قراءة 3 دقيقةSolar string sizing for a 600 V inverterHow many 49.5 V modules fit a string on a 600 V inverter at -5 °C? Work cold Voc, hot Vmp, the string current, fuses and the d.c. isolator by AS/NZS 5033.

- قراءة 3 دقيقةStarting a loaded conveyorA 22 kW conveyor that needs 120 % torque to break away. Why star-delta and a soft starter will not start it, and what a drive or autotransformer does.

- قراءة 4 دقيقةMotor circuit for a 15 kW pump: DOL or star-deltaSize a 15 kW 400 V pump circuit: cable, breaker, contactor and overload relay. Compare DOL, star-delta, soft starter and drive starts.

- قراءة 3 دقيقةTransformer secondary fault current for 500 kVAA 500 kVA 11 kV to 400 V transformer at 6 percent impedance, worked through to 721.69 A of secondary full load current and 12,028.13 A of fault current.

- قراءة 3 دقيقةFactory power factor correction: 250 kW at 0.78A 250 kW factory load at 0.78 power factor lifted to 0.95. The kvar, the capacitor steps, the current saved, the kVA released and why the bank is detuned.

- قراءة 3 دقيقةFault level at a sub‑board, 300 kVA transformerWork the prospective fault current at a sub-board 45 m from a 300 kVA transformer, three-phase and phase-earth, and check 6 kA and 10 kA breakers against it.

- قراءة 4 دقيقةAmpSize vs jCalc vs free cable sizing toolsCompare AmpSize with jCalc and other free cable sizing tools. One 63 A three-phase submain shows which checks decide a size, and what AmpSize leaves out.

- قراءة 3 دقيقةArc flash incident energy at a 400 V switchboardA 400 V board with 20 kA bolted fault and 0.2 s clearing gives 6.23 cal/cm² at 455 mm, an arcing current of 9.64 kA and a 1395.97 mm boundary.

- قراءة 4 دقيقةAS/NZS 3008.1.2 Table 52: the k factorWhat Table 52 governs, how the adiabatic check uses k, and a 10 kA fault cleared in 0.1 s that needs 22.11 mm² against an installed 25 mm² conductor.

- قراءة 3 دقيقةIDMT curve grading for a 100 A feederTwo standard inverse relays at 2000 A give a feeder trip at 0.23 s, an incomer trip at 0.99 s and a grading margin of 0.76 s, read off one chart.

- قراءة 6 دقيقةAS/NZS 3008.1.1 table numbers: 2017 to 2025Each AS/NZS 3008.1.1 table AmpSize reads, with its 2017 number, its 2025 number and whether its values moved, and one submain that cites both sets.

- قراءة 4 دقيقةAS/NZS 3008.1.1 vs 3008.1.2: AU and NZ conditionsThe AU part of AS/NZS 3008.1 rates cable at 40 °C air and the NZ part at 30 °C. One 32 A circuit needs 6 mm² in Australia and 4 mm² in New Zealand.

- قراءة 5 دقيقةAS/NZS 3008 vs BS 7671: cable sizing comparedHow BS 7671 and AS/NZS 3000 with AS/NZS 3008.1 size a cable, where they differ, and why a BS current rating never converts into an AS/NZS one.

- قراءة 5 دقيقةDC cable size: 48 V battery and 600 V PV arrayTwo d.c. circuits sized to AS/NZS 3008.1.1:2025, a 48 V battery-to-inverter run that current sizes and a 600 V array feed that voltage drop sizes.

- قراءة 3 دقيقةProspective fault current at a main switchboardA 16 kA fault cleared in 0.1 s on 70 mm² copper XLPE, with the minimum conductor size, the withstand current and the k factor the adiabatic check returns.

- قراءة 5 دقيقةAS/NZS 3008.1.1:2025: what changed from 2017The 2025 AU part adds d.c. ratings to 1500 V, renumbers every table and moves some ratings. Four circuits, each run on both editions, show what moves.

- قراءة 3 دقيقةVoltage rise for a 5 kW solar inverter cableA 5 kW single-phase inverter 40 m from the switchboard on 10 mm² copper, with the rise in volts, the percent and the maximum length the tool returns.

- قراءة 4 دقيقةEarth fault loop impedance and maximum ZsWhat earth fault loop impedance measures, how the maximum Zs check works, and a 32 A circuit on 6 mm² over 25 m that lands on 0.67 ohms against a 0.96 limit.

- قراءة 3 دقيقةVoltage drop with the mV/A·m methodHow the millivolt per amp metre method works, with a 32 A run over 25 metres on 6 mm² copper and the exact drop, percent and maximum length the tool returns.

الحاسبات التي تستخدمها هذه الأدلة
- مدقق الضوء المزعجتحقّق من الإضاءة الخارجية عند نافذة على حد الملكية وفق AS/NZS 4282.
- حاسبة تيار المولّدتيار الحمل الكامل وتيار العطل للمولّد من قيمته kVA.
- حاسبة وميض القوس الكهربائيقدّر طاقة وميض القوس الكهربائي وفئة PPE.
- وميض القوس للبطارية وفئتهاDVC للبطارية، وفئة الخطر، وطاقة وميض القوس، ومستوى PPE.
- حاسبة تدرّج IDMTارسم منحنيات فصل مرحّلات التيار الزائد ذات الزمن العكسي.
- حاسبة تحمّل الكابل لتيار العطلتحقّق من أن الموصل يتحمل تيار العطل.
- حاسبة مفتاح عزل PV والتأريضقيّم كابلات مصفوفة PV ومفتاح العزل للتيار المستمر والتأريض.
- حاسبة سلسلة PVالوحدات في كل سلسلة وتيار السلسلة ومفتاح العزل لـ PV.
- مقارنة طرق بدء تشغيل المحركقارن بدءات DOL والنجمة-المثلث والبدء الناعم والمشغّل.
- حاسبة دائرة المحركالكابل والقاطع والكونتاكتور والحمل الزائد لمحرك واحد.
- حاسبة المحوّلاحسب تيار الحمل الكامل والمعاوقة للمحوّل.
- حاسبة تصحيح معامل القدرةحدّد قدرة المكثف بوحدة kvar اللازمة لرفع معامل القدرة.
- حاسبة مستوى العطلتيار العطل المتوقع عند لوحة من مصدرها.
- حاسبة مقاس الكابلاعثر على أصغر مقاس كابل يكون مطابقاً في كل فحص.
- حاسبة مقاس كابل DCحدّد مقاس كابل d.c. حتى 1500 V للتيار وهبوط الجهد.
- حاسبة ارتفاع الجهداحسب ارتفاع الجهد للتوليد الموزّع أو PV.
- حاسبة معاوقة حلقة عطل التأريضتحقّق من معاوقة حلقة عطل التأريض مقارنةً بالحد الأقصى لـ Zs.
- حاسبة هبوط الجهداحسب هبوط الجهد على مسار الكابل وتحقّق من الحد.