AS/NZS 3000:2018
Table 5.1, copper
Minimum earthing conductor size by active conductor size
The loop impedance and cable size tools read the smallest earthing conductor for the active conductor size. The earth size feeds straight back into the loop impedance sum.
Verified: read against the printed standard, pages 278–279. Checked 27 Sept 2026.
Units: Active mm², Earth mm²
These are the values AmpSize encodes. No text of the standard is reproduced. Verify against the current standard.
20 rows
| Active (mm²) | Earth (mm²) |
|---|---|
| 1 | 1 |
| 1.5 | 1.5 |
| 2.5 | 2.5 |
| 4 | 2.5 |
| 6 | 2.5 |
| 10 | 4 |
| 16 | 6 |
| 25 | 6 |
| 35 | 10 |
| 50 | 16 |
| 70 | 25 |
| 95 | 25 |
| 120 | 35 |
| 150 | 50 |
| 185 | 70 |
| 240 | 95 |
| 300 | 120 |
| 400 | 120 |
| 500 | 120 |
| 630 | 120 |