AS/NZS 3000:2018
Table 5.1, copper
Minimum earthing conductor size by active conductor size
The loop impedance and cable size tools read the smallest earthing conductor for the active conductor size. The earth size feeds straight back into the loop impedance sum.
Na-verify: binasa laban sa naka-print na standard, mga pahina 278–279. Na-check noong 27 Sept 2026.
Mga unit: Active mm², Earth mm²
Ito ang mga value na ine-encode ng AmpSize. Walang text ng standard na inilalathala. I-verify laban sa kasalukuyang standard.
20 na row
| Active (mm²) | Earth (mm²) |
|---|---|
| 1 | 1 |
| 1.5 | 1.5 |
| 2.5 | 2.5 |
| 4 | 2.5 |
| 6 | 2.5 |
| 10 | 4 |
| 16 | 6 |
| 25 | 6 |
| 35 | 10 |
| 50 | 16 |
| 70 | 25 |
| 95 | 25 |
| 120 | 35 |
| 150 | 50 |
| 185 | 70 |
| 240 | 95 |
| 300 | 120 |
| 400 | 120 |
| 500 | 120 |
| 630 | 120 |