AS/NZS 3000:2018

Table 3.8, 3.10

Aerial conductor clearances and spacing at supports

The aerial spans tool reads the minimum clearance for each conductor type from Table 3.8. From Table 3.10 it reads the conductor spacing at the supports for a span. Table 3.10 stops at a 60 m span. The tool refuses a longer span rather than hold the 60 m figure.

Verified: read against the printed standard, pages 206, 208. Checked 26 Sept 2026.

Units: Clearance m, Spacing m, Span m

These are the values AmpSize encodes. No text of the standard is reproduced. Verify against the current standard.

Back to its card on the AS/NZS 3000:2018 page

7 rows

Table 3.8, 3.10, Aerial conductor clearances and spacing at supports
KindConductorOver areas used by vehiclesOver areas not used by vehiclesOver roofs used for traffic or resortOver other roofs and structuresHorizontal from wallsFrom clothes lines aerials or stay wiresFrom telecommunications linesAbove swimming poolsAbove sailing or irrigationMax span MInsulatedBare
clearancebare5.553.73221.2——
clearanceinsulated-unsheathed4.6332120.635.5
clearanceneutral-screened4.632.70.5120.634.5
spacing100.20.4
spacing250.30.5
spacing450.40.6
spacing600.50.7