Table 5.1, parahi

Minimum earthing conductor size by active conductor size

The loop impedance and cable size tools read the smallest earthing conductor for the active conductor size. The earth size feeds straight back into the loop impedance sum.

Kua manatokotia: pānuitia ki te paerewa tā, whārangi 278–279. I tirohia 27 Sept 2026.

Ngā unit: Active mm², Earth mm²

Ko ēnei ngā uara e tuhia ana e AmpSize. Kāore he kupu o te paerewa e tuhia ana. Whakamanahia ki te paerewa o nāianei.

Hoki ki tana kāri i te whārangi AS/NZS 3000:2018

20 rārangi

Table 5.1, Minimum earthing conductor size by active conductor size
Active (mm²)Earth (mm²)
11
1.51.5
2.52.5
42.5
62.5
104
166
256
3510
5016
7025
9525
12035
15050
18570
24095
300120
400120
500120
630120