DC cable size calculator

DC cable size calculator para sa New Zealand at Australia, hanggang 1500 V d.c. Binabasa nito ang d.c. ratings ng AS/NZS 3008.1.1:2025 at ang mV/A.m. Para sa NZ, itinatama nito ang mga ito sa 30 °C at minamarkahan ang resulta bilang derived.

Reads AS/NZS 3008.1.1:2025 (AU). Tables checked 27 Sept 2026.

Mga input

Worked example gamit ang mga default na input.

Standard
AU · AS/NZS 3008.1.1:2025
Voltage
48 V d.c.
Design current
100 A
Uri ng supply
ELV, 120 V d.c. o mas mababa (10 %)
Limit ng voltage drop
10 %
Haba ng ruta
5 m
Installation method
Unenclosed, magkadikit
Temperatura ng hangin
40 °C
Naka-group na circuit
1
Grouping arrangement
Pinagsama-sama sa ibabaw o nakasara
Mga cable
Dalawang single‑core cable
Material
Tanso
Insulation
PVC 75 °C

Laki ng conductor

35mm²

Itinamang rating Iz
119A
Voltage drop
0.64V
Voltage drop, porsyento
1.32%
Limit ng voltage drop
10%
Kabuuang correction factor
×1.00
Laki na itinakda ng
Current

Design aid lang ang resultang ito. I-verify ito laban sa kasalukuyang standard.

Mga hakbang ng kalkulasyon

  1. Ambient correction factor×1.00

    AS/NZS 3008.1.1:2025 Table 3.44 p.84

  2. Correction factor ng grouping×1.00

    One circuit, no grouping factor

  3. Total correction factor×1.00
  4. Kinakailangang current rating100A

    AS/NZS 3000:2018 Cl 3.4

  5. Limitasyon ng voltage drop10%

    AS/NZS 3008.1.1:2025 Cl 4.1.1

  6. Pinapayagang voltage drop4.8V

    AS/NZS 3008.1.1:2025 Cl 4.1.1

  7. Napiling laki ng conductorResulta35mm²

    AS/NZS 3008.1.1:2025 Table 3.21 p.54–55

  8. Current rating119A

    AS/NZS 3008.1.1:2025 Table 3.21 p.54–55

  9. Itinamang current rating Iz119A

    AS/NZS 3000:2018 Cl 3.4

  10. mV/A·m1.27mV/A·m

    AS/NZS 3008.1.1:2025 Table 4.16 p.123

  11. Voltage drop0.64V

    AS/NZS 3008.1.1:2025 Cl 4.7

  12. Voltage drop percent1.32%

Tungkol sa calculator na ito

How this is calculated

The tool tests every standard conductor size in turn. It reports the smallest size that passes the current check and the voltage drop check.

  1. Tabulated d.c. current. It reads the d.c. rating of each size for your cables, material, insulation and installation method. AS/NZS 3008.1.1:2025 prints these ratings for 40 °C air and 25 °C soil. The tool skips a size with no printed rating for the method.
  2. Correction factors. It multiplies the ambient, grouping, soil and burial depth factors into one correction factor (derating factor in 2017). One circuit alone takes no grouping factor. On a tray, ladder, rack or cleats, pick the cable support.
  3. Current check. It multiplies the rating by the correction factor to get Iz. The size passes when Iz is at or above the design current.
  4. Voltage drop. It multiplies the d.c. mV/A.m by the current and the route length, one way, and divides by 1000. The mV/A.m covers both conductors of the circuit.
  5. Limit. It compares the drop with the limit for the supply type. The limit follows the supply type until you type another one.
  6. Result. The candidate table shows each size, its Iz, its drop and the check it fails. The result says which check sets the size.
StepTable or clauseWhat it decides
d.c. rating, two single‑core cablesTables 3.21 and 3.22The current each size carries in your installation method
d.c. rating, one 2‑core cableTables 3.24 and 3.25The current each size carries in your installation method
AmbientTables 3.44 and 3.45, Cl 3.5.3The correction factor: Table 3.44 for air, Table 3.45 for soil
GroupingTables 3.33 to 3.36, 3.38, 3.40 and 3.42The correction factor for circuits run together, on a support too
Buried cableTables 3.46, 3.47 and 3.48The correction factors for depth and soil resistivity
Required currentAS/NZS 3000 Cl 3.4The current the cable must carry after correction
Voltage dropTables 4.16, 4.18, 4.21 and 4.23, Cl 4.7The drop over the route
LimitCl 4.1.1The limit for the supply type

Tables and clauses without a standard named are in AS/NZS 3008.1.1:2025.

Common circuits, worked with the tool

Each line states its route. Change one input and the size can change, so run your own circuit before you buy cable. Every line uses copper with PVC insulation and one circuit on the route. Each uses the Australian conditions, except where a line says otherwise.

  • Caravan, 30 A at 12 V over 6 m. One 2‑core cable, enclosed in air at 40 °C, against the 10 % ELV limit. It needs 10 mm² with a 0.8 V drop, 6.68 %. The drop sets the size, because 4 mm² carries the current but drops 16.8 %.
  • Battery to inverter, 100 A at 48 V over 5 m. Two single‑core cables, unenclosed and touching at 40 °C. It needs 35 mm² with a 0.64 V drop, 1.32 %. The current sets the size.
  • PV array feed, 15 A at 600 V over 40 m. One 2‑core XLPE cable, enclosed in air at 40 °C, against the 5 % network limit. It needs 1.5 mm² with a 20.82 V drop, 3.47 %. The drop sets the size, because 1 mm² carries the current but drops 5.41 %.
  • NZ battery to inverter, 100 A at 48 V over 5 m. The same route at 30 °C in New Zealand. It needs 25 mm² with a 0.89 V drop, 1.84 %. The current sets the size. The result is derived.

New Zealand

AS/NZS 3008.1.2:2017 has no d.c. ratings. For New Zealand, the tool uses the AS/NZS 3008.1.1:2025 d.c. ratings. It corrects them from 40 °C to the air temperature you enter, 30 °C by default. A buried run corrects from 25 °C to the soil temperature, 15 °C by default. No NZ table prints these figures, so the result says Derived.

What the tool does not check

The tool does not check the d.c. protective device. Check its rating against Iz. It does not check the prospective short-circuit current of a battery. Check the cable and the device against the battery maker's fault current.

To size the battery bank itself, use the battery calculator. To check a 4–20 mA loop on a d.c. supply, use the loop power budget. For an a.c. circuit, use the cable size calculator or the voltage drop calculator. To check the drop on a d.c. cable you have already chosen, use the d.c. mode of the voltage drop calculator. It works from the d.c. resistance, so its last digit can differ from this tool.

Mga tanong

Design aid ang resulta. I-verify ito laban sa kasalukuyang standard.

Anong laki ng cable para sa 48 V battery sa 100 A?

Ang run ay 5 m ng dalawang single‑core copper PVC cable, magkadikit, sa 40 °C sa Australia. Pinipili ng tool ang 35 mm². Ang corrected rating nitong Iz ay 119 A. Ang drop ay 0.64 V, o 1.32 %. Hindi pumapasa ang 25 mm² sa 97 A. Iba ang sagot kapag iba ang ruta.

Anong voltage drop ang pinapayagan sa d.c. circuit?

Itinatakda ng AS/NZS 3008.1.1:2025 Cl 4.1.1 ang limit ayon sa supply. Gumagamit ang tool ng 10 % para sa ELV na 120 V d.c. o mas mababa. Gumagamit ito ng 5 % para sa LV sa network at 7 % mula sa dedicated substation. Gumagamit ito ng 11 % para sa stand-alone system. Puwede kang mag-type ng ibang limit.

Bakit minarkahang derived ang resulta ko sa NZ?

Walang d.c. ratings ang AS/NZS 3008.1.2:2017. Para sa NZ, gumagamit ang tool ng d.c. ratings ng AS/NZS 3008.1.1:2025. Itinatama ito mula 40 °C patungo sa NZ ambient, 30 °C bilang default. Ibinibigay ng Tables 3.44 at 3.45 ang correction factor (derating factor noong 2017). Walang NZ table na naglilimbag ng resulta, kaya minamarkahan ito ng tool bilang derived.

Two single‑core o 2‑core?

Piliin ang Two single‑core cables para sa positive at negative run bilang hiwalay na cable. I-rate ang mga ito ng Tables 3.21 at 3.22. Piliin ang One 2‑core cable para sa isang sheathed cable na may dalawang conductor. I-rate ito ng Tables 3.24 at 3.25. Ibinibigay ng Tables 4.16, 4.18, 4.21 at 4.23 ang mV/A.m.

Ano ang hindi sinusuri ng DC cable size tool?

Hindi nito tinitingnan ang d.c. protective device. Tingnan ang device rating laban sa corrected rating Iz. Hindi rin nito tinitingnan ang prospective short-circuit current ng battery. Tingnan ang cable at device laban sa fault current ng battery maker.

Mga worked example

Lahat ng 7 na guide para sa calculator na ito

Background

Mga clause at table na binabasa ng tool na ito

Bawat clause at table, kasama kung paano ito na-verify

Huling na-check ang mga table noong 27 Sept 2026.