直流电缆截面计算器
新西兰和澳大利亚直流电缆截面计算器,适用于最高 1500 V 直流。读取 AS/NZS 3008.1.1:2025 的直流额定值及 mV/A.m。对于新西兰,将其修正至 30 °C,并将结果标注为推导值。
Reads AS/NZS 3008.1.1:2025 (AU). Tables checked 27 Sept 2026.
尝试一个工程 8
每项工作都会预填示例数值。请替换为您自己的数值。
- Size a battery cableThe d.c. cable size for a 3 m, 48 V battery run at 100 A.
- Size a PV string cableThe d.c. cable for 14 A at 600 V over 30 m.
- Size a 12 V run in a camperThe cable for 8 A at 12 V over 6 m at 3 %.
- Size a 24 V control supplyThe cable for 10 A at 24 V over 40 m.
- Size an array cable on a hot roofThe cable for 28 A at 1000 V and 60 °C.
- Size a battery inverter cableThe cable for 250 A at 48 V over 2 m.
- Size a buried array cableThe cable to a ground-mount array, buried 0.6 m.
- Size a 48 V telecom feedThe cable for 60 A at 48 V over 15 m.
输入
使用默认输入值的示例计算。
- 标准
- AU · AS/NZS 3008.1.1:2025
- 电压
- 48 V d.c.
- 设计电流
- 100 A
- 供电类型
- 特低电压,直流 120 V 或以下(10 %)
- 电压降限值
- 10 %
- 路径长度
- 5 m
- 敷设方式
- 无外壳,紧贴敷设
- 空气温度
- 40 °C
- 成组回路
- 1
- 成组布置
- 表面或封闭中成束敷设
- 电缆
- 两根单芯电缆
- 材料
- 铜
- 绝缘
- PVC 75 °C
导体规格
35mm²
- 修正后载流量 Iz
- 119A
- 电压降
- 0.64V
- 电压降百分比
- 1.32%
- 电压降限值
- 10%
- 总修正系数
- ×1.00
- 规格取决于
- 电流
此结果仅供设计参考。请对照现行标准进行核验。
计算步骤
- 环境温度修正系数×1.00
AS/NZS 3008.1.1:2025 Table 3.44 p.84
- 成组修正系数×1.00
One circuit, no grouping factor
- 总校正系数×1.00
- 所需额定电流100A
AS/NZS 3000:2018 Cl 3.4
- 电压降限值10%
AS/NZS 3008.1.1:2025 Cl 4.1.1
- 允许的电压降4.8V
AS/NZS 3008.1.1:2025 Cl 4.1.1
- 所选导体规格结果35mm²
AS/NZS 3008.1.1:2025 Table 3.21 p.54–55
- 额定电流119A
AS/NZS 3008.1.1:2025 Table 3.21 p.54–55
- 修正后的载流量 Iz119A
AS/NZS 3000:2018 Cl 3.4
- mV/A·m1.27mV/A·m
AS/NZS 3008.1.1:2025 Table 4.16 p.123
- 电压降0.64V
AS/NZS 3008.1.1:2025 Cl 4.7
- 电压降百分比1.32%
关于此计算器
How this is calculated
The tool tests every standard conductor size in turn. It reports the smallest size that passes the current check and the voltage drop check.
- Tabulated d.c. current. It reads the d.c. rating of each size for your cables, material, insulation and installation method. AS/NZS 3008.1.1:2025 prints these ratings for 40 °C air and 25 °C soil. The tool skips a size with no printed rating for the method.
- Correction factors. It multiplies the ambient, grouping, soil and burial depth factors into one correction factor (derating factor in 2017). One circuit alone takes no grouping factor. On a tray, ladder, rack or cleats, pick the cable support.
- Current check. It multiplies the rating by the correction factor to get Iz. The size passes when Iz is at or above the design current.
- Voltage drop. It multiplies the d.c. mV/A.m by the current and the route length, one way, and divides by 1000. The mV/A.m covers both conductors of the circuit.
- Limit. It compares the drop with the limit for the supply type. The limit follows the supply type until you type another one.
- Result. The candidate table shows each size, its Iz, its drop and the check it fails. The result says which check sets the size.
| Step | Table or clause | What it decides |
|---|---|---|
| d.c. rating, two single‑core cables | Tables 3.21 and 3.22 | The current each size carries in your installation method |
| d.c. rating, one 2‑core cable | Tables 3.24 and 3.25 | The current each size carries in your installation method |
| Ambient | Tables 3.44 and 3.45, Cl 3.5.3 | The correction factor: Table 3.44 for air, Table 3.45 for soil |
| Grouping | Tables 3.33 to 3.36, 3.38, 3.40 and 3.42 | The correction factor for circuits run together, on a support too |
| Buried cable | Tables 3.46, 3.47 and 3.48 | The correction factors for depth and soil resistivity |
| Required current | AS/NZS 3000 Cl 3.4 | The current the cable must carry after correction |
| Voltage drop | Tables 4.16, 4.18, 4.21 and 4.23, Cl 4.7 | The drop over the route |
| Limit | Cl 4.1.1 | The limit for the supply type |
Tables and clauses without a standard named are in AS/NZS 3008.1.1:2025.
Common circuits, worked with the tool
Each line states its route. Change one input and the size can change, so run your own circuit before you buy cable. Every line uses copper with PVC insulation and one circuit on the route. Each uses the Australian conditions, except where a line says otherwise.
- Caravan, 30 A at 12 V over 6 m. One 2‑core cable, enclosed in air at 40 °C, against the 10 % ELV limit. It needs 10 mm² with a 0.8 V drop, 6.68 %. The drop sets the size, because 4 mm² carries the current but drops 16.8 %.
- Battery to inverter, 100 A at 48 V over 5 m. Two single‑core cables, unenclosed and touching at 40 °C. It needs 35 mm² with a 0.64 V drop, 1.32 %. The current sets the size.
- PV array feed, 15 A at 600 V over 40 m. One 2‑core XLPE cable, enclosed in air at 40 °C, against the 5 % network limit. It needs 1.5 mm² with a 20.82 V drop, 3.47 %. The drop sets the size, because 1 mm² carries the current but drops 5.41 %.
- NZ battery to inverter, 100 A at 48 V over 5 m. The same route at 30 °C in New Zealand. It needs 25 mm² with a 0.89 V drop, 1.84 %. The current sets the size. The result is derived.
New Zealand
AS/NZS 3008.1.2:2017 has no d.c. ratings. For New Zealand, the tool uses the AS/NZS 3008.1.1:2025 d.c. ratings. It corrects them from 40 °C to the air temperature you enter, 30 °C by default. A buried run corrects from 25 °C to the soil temperature, 15 °C by default. No NZ table prints these figures, so the result says Derived.
What the tool does not check
The tool does not check the d.c. protective device. Check its rating against Iz. It does not check the prospective short-circuit current of a battery. Check the cable and the device against the battery maker's fault current.
To size the battery bank itself, use the battery calculator. To check a 4–20 mA loop on a d.c. supply, use the loop power budget. For an a.c. circuit, use the cable size calculator or the voltage drop calculator. To check the drop on a d.c. cable you have already chosen, use the d.c. mode of the voltage drop calculator. It works from the d.c. resistance, so its last digit can differ from this tool.
问题
结果仅供设计参考。请依据现行标准核对。
100 A 的 48 V 蓄电池需要多大的电缆?
线路为 5 m 长的两根单芯铜质 PVC 电缆,紧密相贴,位于澳大利亚,环境温度 40 °C。工具选定 35 mm²。其修正后的额定值 Iz 为 119 A。电压降为 0.64 V,即 1.32 %。25 mm² 在 97 A 时不合格。不同的敷设路径会得出不同的结果。
直流回路允许多大的电压降?
AS/NZS 3008.1.1:2025 Cl 4.1.1 按供电方式规定限值。对于直流 120 V 及以下的 ELV,本工具采用 10 %。对于电网供电的低压,采用 5 %;来自专用变电站时采用 7 %。独立系统采用 11 %。您可以输入其他限值。
为何我的新西兰结果被标记为衍生数据?
AS/NZS 3008.1.2:2017 不含直流额定值。对于新西兰,本工具采用 AS/NZS 3008.1.1:2025 的直流额定值,并将其由 40 °C 修正至新西兰环境温度(默认 30 °C)。Tables 3.44 and 3.45 给出修正系数(2017 版中为降容系数)。新西兰的任何表格均未直接给出结果,因此本工具将其标注为推导值。
单芯还是双芯?
正极和负极线路分别选择两根单芯电缆作为独立电缆。Tables 3.21 和 3.22 给出其额定值。选择一根 2 芯电缆,即一根带护套、包含两根导体的电缆,Tables 3.24 和 3.25 给出其额定值。Tables 4.16、4.18、4.21 和 4.23 给出 mV/A.m 值。
直流电缆截面工具不检查什么?
本工具不检查直流保护装置。请将保护装置额定值与修正后的额定值 Iz 进行比较。本工具也不检查蓄电池的预期短路电流。请将电缆和保护装置与蓄电池制造商的故障电流进行比对。
计算示例
- Arc flash at a 48 V home batteryClass a 48 V lithium home battery with 6 kA at its terminals by AS/NZS 5139, find its arc flash energy and PPE level, then bring it down with fuses.
- DC isolator rating for a 10 kW solar arrayRate the d.c. isolator and size the frame earth for a four-string domestic array. Check one data sheet that passes and one that fails per pole.
- Solar string sizing for a 600 V inverterHow many 49.5 V modules fit a string on a 600 V inverter at −5 °C? Work cold Voc, hot Vmp, the string current, fuses and the d.c. isolator by AS/NZS 5033.
- 12 V caravan cable: d.c. voltage dropA 12 V caravan feed at 30 A over 6 m, checked on 4, 6 and 10 mm² twin against the 10 % ELV limit, then a 48 V battery-to-inverter run.
- Solar battery size for a family home: 25 kWh a daySize a solar battery for a home that uses 25 kWh a day with an 8 kW array. Usable and nominal kWh, the bank, the inverter, winter solar and where it can go.
- DC cable size: 48 V battery and 600 V PV arrayTwo d.c. circuits sized to AS/NZS 3008.1.1:2025, a 48 V battery-to-inverter run that current sizes and a 600 V array feed that voltage drop sizes.
背景
- Home batteries and AS/NZS 5139How a home solar battery is sized in kWh, what usable, nominal, depth of discharge and round-trip efficiency mean, and where AS/NZS 5139 lets one go.
- AS/NZS 3008.1.1:2025: what the AU part coversWhat AS/NZS 3008.1.1:2025 covers, a.c. to 0.6/1 kV and d.c. to 1500 V at 40 °C air and 25 °C soil, how its sections run, and where the d.c. tables are.
- DC voltage drop and conductor resistanceWhy d.c. drop is 2 × I × R × L, why it has no reactance or power factor, and how the hot resistance, the cable tables, the limit and parallel cables change it.
- PV array isolators and earthingHow parallel strings feed a fault, what Ithe, Ie and make and break mean for a d.c. isolator, and how AS/NZS 5033 earths and alarms a PV array.
- PV string voltage and temperatureWhy a PV string's voltage rises in the cold and falls in the heat, how AS/NZS 5033 limits it, and how the string current, fuses and isolator follow.
本工具读取的条款和表格
- AS/NZS 3008.1.1:2025 Cl 3.5.3Ambient correction
- AS/NZS 3008.1.1:2025 Cl 4.1.1d.c. voltage drop limit
- AS/NZS 3008.1.1:2025 Cl 4.7d.c. voltage drop
- AS/NZS 3008.1.1:2025 Table 3.21Current ratings (d.c.), two single‑core cables, thermoplastic 75 °C
- AS/NZS 3008.1.1:2025 Table 3.22Current ratings (d.c.), two single‑core cables, cross-linked 90 °C
- AS/NZS 3008.1.1:2025 Table 3.24Current ratings (d.c.), 2‑core cable, thermoplastic 75 °C
- AS/NZS 3008.1.1:2025 Table 3.25Current ratings (d.c.), 2‑core cable, cross-linked 90 °C
- AS/NZS 3008.1.1:2025 Table 3.33, 3.36, 3.38, 3.40, 3.42Correction factors for bunched circuits, buried circuits and underground wiring enclosures
表格最后核对于 27 Sept 2026。