حاسبة مقاس كابل DC
حاسبة حجم كابل التيار المستمر لنيوزيلندا وأستراليا، حتى 1500 V تيار مستمر. تقرأ تصنيفات التيار المستمر في AS/NZS 3008.1.1:2025 وmV/A.m. ولـ NZ، تصححها إلى 30 °C وتعلّم النتيجة كمشتقة.
Reads AS/NZS 3008.1.1:2025 (AU). Tables checked 27 Sept 2026.
جرّب مشروعاً 8
تملأ كل مهمة قيماً توضيحية. استبدلها بقيمك.
- Size a battery cableThe d.c. cable size for a 3 m, 48 V battery run at 100 A.
- Size a PV string cableThe d.c. cable for 14 A at 600 V over 30 m.
- Size a 12 V run in a camperThe cable for 8 A at 12 V over 6 m at 3 %.
- Size a 24 V control supplyThe cable for 10 A at 24 V over 40 m.
- Size an array cable on a hot roofThe cable for 28 A at 1000 V and 60 °C.
- Size a battery inverter cableThe cable for 250 A at 48 V over 2 m.
- Size a buried array cableThe cable to a ground-mount array, buried 0.6 m.
- Size a 48 V telecom feedThe cable for 60 A at 48 V over 15 m.
المدخلات
مثال محلول بالمدخلات الافتراضية.
- المعيار
- AU · AS/NZS 3008.1.1:2025
- الجهد
- 48 V d.c.
- تيار التصميم
- 100 A
- نوع التغذية
- جهد منخفض جدًا ELV، 120 V تيار مستمر أو أقل (10 %)
- حد هبوط الجهد
- 10 %
- طول المسار
- 5 m
- طريقة التركيب
- بدون حاوية، متلامسة
- درجة حرارة الهواء
- 40 °C
- الدوائر المجمّعة
- 1
- ترتيب المجموعة
- متجمعة على سطح أو داخل غلاف
- الكابلات
- كابلان أحاديا القلب
- المادة
- النحاس
- العزل
- PVC 75 °C
حجم الموصل
35mm²
- التصنيف المصحح Iz
- 119A
- هبوط الجهد
- 0.64V
- نسبة هبوط الجهد
- 1.32%
- حد هبوط الجهد
- 10%
- معامل التصحيح الكلي
- ×1.00
- المقاس محدد بواسطة
- التيار
هذه النتيجة أداة للتصميم. تحقق منها وفق المعيار الحالي.
خطوات الحساب
- معامل تصحيح المحيط×1.00
AS/NZS 3008.1.1:2025 Table 3.44 p.84
- معامل تصحيح التجميع×1.00
One circuit, no grouping factor
- معامل التصحيح الكلي×1.00
- تصنيف التيار المطلوب100A
AS/NZS 3000:2018 Cl 3.4
- حد هبوط الجهد10%
AS/NZS 3008.1.1:2025 Cl 4.1.1
- هبوط الجهد المسموح به4.8V
AS/NZS 3008.1.1:2025 Cl 4.1.1
- مقاس الموصل المختارالنتيجة35mm²
AS/NZS 3008.1.1:2025 Table 3.21 p.54–55
- تصنيف التيار119A
AS/NZS 3008.1.1:2025 Table 3.21 p.54–55
- تصنيف التيار المصحح Iz119A
AS/NZS 3000:2018 Cl 3.4
- mV/A·m1.27mV/A·m
AS/NZS 3008.1.1:2025 Table 4.16 p.123
- هبوط الجهد0.64V
AS/NZS 3008.1.1:2025 Cl 4.7
- نسبة هبوط الجهد1.32%
حول هذه الحاسبة
How this is calculated
The tool tests every standard conductor size in turn. It reports the smallest size that passes the current check and the voltage drop check.
- Tabulated d.c. current. It reads the d.c. rating of each size for your cables, material, insulation and installation method. AS/NZS 3008.1.1:2025 prints these ratings for 40 °C air and 25 °C soil. The tool skips a size with no printed rating for the method.
- Correction factors. It multiplies the ambient, grouping, soil and burial depth factors into one correction factor (derating factor in 2017). One circuit alone takes no grouping factor. On a tray, ladder, rack or cleats, pick the cable support.
- Current check. It multiplies the rating by the correction factor to get Iz. The size passes when Iz is at or above the design current.
- Voltage drop. It multiplies the d.c. mV/A.m by the current and the route length, one way, and divides by 1000. The mV/A.m covers both conductors of the circuit.
- Limit. It compares the drop with the limit for the supply type. The limit follows the supply type until you type another one.
- Result. The candidate table shows each size, its Iz, its drop and the check it fails. The result says which check sets the size.
| Step | Table or clause | What it decides |
|---|---|---|
| d.c. rating, two single‑core cables | Tables 3.21 and 3.22 | The current each size carries in your installation method |
| d.c. rating, one 2‑core cable | Tables 3.24 and 3.25 | The current each size carries in your installation method |
| Ambient | Tables 3.44 and 3.45, Cl 3.5.3 | The correction factor: Table 3.44 for air, Table 3.45 for soil |
| Grouping | Tables 3.33 to 3.36, 3.38, 3.40 and 3.42 | The correction factor for circuits run together, on a support too |
| Buried cable | Tables 3.46, 3.47 and 3.48 | The correction factors for depth and soil resistivity |
| Required current | AS/NZS 3000 Cl 3.4 | The current the cable must carry after correction |
| Voltage drop | Tables 4.16, 4.18, 4.21 and 4.23, Cl 4.7 | The drop over the route |
| Limit | Cl 4.1.1 | The limit for the supply type |
Tables and clauses without a standard named are in AS/NZS 3008.1.1:2025.
Common circuits, worked with the tool
Each line states its route. Change one input and the size can change, so run your own circuit before you buy cable. Every line uses copper with PVC insulation and one circuit on the route. Each uses the Australian conditions, except where a line says otherwise.
- Caravan, 30 A at 12 V over 6 m. One 2‑core cable, enclosed in air at 40 °C, against the 10 % ELV limit. It needs 10 mm² with a 0.8 V drop, 6.68 %. The drop sets the size, because 4 mm² carries the current but drops 16.8 %.
- Battery to inverter, 100 A at 48 V over 5 m. Two single‑core cables, unenclosed and touching at 40 °C. It needs 35 mm² with a 0.64 V drop, 1.32 %. The current sets the size.
- PV array feed, 15 A at 600 V over 40 m. One 2‑core XLPE cable, enclosed in air at 40 °C, against the 5 % network limit. It needs 1.5 mm² with a 20.82 V drop, 3.47 %. The drop sets the size, because 1 mm² carries the current but drops 5.41 %.
- NZ battery to inverter, 100 A at 48 V over 5 m. The same route at 30 °C in New Zealand. It needs 25 mm² with a 0.89 V drop, 1.84 %. The current sets the size. The result is derived.
New Zealand
AS/NZS 3008.1.2:2017 has no d.c. ratings. For New Zealand, the tool uses the AS/NZS 3008.1.1:2025 d.c. ratings. It corrects them from 40 °C to the air temperature you enter, 30 °C by default. A buried run corrects from 25 °C to the soil temperature, 15 °C by default. No NZ table prints these figures, so the result says Derived.
What the tool does not check
The tool does not check the d.c. protective device. Check its rating against Iz. It does not check the prospective short-circuit current of a battery. Check the cable and the device against the battery maker's fault current.
To size the battery bank itself, use the battery calculator. To check a 4–20 mA loop on a d.c. supply, use the loop power budget. For an a.c. circuit, use the cable size calculator or the voltage drop calculator. To check the drop on a d.c. cable you have already chosen, use the d.c. mode of the voltage drop calculator. It works from the d.c. resistance, so its last digit can differ from this tool.
الأسئلة
النتيجة أداة للتصميم. تحقق منها وفق المعيار الحالي.
ما مقاس الكابل لبطارية 48 V عند 100 A؟
المسار هو 5 m من كابلين نحاسيين أحاديي القلب بعازل PVC، متلامسين، عند 40 °C في أستراليا. تختار الأداة 35 mm². قيمتها الاسمية المصحّحة Iz هي 119 A. الهبوط 0.64 V، أي 1.32 %. يكون 25 mm² غير مطابق عند 97 A. يعطي مسار مختلف نتيجة مختلفة.
ما هبوط الجهد المسموح به في دائرة التيار المستمر؟
يحدد AS/NZS 3008.1.1:2025 Cl 4.1.1 الحد وفق نوع التغذية. تستخدم الأداة 10 % للجهد المنخفض جداً ELV عند 120 V d.c. أو أقل. وتستخدم 5 % للجهد المنخفض LV على الشبكة، و7 % من محطة فرعية مخصصة. وتستخدم 11 % لنظام مستقل. يمكنك كتابة حد آخر.
لماذا تُوسم نتيجة NZ الخاصة بي بأنها مشتقة؟
لا تتضمن AS/NZS 3008.1.2:2017 قيماً اسمية للتيار المستمر. بالنسبة لنيوزيلندا، تستخدم الأداة القيم الاسمية للتيار المستمر في AS/NZS 3008.1.1:2025. وتصحّحها من 40 °C إلى درجة الحرارة المحيطة في نيوزيلندا، أي 30 °C افتراضياً. تعطي Tables 3.44 و3.45 معامل التصحيح (معامل التخفيض في نسخة 2017). لا يوجد جدول لنيوزيلندا يذكر النتيجة، لذلك تُعلّمها الأداة بأنها مشتقة.
أحادي القلب أم ثنائي القلب؟
اختر كابلين أحاديي القلب لمسار موجب وسالب ككابلين منفصلين. تقيّمهما Tables 3.21 و3.22. اختر كابلاً واحداً ثنائي القلب لكابل واحد مغلّف بالموصلين معاً. تقيّمه Tables 3.24 و3.25. تعطي Tables 4.16 و4.18 و4.21 و4.23 قيم mV/A.m.
ما الذي لا تفحصه أداة مقاس كابل DC؟
لا تتحقق الأداة من جهاز الحماية لتيار d.c. تحقّق من القيمة الاسمية للجهاز مقارنةً بالقيمة الاسمية المصحّحة Iz. ولا تتحقق الأداة من تيار قصر الدائرة المتوقع للبطارية. تحقّق من الكابل والجهاز مقارنةً بتيار العطل الذي يذكره صانع البطارية.
أمثلة محلولة
- Arc flash at a 48 V home batteryClass a 48 V lithium home battery with 6 kA at its terminals by AS/NZS 5139, find its arc flash energy and PPE level, then bring it down with fuses.
- DC isolator rating for a 10 kW solar arrayRate the d.c. isolator and size the frame earth for a four-string domestic array. Check one data sheet that passes and one that fails per pole.
- Solar string sizing for a 600 V inverterHow many 49.5 V modules fit a string on a 600 V inverter at −5 °C? Work cold Voc, hot Vmp, the string current, fuses and the d.c. isolator by AS/NZS 5033.
- 12 V caravan cable: d.c. voltage dropA 12 V caravan feed at 30 A over 6 m, checked on 4, 6 and 10 mm² twin against the 10 % ELV limit, then a 48 V battery-to-inverter run.
- Solar battery size for a family home: 25 kWh a daySize a solar battery for a home that uses 25 kWh a day with an 8 kW array. Usable and nominal kWh, the bank, the inverter, winter solar and where it can go.
- DC cable size: 48 V battery and 600 V PV arrayTwo d.c. circuits sized to AS/NZS 3008.1.1:2025, a 48 V battery-to-inverter run that current sizes and a 600 V array feed that voltage drop sizes.
الخلفية
- Home batteries and AS/NZS 5139How a home solar battery is sized in kWh, what usable, nominal, depth of discharge and round-trip efficiency mean, and where AS/NZS 5139 lets one go.
- AS/NZS 3008.1.1:2025: what the AU part coversWhat AS/NZS 3008.1.1:2025 covers, a.c. to 0.6/1 kV and d.c. to 1500 V at 40 °C air and 25 °C soil, how its sections run, and where the d.c. tables are.
- DC voltage drop and conductor resistanceWhy d.c. drop is 2 × I × R × L, why it has no reactance or power factor, and how the hot resistance, the cable tables, the limit and parallel cables change it.
- PV array isolators and earthingHow parallel strings feed a fault, what Ithe, Ie and make and break mean for a d.c. isolator, and how AS/NZS 5033 earths and alarms a PV array.
- PV string voltage and temperatureWhy a PV string's voltage rises in the cold and falls in the heat, how AS/NZS 5033 limits it, and how the string current, fuses and isolator follow.
البنود والجداول التي تقرأها هذه الأداة
- AS/NZS 3008.1.1:2025 Cl 3.5.3Ambient correction
- AS/NZS 3008.1.1:2025 Cl 4.1.1d.c. voltage drop limit
- AS/NZS 3008.1.1:2025 Cl 4.7d.c. voltage drop
- AS/NZS 3008.1.1:2025 Table 3.21Current ratings (d.c.), two single‑core cables, thermoplastic 75 °C
- AS/NZS 3008.1.1:2025 Table 3.22Current ratings (d.c.), two single‑core cables, cross-linked 90 °C
- AS/NZS 3008.1.1:2025 Table 3.24Current ratings (d.c.), 2‑core cable, thermoplastic 75 °C
- AS/NZS 3008.1.1:2025 Table 3.25Current ratings (d.c.), 2‑core cable, cross-linked 90 °C
- AS/NZS 3008.1.1:2025 Table 3.33, 3.36, 3.38, 3.40, 3.42Correction factors for bunched circuits, buried circuits and underground wiring enclosures
كل البنود والجداول، مع طريقة التحقق من كل منها
آخر فحص للجداول في 27 Sept 2026.
أدوات ذات صلة
هل كان هذا مفيداً؟