Skip to content
AmpSize

Existing circuit check

Check an installed circuit: cable, device, drop and Zs.

Reads AS/NZS 3008.1.2:2017 (NZ), AS/NZS 3008.1.1:2017 and 2025 (AU) and AS/NZS 3000:2018. Tables checked 27 Sept 2026.

Try a job 7

Each job fills in example values. Replace them with your values.

Inputs

Worked example with the default inputs. The live calculator replaces it when the page loads.

Phases
Single phase
Voltage
230 V
Design current
20 A
Power factor
0.9
Standard
NZ · AS/NZS 3008.1.2
Run length
30 m
Installation method
Enclosed in air
Ambient temperature
30 °C
Grouped circuits
1
Installed cable size
2.5 mm²
Material
Copper
Insulation
PVC 75 °C
Cores
Multicore
Cables in parallel
1
Voltage drop limit
5 %
External impedance Ze
0.35 Ω
Prospective fault current
0 kA
Device curve
Curve C
Device rating
20 A

Circuit on 2.5 mm²

Passes

Corrected rating Iz
23A
Voltage drop
4.25%
Earth fault loop impedance
0.89Ω
Maximum Zs for the device
1.53Ω
Smallest size that passes
2.5mm²
Largest curve C device the cable allows
20A
Combined correction factor
1x

This result is a design aid. Verify it against the current standard.

Calculation steps

  1. Installed conductor size2.5mm²

    AS/NZS 3008.1.2:2017 Table 13 p.62–64

  2. Tabulated rating of 2.5 mm²23A

    AS/NZS 3008.1.2:2017 Table 13 p.62–64

  3. Ambient correction factor1x

    AS/NZS 3008.1.2:2017 Tables 27(1), 27(2) p.88

  4. Grouping correction factor1x

    One circuit, no grouping factor

  5. Combined correction factor1x
  6. Corrected rating Iz23A

    AS/NZS 3000:2018 Cl 3.4

  7. Voltage drop9.78V
  8. Voltage drop percent4.25%

    AS/NZS 3000:2018 Cl 3.6.2

  9. Device rating In20A

    AS/NZS 3000:2018 Cl 2.5.3.1

  10. Earth conductor size2.5mm²

    AS/NZS 3000:2018 Table 5.1

  11. Earth fault loop impedance at 230 V phase to earth0.89Ω

    AS/NZS 3000:2018 Table 8.1

  12. Maximum Zs for the device1.53Ω

    AS/NZS 3000:2018 Table 8.1

  13. Smallest size that passes2.5mm²

    AS/NZS 3000:2018 Cl 3.4

About this calculator

How this is calculated

The tool takes a circuit that is already installed and runs the five checks of the cable size calculator at its size. It uses the same code, so the two tools agree on every size.

  1. Current capacity. It reads the tabulated rating of the installed size for your material, insulation, core count and installation method. It multiplies the rating by the correction factors for the route to get Iz. Iz must be at or above the design current Ib.
  2. Voltage drop. It works out the drop for the run length, the power factor and the conductor. It compares the drop with the limit you set.
  3. Breaker rating. The breaker rating In must sit between the two: Ib at or below In, and In at or below Iz. The tool gives both margins.
  4. Loop impedance. It adds the active and earth conductor resistance to the external impedance Ze. The total Zs must stay under the maximum for the breaker curve and rating.
  5. Fault withstand. If you enter a prospective fault current, the conductor must withstand it for the clearing time.
  6. Result. The circuit passes when every check it runs passes. The tool gives the smallest standard size that passes with the same breaker, and the largest breaker of the same curve that the cable allows.
StepTable or clauseWhat it decides
Current ratingTable 13 or 14 for multicore, Tables 4, 5, 7 and 8 for single coreThe tabulated rating of the installed size
Correction factorsTables 22 to 29 and Table 2The factors for the route
Voltage dropTables 30, 34 and 35, AS/NZS 3000 Cl 3.6.2The drop over the run and its limit
Breaker ratingAS/NZS 3000 Cl 2.5.3.1That In sits between Ib and Iz
Earth and ZsAS/NZS 3000 Table 5.1 and Table 8.1The earth conductor size and the maximum loop impedance
Fault withstandTable 52 and Cl 5.3The fault current the conductor survives

Tables without a standard named are in the part of AS/NZS 3008.1 you pick. AS/NZS 3008.1.1:2025 numbers them by section.

Common circuits, worked with the tool

Each line states its circuit. Every line uses multicore copper cable with PVC insulation and one circuit on the route, enclosed in air at 30 °C. Every breaker is a C curve and Ze is 0.35 Ω, on the New Zealand tables.

New Zealand and Australia

The Standard select picks the part of AS/NZS 3008.1 the tool reads. For Australia, the Edition select picks 2025 or the superseded 2017 edition. The breaker and Zs rules come from AS/NZS 3000, which is the same in both countries.

What the tool does not check

The tool works from the inputs, not from a test. Measure Ze and Zs on site and compare the reading with the maximum it gives. It does not check RCD rules or discrimination between breakers.

To size a new circuit, use the cable size calculator. To read the factors for a route on their own, use the correction factors calculator.

Questions

Each answer describes what this tool calculates. The result is a design aid. Verify against the current standard.

What size breaker can go on 4 mm² cable?

It depends on the route. Enclosed in 30 °C air on its own, 4 mm² copper rates 29 A in New Zealand, so a 25 A breaker is the largest standard size. Grouping, heat or insulation lowers it. Enter your route to read the largest breaker the cable allows.

What does Ib ≤ In ≤ Iz mean?

Ib is the design current of the load, In the breaker rating and Iz the cable rating after correction. The breaker must carry the load and the cable must carry the breaker rating. AS/NZS 3000 Clause 2.5.3.1 sets the rule.

Why does a long circuit fail on loop impedance?

A long or small cable has a high earth fault loop impedance. The fault current is then too low to trip the breaker on its magnetic setting in time. Use a larger cable, a lower breaker rating, a B curve, or check the RCD rules for the circuit.

Does the tool measure my circuit?

No. It works from the cable size, the route and the external impedance Ze you enter. Measure Ze and Zs on site and compare the reading with the maximum Zs the tool gives.

What size does the tool suggest when the circuit fails?

The smallest standard size that passes every check with the same breaker, route and load. It is the answer the cable size calculator gives for the same circuit.

Clauses and tables this tool reads

Every clause and table, with how each was verified

Tables last checked on 27 Sept 2026.

Was this useful?

A question, or a value that looks wrong? Contact us.